- VERTIV-V5-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- DisplayString, TruthValue, MacAddress FROM SNMPv2-TC
- SnmpAdminString FROM SNMP-FRAMEWORK-MIB
- MODULE-IDENTITY, OBJECT-TYPE, enterprises, Integer32,
- Gauge32, NOTIFICATION-TYPE, OBJECT-IDENTITY FROM SNMPv2-SMI
- sysName FROM SNMPv2-MIB;
- vertiv MODULE-IDENTITY
- LAST-UPDATED "202001070000Z"
- ORGANIZATION "Vertiv"
- CONTACT-INFO "support@geistglobal.com"
- DESCRIPTION
- "The MIB for Vertiv products"
- REVISION "202001070000Z"
- DESCRIPTION
- "Updates for VRC spec change"
- REVISION "201909300000Z"
- DESCRIPTION
- "Added hostname, alarm/warning count, and manufacturer to deviceInfo"
- REVISION "201909120000Z"
- DESCRIPTION
- "Added SN-2D door switch sensor"
- REVISION "201908300000Z"
- DESCRIPTION
- "Removed current min, max, and peak fields from pdu phase, line,
- breaker, and outlet tables
- Removed voltage min, max, and peak fields from pdu phase, line,
- breaker, and outlet tables
- Removed minmax reset value from pduOutletMeterReset
- Added balance field to pdu phase table"
- REVISION "201906060000Z"
- DESCRIPTION
- "Updated pduOutletSwitchControl description"
- REVISION "201905070000Z"
- DESCRIPTION
- "Changed productMacAddress type to MacAddress"
- REVISION "201904300000Z"
- DESCRIPTION
- "Added remote humidity-only sensor"
- REVISION "201903070000Z"
- DESCRIPTION
- "Added VRC support"
- REVISION "201801190000Z"
- DESCRIPTION
- "Modified pduOutletSwitchTable to support outlet actions with delays"
- REVISION "201709190000Z"
- DESCRIPTION
- "Changed SYNTAX of objects, with a UTF-8 encoded string value, to
- SnmpAdminString"
- REVISION "201708100000Z"
- DESCRIPTION
- "Added pduBreakerCurrentPeak, pduLineCurrentPeak,
- pduOutletMeterCurrentPeak, pduPhaseVoltagePeak, and
- pduPhaseCurrentPeak
- Updated object descriptions, indicating which fields are not supported
- on all platforms"
- REVISION "201705100000Z"
- DESCRIPTION
- "Added trapObj group with trap payload objects
- Added additional payload objects to trap definitions"
- REVISION "201704050000Z"
- DESCRIPTION
- "Added productPlatform to deviceInfo group
- Added product identity entries"
- REVISION "201606300000Z"
- DESCRIPTION
- "Raven version"
- REVISION "201209110000Z"
- DESCRIPTION
- "Original version"
- ::= { enterprises 21239 }
- v5 OBJECT IDENTIFIER ::= { vertiv 5 }
- imd OBJECT IDENTIFIER ::= { v5 2 }
- --###########################################################################################--
- --deviceInfo--
- --###########################################################################################--
- deviceInfo OBJECT IDENTIFIER ::= { imd 1 }
- productTitle OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product name"
- ::= { deviceInfo 1 }
- productVersion OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product version"
- ::= { deviceInfo 2 }
- productFriendlyName OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "User-assigned name"
- ::= { deviceInfo 3 }
- productMacAddress OBJECT-TYPE
- SYNTAX MacAddress
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product's unique MAC address"
- ::= { deviceInfo 4 }
- deviceCount OBJECT-TYPE
- SYNTAX Integer32(0..16)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Total number of devices on unit"
- ::= { deviceInfo 6 }
- temperatureUnits OBJECT-TYPE
- SYNTAX INTEGER {
- fahrenheit(0),
- celsius(1)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Current units for temperature/dewpoint values:
- 0 = Degrees Fahrenheit
- 1 = Degrees Celsius"
- ::= { deviceInfo 7 }
- productModelNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product model number (factory-assigned)"
- ::= { deviceInfo 8 }
- productPartNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product part number (factory-assigned)"
- ::= { deviceInfo 9 }
- productSerialNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product serial number (factory-assigned)"
- ::= { deviceInfo 10 }
- productPlatform OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product platform"
- ::= { deviceInfo 11 }
- productHostname OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product hostname"
- ::= { deviceInfo 12 }
- productAlarmCount OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Number of alarms currently tripped"
- ::= { deviceInfo 13 }
- productWarnCount OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Number of warnings currently tripped"
- ::= { deviceInfo 14 }
- productManufacturer OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product manufacturer"
- ::= { deviceInfo 15 }
- --###########################################################################################--
- --pdu--
- --###########################################################################################--
- pdu OBJECT IDENTIFIER ::= { imd 3 }
- --###########################################################################################--
- --pduMainTable--
- --###########################################################################################--
- pduMainTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduMainEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "PDU general information"
- ::= { pdu 1 }
- pduMainEntry OBJECT-TYPE
- SYNTAX PduMainEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduMainTable table: each entry contains an index
- and other sensor details"
- INDEX { pduMainIndex }
- ::= { pduMainTable 1 }
- PduMainEntry ::= SEQUENCE {
- pduMainIndex Integer32,
- pduMainSerial DisplayString,
- pduMainName SnmpAdminString,
- pduMainLabel SnmpAdminString,
- pduMainAvail Gauge32,
- pduMeterType INTEGER,
- pduTotalName SnmpAdminString,
- pduTotalLabel SnmpAdminString,
- pduTotalRealPower Gauge32,
- pduTotalApparentPower Gauge32,
- pduTotalPowerFactor Gauge32,
- pduTotalEnergy Gauge32
- }
- pduMainIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduMainEntry 1 }
- pduMainSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { pduMainEntry 2 }
- pduMainName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU name (factory-assigned)"
- ::= { pduMainEntry 3 }
- pduMainLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU label (user-defined)"
- ::= { pduMainEntry 4 }
- pduMainAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { pduMainEntry 5 }
- pduMeterType OBJECT-TYPE
- SYNTAX INTEGER {
- wye(0),
- delta(1)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current meter type:
- 0 = Wye
- 1 = Delta"
- ::= { pduMainEntry 6 }
- pduTotalName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Total name (factory-assigned)"
- ::= { pduMainEntry 7 }
- pduTotalLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Total label (user-defined)"
- ::= { pduMainEntry 8 }
- pduTotalRealPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU total real power"
- ::= { pduMainEntry 9 }
- pduTotalApparentPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "volt-amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU total apparent power"
- ::= { pduMainEntry 10 }
- pduTotalPowerFactor OBJECT-TYPE
- SYNTAX Gauge32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU total power factor"
- ::= { pduMainEntry 11 }
- pduTotalEnergy OBJECT-TYPE
- SYNTAX Gauge32(0..9999000)
- UNITS "watt-hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU total accumulated energy in watt-hours"
- ::= { pduMainEntry 12 }
- --###########################################################################################--
- --pduPhaseTable--
- --###########################################################################################--
- pduPhaseTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduPhaseEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "PDU phases information"
- ::= { pdu 2 }
- pduPhaseEntry OBJECT-TYPE
- SYNTAX PduPhaseEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduPhaseTable table: each entry contains an index
- and other sensor details"
- INDEX { pduPhaseIndex }
- ::= { pduPhaseTable 1 }
- PduPhaseEntry ::= SEQUENCE {
- pduPhaseIndex Integer32,
- pduPhaseName SnmpAdminString,
- pduPhaseLabel SnmpAdminString,
- pduPhaseVoltage Gauge32,
- pduPhaseCurrent Gauge32,
- pduPhaseRealPower Gauge32,
- pduPhaseApparentPower Gauge32,
- pduPhasePowerFactor Gauge32,
- pduPhaseEnergy Gauge32,
- pduPhaseBalance Gauge32,
- pduPhaseCurrentCrestFactor Gauge32
- }
- pduPhaseIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduPhaseEntry 1 }
- pduPhaseName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU phase name (factory-assigned)"
- ::= { pduPhaseEntry 2 }
- pduPhaseLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU phase label (user-defined)"
- ::= { pduPhaseEntry 3 }
- pduPhaseVoltage OBJECT-TYPE
- SYNTAX Gauge32(0..3100)
- UNITS "decivolts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU phase voltage in tenths of a volt"
- ::= { pduPhaseEntry 4 }
- pduPhaseCurrent OBJECT-TYPE
- SYNTAX Gauge32(0..9900)
- UNITS "centiamps (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU phase current reading in hundredths of an amp"
- ::= { pduPhaseEntry 8 }
- pduPhaseRealPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Real power for phase in watts"
- ::= { pduPhaseEntry 12 }
- pduPhaseApparentPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "volt-amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Apparent power for phase in volt-amps"
- ::= { pduPhaseEntry 13 }
- pduPhasePowerFactor OBJECT-TYPE
- SYNTAX Gauge32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power factor for phase"
- ::= { pduPhaseEntry 14 }
- pduPhaseEnergy OBJECT-TYPE
- SYNTAX Gauge32(0..9999000)
- UNITS "watt-hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Accumulated energy for phase in watt-hours"
- ::= { pduPhaseEntry 15 }
- pduPhaseBalance OBJECT-TYPE
- SYNTAX Gauge32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Phase balance as percent"
- ::= { pduPhaseEntry 17 }
- pduPhaseCurrentCrestFactor OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current crest factor for phase, in hundredths"
- ::= { pduPhaseEntry 19 }
- --###########################################################################################--
- --pduBreakerTable--
- --###########################################################################################--
- pduBreakerTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduBreakerEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "PDU breaker information"
- ::= { pdu 3 }
- pduBreakerEntry OBJECT-TYPE
- SYNTAX PduBreakerEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduBreakerTable table: each entry contains an index
- and other sensor details"
- INDEX { pduBreakerIndex }
- ::= { pduBreakerTable 1 }
- PduBreakerEntry ::= SEQUENCE {
- pduBreakerIndex Integer32,
- pduBreakerName SnmpAdminString,
- pduBreakerLabel SnmpAdminString,
- pduBreakerCurrent Gauge32,
- pduBreakerVoltage Gauge32,
- pduBreakerRealPower Gauge32,
- pduBreakerApparentPower Gauge32,
- pduBreakerPowerFactor Gauge32,
- pduBreakerEnergy Gauge32
- }
- pduBreakerIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduBreakerEntry 1 }
- pduBreakerName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU breaker name (factory-assigned)"
- ::= { pduBreakerEntry 2 }
- pduBreakerLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU breaker label (user-defined)"
- ::= { pduBreakerEntry 3 }
- pduBreakerCurrent OBJECT-TYPE
- SYNTAX Gauge32(0..9900)
- UNITS "centiamps (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU breaker current reading in hundredths of an amp"
- ::= { pduBreakerEntry 4 }
- pduBreakerVoltage OBJECT-TYPE
- SYNTAX Gauge32(0..3100)
- UNITS "decivolts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU breaker voltage in tenths of a volt. This object may not exist on
- all platforms, due to hardware differences."
- ::= { pduBreakerEntry 8 }
- pduBreakerRealPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Real power for breaker in watts. This object may not exist on all
- platforms, due to hardware differences."
- ::= { pduBreakerEntry 12 }
- pduBreakerApparentPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "volt-amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Apparent power for breaker in volt-amps. This object may not exist on
- all platforms, due to hardware differences."
- ::= { pduBreakerEntry 13 }
- pduBreakerPowerFactor OBJECT-TYPE
- SYNTAX Gauge32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power factor for breaker. This object may not exist on all platforms,
- due to hardware differences."
- ::= { pduBreakerEntry 14 }
- pduBreakerEnergy OBJECT-TYPE
- SYNTAX Gauge32(0..9999000)
- UNITS "watt-hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Accumulated energy for breaker in watt-hours. This object may not
- exist on all platforms, due to hardware differences."
- ::= { pduBreakerEntry 15 }
- --###########################################################################################--
- --pduLineTable--
- --###########################################################################################--
- pduLineTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduLineEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "PDU line current information"
- ::= { pdu 4 }
- pduLineEntry OBJECT-TYPE
- SYNTAX PduLineEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduLineTable table: each entry contains an index
- and other sensor details"
- INDEX { pduLineIndex }
- ::= { pduLineTable 1 }
- PduLineEntry ::= SEQUENCE {
- pduLineIndex Integer32,
- pduLineName SnmpAdminString,
- pduLineLabel SnmpAdminString,
- pduLineCurrent Gauge32
- }
- pduLineIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduLineEntry 1 }
- pduLineName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU line name (factory-assigned)"
- ::= { pduLineEntry 2 }
- pduLineLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU line label (user-defined)"
- ::= { pduLineEntry 3 }
- pduLineCurrent OBJECT-TYPE
- SYNTAX Gauge32(0..9900)
- UNITS "centiamps (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU line current reading in hundredths of an amp"
- ::= { pduLineEntry 4 }
- --###########################################################################################--
- --pduOutletSwitchTable--
- --###########################################################################################--
- pduOutletSwitchTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduOutletSwitchEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Data, config and control for outlets with switching"
- ::= { pdu 5 }
- pduOutletSwitchEntry OBJECT-TYPE
- SYNTAX PduOutletSwitchEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduOutletSwitchTable table: each entry contains an index
- and other sensor details"
- INDEX { pduOutletSwitchIndex }
- ::= { pduOutletSwitchTable 1 }
- PduOutletSwitchEntry ::= SEQUENCE {
- pduOutletSwitchIndex Integer32,
- pduOutletSwitchName SnmpAdminString,
- pduOutletSwitchLabel SnmpAdminString,
- pduOutletSwitchState INTEGER,
- pduOutletSwitchRelayFailure TruthValue,
- pduOutletSwitchControl INTEGER,
- pduOutletSwitchTimeToAction Integer32,
- pduOutletSwitchOnDelay Integer32,
- pduOutletSwitchOffDelay Integer32,
- pduOutletSwitchRebootDelay Integer32,
- pduOutletSwitchRebootHoldDelay Integer32,
- pduOutletSwitchPoaAction INTEGER,
- pduOutletSwitchPoaDelay Integer32
- }
- pduOutletSwitchIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduOutletSwitchEntry 1 }
- pduOutletSwitchName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU outlet name (factory-assigned)"
- ::= { pduOutletSwitchEntry 2 }
- pduOutletSwitchLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU outlet label (user-defined)"
- ::= { pduOutletSwitchEntry 3 }
- pduOutletSwitchState OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2),
- on2off(3),
- off2on(4),
- rebootOn(5),
- rebootOff(6),
- unavailable(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Switch state of the outlet:
- 1 = Outlet is on
- 2 = Outlet is off
- 3 = Outlet is on, but will turn off after a delay
- 4 = Outlet is off, but will turn on after a delay
- 5 = Starting reboot cycle, outlet is on, but will go to the
- rebootOff(6) state after a delay
- 6 = Rebooting, outlet is off, but it will turn on after a delay
- 7 = Cannot get outlet state"
- ::= { pduOutletSwitchEntry 4 }
- pduOutletSwitchRelayFailure OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Tells if the outlet relay has failed. In normal operation, the value
- will be false(2)."
- ::= { pduOutletSwitchEntry 5 }
- pduOutletSwitchControl OBJECT-TYPE
- SYNTAX INTEGER {
- cancel(1),
- on(2),
- onAfterDelay(3),
- off(4),
- offAfterDelay(5),
- reboot(6),
- rebootAfterDelay(7),
- none(8)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Used for manual control of the outlet. If the outlet is in manual
- mode, this field can be set to one of the following values:
- 1 = Cancel pending operation
- 2 = Turn outlet on
- 3 = After delay (pduOutletSwitchOnDelay), turn outlet on
- 4 = Turn outlet off
- 5 = After delay (pduOutletSwitchOffDelay), turn outlet off
- 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn
- outlet back on
- 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet
- When not in manual mode, setting this field will give an
- inconsistentValue error. Returns none(8) for all get requests."
- ::= { pduOutletSwitchEntry 6 }
- pduOutletSwitchTimeToAction OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Seconds until an outlet state change. The value of
- pduOutletSwitchState tells what state the outlet will be set, after
- the delay."
- ::= { pduOutletSwitchEntry 7 }
- pduOutletSwitchOnDelay OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Seconds to wait before powering on the outlet, during onAfterDelay(3)
- operation. Changing this value has no effect on pending actions."
- ::= { pduOutletSwitchEntry 8 }
- pduOutletSwitchOffDelay OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Seconds to wait before powering off the outlet, during
- offAfterDelay(5) operation. Changing this value has no effect on
- pending actions."
- ::= { pduOutletSwitchEntry 9 }
- pduOutletSwitchRebootDelay OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Seconds to wait before powering off the outlet, during
- rebootAfterDelay(7) operation. Changing this value has no effect on
- pending actions. See pduOutletSwitchControl for more info."
- ::= { pduOutletSwitchEntry 10 }
- pduOutletSwitchRebootHoldDelay OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Seconds to hold the outlet off, before powering on the outlet, during
- rebootAfterDelay(7) operation. Changing this value has no effect on
- pending actions. See pduOutletSwitchControl for more info."
- ::= { pduOutletSwitchEntry 11 }
- pduOutletSwitchPoaAction OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2),
- last(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The outlet is set to this state during power-up. The action can be
- have one the following values:
- 1 = Outlet will be turned on
- 2 = Outlet will stay off
- 3 = Outlet will be set to last known state"
- ::= { pduOutletSwitchEntry 12 }
- pduOutletSwitchPoaDelay OBJECT-TYPE
- SYNTAX Integer32(0..600)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Seconds to wait before setting the outlet to the
- pduOutletSwitchPoaAction state. The delay starts at power-up."
- ::= { pduOutletSwitchEntry 13 }
- --###########################################################################################--
- --pduOutletMeterTable--
- --###########################################################################################--
- pduOutletMeterTable OBJECT-TYPE
- SYNTAX SEQUENCE OF PduOutletMeterEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Metering data for outlets that support this feature"
- ::= { pdu 6 }
- pduOutletMeterEntry OBJECT-TYPE
- SYNTAX PduOutletMeterEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the pduOutletMeterTable table: each entry contains an index
- and other sensor details"
- INDEX { pduOutletMeterIndex }
- ::= { pduOutletMeterTable 1 }
- PduOutletMeterEntry ::= SEQUENCE {
- pduOutletMeterIndex Integer32,
- pduOutletMeterName SnmpAdminString,
- pduOutletMeterLabel SnmpAdminString,
- pduOutletMeterVoltage Gauge32,
- pduOutletMeterCurrent Gauge32,
- pduOutletMeterRealPower Gauge32,
- pduOutletMeterApparentPower Gauge32,
- pduOutletMeterPowerFactor Gauge32,
- pduOutletMeterEnergy Gauge32,
- pduOutletMeterReset INTEGER,
- pduOutletCurrentCrestFactor Gauge32
- }
- pduOutletMeterIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { pduOutletMeterEntry 1 }
- pduOutletMeterName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU outlet name (factory-assigned)"
- ::= { pduOutletMeterEntry 2 }
- pduOutletMeterLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "PDU outlet label (user-defined)"
- ::= { pduOutletMeterEntry 3 }
- pduOutletMeterVoltage OBJECT-TYPE
- SYNTAX Gauge32(0..3100)
- UNITS "decivolts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU outlet voltage in tenths of a volt"
- ::= { pduOutletMeterEntry 4 }
- pduOutletMeterCurrent OBJECT-TYPE
- SYNTAX Gauge32(0..9900)
- UNITS "centiamps (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "PDU outlet current reading in hundredths of an amp"
- ::= { pduOutletMeterEntry 8 }
- pduOutletMeterRealPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Real power for outlet in watts"
- ::= { pduOutletMeterEntry 12 }
- pduOutletMeterApparentPower OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- UNITS "volt-amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Apparent power for outlet in volt-amps"
- ::= { pduOutletMeterEntry 13 }
- pduOutletMeterPowerFactor OBJECT-TYPE
- SYNTAX Gauge32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power factor for outlet"
- ::= { pduOutletMeterEntry 14 }
- pduOutletMeterEnergy OBJECT-TYPE
- SYNTAX Gauge32(0..9999000)
- UNITS "watt-hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Accumulated energy for outlet in watt-hours"
- ::= { pduOutletMeterEntry 15 }
- pduOutletMeterReset OBJECT-TYPE
- SYNTAX INTEGER {
- resetEnergy(1),
- none(8)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Used to reset energy. If read, the value is none(8). It can be set to
- resetEnergy(1), which sets outlet energy to 0"
- ::= { pduOutletMeterEntry 16 }
- pduOutletCurrentCrestFactor OBJECT-TYPE
- SYNTAX Gauge32(0..9999)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current crest factor for outlet, in hundredths"
- ::= { pduOutletMeterEntry 19 }
- --###########################################################################################--
- --tempSensorTable--
- --###########################################################################################--
- tempSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF TempSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature (RT) sensor"
- ::= { imd 4 }
- tempSensorEntry OBJECT-TYPE
- SYNTAX TempSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the tempSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { tempSensorIndex }
- ::= { tempSensorTable 1 }
- TempSensorEntry ::= SEQUENCE {
- tempSensorIndex Integer32,
- tempSensorSerial DisplayString,
- tempSensorLabel SnmpAdminString,
- tempSensorAvail Gauge32,
- tempSensorTemp Integer32
- }
- tempSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { tempSensorEntry 1 }
- tempSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { tempSensorEntry 2 }
- tempSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { tempSensorEntry 3 }
- tempSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { tempSensorEntry 4 }
- tempSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Temperature in tenths of a degree. Units are given by temperatureUnits
- field in deviceInfo."
- ::= { tempSensorEntry 5 }
- --###########################################################################################--
- --airFlowSensorTable--
- --###########################################################################################--
- airFlowSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFlowSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor"
- ::= { imd 5 }
- airFlowSensorEntry OBJECT-TYPE
- SYNTAX AirFlowSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the airFlowSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { airFlowSensorIndex }
- ::= { airFlowSensorTable 1 }
- AirFlowSensorEntry ::= SEQUENCE {
- airFlowSensorIndex Integer32,
- airFlowSensorSerial DisplayString,
- airFlowSensorLabel SnmpAdminString,
- airFlowSensorAvail Gauge32,
- airFlowSensorTemp Integer32,
- airFlowSensorFlow Integer32,
- airFlowSensorHumidity Integer32,
- airFlowSensorDewPoint Integer32
- }
- airFlowSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { airFlowSensorEntry 1 }
- airFlowSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { airFlowSensorEntry 2 }
- airFlowSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { airFlowSensorEntry 3 }
- airFlowSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { airFlowSensorEntry 4 }
- airFlowSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Temperature reading in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { airFlowSensorEntry 5 }
- airFlowSensorFlow OBJECT-TYPE
- SYNTAX Integer32(0..100)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Airflow reading. Still air will be less than 20, while rushing air
- will be around 100."
- ::= { airFlowSensorEntry 6 }
- airFlowSensorHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity reading"
- ::= { airFlowSensorEntry 7 }
- airFlowSensorDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Dewpoint reading in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { airFlowSensorEntry 8 }
- --###########################################################################################--
- --t3hdSensorTable--
- --###########################################################################################--
- t3hdSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF T3hdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature x 3, Humidity and Dewpoint Sensor"
- ::= { imd 8 }
- t3hdSensorEntry OBJECT-TYPE
- SYNTAX T3hdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the t3hdSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { t3hdSensorIndex }
- ::= { t3hdSensorTable 1 }
- T3hdSensorEntry ::= SEQUENCE {
- t3hdSensorIndex Integer32,
- t3hdSensorSerial DisplayString,
- t3hdSensorLabel SnmpAdminString,
- t3hdSensorAvail Gauge32,
- t3hdSensorIntLabel SnmpAdminString,
- t3hdSensorIntTemp Integer32,
- t3hdSensorIntHumidity Integer32,
- t3hdSensorIntDewPoint Integer32,
- t3hdSensorExtAAvail Gauge32,
- t3hdSensorExtALabel SnmpAdminString,
- t3hdSensorExtATemp Integer32,
- t3hdSensorExtBAvail Gauge32,
- t3hdSensorExtBLabel SnmpAdminString,
- t3hdSensorExtBTemp Integer32
- }
- t3hdSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { t3hdSensorEntry 1 }
- t3hdSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { t3hdSensorEntry 2 }
- t3hdSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { t3hdSensorEntry 3 }
- t3hdSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { t3hdSensorEntry 4 }
- t3hdSensorIntLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Internal label (user-defined)"
- ::= { t3hdSensorEntry 5 }
- t3hdSensorIntTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal temperature in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 6 }
- t3hdSensorIntHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal humidity"
- ::= { t3hdSensorEntry 7 }
- t3hdSensorIntDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal dewpoint in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 8 }
- t3hdSensorExtAAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External A status:
- 0 = Unavailable
- 1 = Available"
- ::= { t3hdSensorEntry 9 }
- t3hdSensorExtALabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "External A label (user-defined)"
- ::= { t3hdSensorEntry 10 }
- t3hdSensorExtATemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External A temperature in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 11 }
- t3hdSensorExtBAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External B status:
- 0 = Unavailable
- 1 = Available"
- ::= { t3hdSensorEntry 12 }
- t3hdSensorExtBLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "External B label (user-defined)"
- ::= { t3hdSensorEntry 13 }
- t3hdSensorExtBTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External B temperature in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 14 }
- --###########################################################################################--
- --thdSensorTable--
- --###########################################################################################--
- thdSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ThdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature, Humidity, and Dewpoint (THD) Sensor"
- ::= { imd 9 }
- thdSensorEntry OBJECT-TYPE
- SYNTAX ThdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the thdSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { thdSensorIndex }
- ::= { thdSensorTable 1 }
- ThdSensorEntry ::= SEQUENCE {
- thdSensorIndex Integer32,
- thdSensorSerial DisplayString,
- thdSensorLabel SnmpAdminString,
- thdSensorAvail Gauge32,
- thdSensorTemp Integer32,
- thdSensorHumidity Integer32,
- thdSensorDewPoint Integer32
- }
- thdSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { thdSensorEntry 1 }
- thdSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { thdSensorEntry 2 }
- thdSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { thdSensorEntry 3 }
- thdSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { thdSensorEntry 4 }
- thdSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Temperature value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { thdSensorEntry 5 }
- thdSensorHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity value"
- ::= { thdSensorEntry 6 }
- thdSensorDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Dewpoint value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { thdSensorEntry 7 }
- --###########################################################################################--
- --a2dSensorTable--
- --###########################################################################################--
- a2dSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF A2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Analog measurement (A2D) sensor (voltage, current, or dry-contact)"
- ::= { imd 11 }
- a2dSensorEntry OBJECT-TYPE
- SYNTAX A2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the a2dSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { a2dSensorIndex }
- ::= { a2dSensorTable 1 }
- A2dSensorEntry ::= SEQUENCE {
- a2dSensorIndex Integer32,
- a2dSensorSerial DisplayString,
- a2dSensorLabel SnmpAdminString,
- a2dSensorAvail Gauge32,
- a2dSensorValue Integer32,
- a2dSensorDisplayValue SnmpAdminString,
- a2dSensorMode INTEGER,
- a2dSensorUnits SnmpAdminString,
- a2dSensorMin Integer32,
- a2dSensorMax Integer32,
- a2dSensorLowLabel SnmpAdminString,
- a2dSensorHighLabel SnmpAdminString,
- a2dSensorAnalogLabel SnmpAdminString
- }
- a2dSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { a2dSensorEntry 1 }
- a2dSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { a2dSensorEntry 2 }
- a2dSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { a2dSensorEntry 3 }
- a2dSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { a2dSensorEntry 4 }
- a2dSensorValue OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Analog measurement value, within either a user-defined or preset
- range, depending on a2dSensorMode."
- ::= { a2dSensorEntry 5 }
- a2dSensorDisplayValue OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "For current/voltage modes, the analog value is given as a string. In
- binary modes, the value is either a2dSensorLowLabel or
- a2dSensorHighLabel, based on a2dSensorValue."
- ::= { a2dSensorEntry 6 }
- a2dSensorMode OBJECT-TYPE
- SYNTAX INTEGER {
- door(1),
- powerFailure(2),
- flood(3),
- wscLeak(4),
- wscFault(5),
- smoke(6),
- ivsNegGnd(7),
- ivsPosGnd(8),
- customVoltage(9),
- customBinary(10),
- customCurrent(11)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Binary modes have two states represented by the values 0 (low) or 1
- (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel.
- Current and voltage modes provide a scaled value from a2dSensorMin to
- a2dSensorMax.
- Analog modes:
- 1 = Door (binary)
- 2 = Power failure (binary)
- 3 = Flood (binary)
- 4 = Water-sensing cable leak (binary)
- 5 = Water-sensing cable fault (binary)
- 6 = Smoke alarm (binary)
- 7 = Isolated voltage negative ground (voltage)
- 8 = Isolated voltage positive ground (voltage)
- 9 = Custom voltage (voltage)
- 10 = Custom binary (binary)
- 11 = Custom current (current)"
- ::= { a2dSensorEntry 7 }
- a2dSensorUnits OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..7))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The units for the analog value. If a2dSensorMode is customVoltage(9)
- or customCurrent(11), then this field has a user-defined value.
- Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 8 }
- a2dSensorMin OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum analog value, given as an integer. The analog measurement is
- scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
- customVoltage(9) or customCurrent(11), then this field has a user-
- defined value. Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 9 }
- a2dSensorMax OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Maximum analog value, given as an integer. The analog measurement is
- scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
- customVoltage(9) or customCurrent(11), then this field has a user-
- defined value. Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 10 }
- a2dSensorLowLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Label for 0 (low) binary value. This field is only applicable if
- a2dSensorMode is one of the binary modes. If a2dSensorMode is
- customBinary(10), then this field is user-defined. Otherwise, it has a
- pre-defined value based on the mode."
- ::= { a2dSensorEntry 11 }
- a2dSensorHighLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Label for 1 (high) binary value. The field is only applicable if
- a2dSensorMode is one of the binary modes. If a2dSensorMode is
- customBinary(10), then this field is user-defined. Otherwise, it has a
- pre-defined value based on the mode."
- ::= { a2dSensorEntry 12 }
- a2dSensorAnalogLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Label for the analog measurement"
- ::= { a2dSensorEntry 13 }
- --###########################################################################################--
- --humiditySensorTable--
- --###########################################################################################--
- humiditySensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF HumiditySensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote humidity sensor"
- ::= { imd 12 }
- humiditySensorEntry OBJECT-TYPE
- SYNTAX HumiditySensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the humiditySensorTable table: each entry contains an index
- and other sensor details"
- INDEX { humiditySensorIndex }
- ::= { humiditySensorTable 1 }
- HumiditySensorEntry ::= SEQUENCE {
- humiditySensorIndex Integer32,
- humiditySensorSerial DisplayString,
- humiditySensorLabel SnmpAdminString,
- humiditySensorAvail Gauge32,
- humiditySensorValue Integer32
- }
- humiditySensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { humiditySensorEntry 1 }
- humiditySensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { humiditySensorEntry 2 }
- humiditySensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { humiditySensorEntry 3 }
- humiditySensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { humiditySensorEntry 4 }
- humiditySensorValue OBJECT-TYPE
- SYNTAX Integer32(0..100)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity value"
- ::= { humiditySensorEntry 5 }
- --###########################################################################################--
- --sn2dSensorTable--
- --###########################################################################################--
- sn2dSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Sn2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "2 Door Switch Sensor (SN-2D)"
- ::= { imd 13 }
- sn2dSensorEntry OBJECT-TYPE
- SYNTAX Sn2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the sn2dSensorTable table: each entry contains an index
- and other sensor details"
- INDEX { sn2dSensorIndex }
- ::= { sn2dSensorTable 1 }
- Sn2dSensorEntry ::= SEQUENCE {
- sn2dSensorIndex Integer32,
- sn2dSensorSerial DisplayString,
- sn2dSensorLabel SnmpAdminString,
- sn2dSensorAvail Gauge32,
- sn2dSensorDoor1Label SnmpAdminString,
- sn2dSensorDoor1State INTEGER,
- sn2dSensorDoor1DisplayState SnmpAdminString,
- sn2dSensorDoor2Label SnmpAdminString,
- sn2dSensorDoor2State INTEGER,
- sn2dSensorDoor2DisplayState SnmpAdminString
- }
- sn2dSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { sn2dSensorEntry 1 }
- sn2dSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { sn2dSensorEntry 2 }
- sn2dSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { sn2dSensorEntry 3 }
- sn2dSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { sn2dSensorEntry 4 }
- sn2dSensorDoor1Label OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Door switch 1 label"
- ::= { sn2dSensorEntry 5 }
- sn2dSensorDoor1State OBJECT-TYPE
- SYNTAX INTEGER {
- open(1),
- closed(2)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Door switch 1 state:
- 1 = open
- 2 = closed"
- ::= { sn2dSensorEntry 6 }
- sn2dSensorDoor1DisplayState OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Door switch 1 state given as a string"
- ::= { sn2dSensorEntry 7 }
- sn2dSensorDoor2Label OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Door switch 2 label"
- ::= { sn2dSensorEntry 8 }
- sn2dSensorDoor2State OBJECT-TYPE
- SYNTAX INTEGER {
- open(1),
- closed(2)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Door switch 2 state:
- 1 = open
- 2 = closed"
- ::= { sn2dSensorEntry 9 }
- sn2dSensorDoor2DisplayState OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Door switch 2 state given as a string"
- ::= { sn2dSensorEntry 10 }
- --###########################################################################################--
- --cooling--
- --###########################################################################################--
- cooling OBJECT IDENTIFIER ::= { imd 30 }
- --###########################################################################################--
- --vrc--
- --###########################################################################################--
- vrc OBJECT IDENTIFIER ::= { cooling 1 }
- --###########################################################################################--
- --vrcMainTable--
- --###########################################################################################--
- vrcMainTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcMainEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains general VRC information"
- ::= { vrc 1 }
- vrcMainEntry OBJECT-TYPE
- SYNTAX VrcMainEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcMainTable: each entry represents a VRC device"
- INDEX { vrcMainIndex }
- ::= { vrcMainTable 1 }
- VrcMainEntry ::= SEQUENCE {
- vrcMainIndex Integer32,
- vrcMainSerial DisplayString,
- vrcMainName SnmpAdminString,
- vrcMainLabel SnmpAdminString,
- vrcMainAvail Gauge32
- }
- vrcMainIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcMainEntry 1 }
- vrcMainSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial number"
- ::= { vrcMainEntry 2 }
- vrcMainName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "VRC name (factory-assigned)"
- ::= { vrcMainEntry 3 }
- vrcMainLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "VRC label (user-defined)"
- ::= { vrcMainEntry 4 }
- vrcMainAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { vrcMainEntry 5 }
- --###########################################################################################--
- --vrcMainPtTable--
- --###########################################################################################--
- vrcMainPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcMainPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains general VRC status"
- ::= { vrc 2 }
- vrcMainPtEntry OBJECT-TYPE
- SYNTAX VrcMainPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcMainPtTable: each entry contains status data for a VRC
- device"
- INDEX { vrcMainPtIndex }
- ::= { vrcMainPtTable 1 }
- VrcMainPtEntry ::= SEQUENCE {
- vrcMainPtIndex Integer32,
- vrcMainPtRunState INTEGER,
- vrcMainPtEevOpened Integer32,
- vrcMainPtAlarmNumbers Integer32,
- vrcMainPtHistoryAlarmNumbers Integer32,
- vrcMainPtHpAbnRecordCnt Integer32,
- vrcMainPtMonitorBaudrate INTEGER,
- vrcMainPtMonitorAddress Integer32,
- vrcMainPtLp TruthValue,
- vrcMainPtFilterMaintRemind TruthValue,
- vrcMainPtCoolingFlag TruthValue,
- vrcMainPtFirstOnFlag TruthValue,
- vrcMainPtNewAlarmFlag TruthValue,
- vrcMainPtComAlarmOutState TruthValue,
- vrcMainPtHighWaterInput TruthValue,
- vrcMainPtHighWaterAlarm TruthValue,
- vrcMainPtWaterUnderFloorAlarm TruthValue,
- vrcMainPtSwShutDownStatus TruthValue,
- vrcMainPtRemoteShutdown TruthValue,
- vrcMainPtRemoteShutDownFlag TruthValue,
- vrcMainPtRemoteShutDownAlarm TruthValue,
- vrcMainPtHmiShutDownFlag TruthValue,
- vrcMainPtLpAlarm TruthValue,
- vrcMainPtHpAlarm TruthValue,
- vrcMainPtLpFreqAlarm TruthValue,
- vrcMainPtHpFreqAlarm TruthValue,
- vrcMainPtLpSensorFailAlarm TruthValue,
- vrcMainPtHpSensorFailAlarm TruthValue,
- vrcMainPtEevCommFailAlarm TruthValue
- }
- vrcMainPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcMainPtEntry 1 }
- vrcMainPtRunState OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "VRC run state:
- 1 = on
- 2 = off"
- ::= { vrcMainPtEntry 2 }
- vrcMainPtEevOpened OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Eev opened value (percent)"
- ::= { vrcMainPtEntry 3 }
- vrcMainPtAlarmNumbers OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Alarm numbers value"
- ::= { vrcMainPtEntry 4 }
- vrcMainPtHistoryAlarmNumbers OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "History alarm numbers value"
- ::= { vrcMainPtEntry 5 }
- vrcMainPtHpAbnRecordCnt OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Hp Abnormal record count"
- ::= { vrcMainPtEntry 6 }
- vrcMainPtMonitorBaudrate OBJECT-TYPE
- SYNTAX INTEGER {
- error(1),
- baud1200(2),
- baud2400(3),
- baud4800(4),
- baud9600(5),
- baud19200(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Monitor baud rate:
- 1 = error
- 2 = 1200
- 3 = 2400
- 4 = 4800
- 5 = 9600
- 6 = 19200"
- ::= { vrcMainPtEntry 7 }
- vrcMainPtMonitorAddress OBJECT-TYPE
- SYNTAX Integer32(1..247)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Monitor address"
- ::= { vrcMainPtEntry 8 }
- vrcMainPtLp OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Lp status"
- ::= { vrcMainPtEntry 9 }
- vrcMainPtFilterMaintRemind OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Filter maintenance reminder status"
- ::= { vrcMainPtEntry 10 }
- vrcMainPtCoolingFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Cooling flag"
- ::= { vrcMainPtEntry 11 }
- vrcMainPtFirstOnFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "First on flag"
- ::= { vrcMainPtEntry 12 }
- vrcMainPtNewAlarmFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "New alarm flag"
- ::= { vrcMainPtEntry 13 }
- vrcMainPtComAlarmOutState OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Common alarm output state"
- ::= { vrcMainPtEntry 14 }
- vrcMainPtHighWaterInput OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "High water input"
- ::= { vrcMainPtEntry 15 }
- vrcMainPtHighWaterAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "High water alarm status"
- ::= { vrcMainPtEntry 16 }
- vrcMainPtWaterUnderFloorAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Water under floor alarm status"
- ::= { vrcMainPtEntry 17 }
- vrcMainPtSwShutDownStatus OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Software shutdown status"
- ::= { vrcMainPtEntry 18 }
- vrcMainPtRemoteShutdown OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Remote shutdown status"
- ::= { vrcMainPtEntry 19 }
- vrcMainPtRemoteShutDownFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Remote shutdown flag"
- ::= { vrcMainPtEntry 20 }
- vrcMainPtRemoteShutDownAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Remote shutdown alarm status"
- ::= { vrcMainPtEntry 21 }
- vrcMainPtHmiShutDownFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Hmi shutdown flag"
- ::= { vrcMainPtEntry 22 }
- vrcMainPtLpAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Low pressure alarm status"
- ::= { vrcMainPtEntry 23 }
- vrcMainPtHpAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "High pressure alarm status"
- ::= { vrcMainPtEntry 24 }
- vrcMainPtLpFreqAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Low pressure frequently alarm status"
- ::= { vrcMainPtEntry 25 }
- vrcMainPtHpFreqAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "High pressure frequently alarm status"
- ::= { vrcMainPtEntry 26 }
- vrcMainPtLpSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Low pressure sensor failure alarm status"
- ::= { vrcMainPtEntry 27 }
- vrcMainPtHpSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "High pressure sensor failure alarm status"
- ::= { vrcMainPtEntry 28 }
- vrcMainPtEevCommFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Eev communication failure alarm status"
- ::= { vrcMainPtEntry 29 }
- --###########################################################################################--
- --vrcMainCfgTable--
- --###########################################################################################--
- vrcMainCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcMainCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains general VRC configuration"
- ::= { vrc 3 }
- vrcMainCfgEntry OBJECT-TYPE
- SYNTAX VrcMainCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcMainCfgTable: each entry contains general config
- fields for a VRC device"
- INDEX { vrcMainCfgIndex }
- ::= { vrcMainCfgTable 1 }
- VrcMainCfgEntry ::= SEQUENCE {
- vrcMainCfgIndex Integer32,
- vrcMainCfgModelSelect INTEGER,
- vrcMainCfgSystemTimeYear Integer32,
- vrcMainCfgSystemTimeMonth Integer32,
- vrcMainCfgSystemTimeDay Integer32,
- vrcMainCfgSystemTimeHour Integer32,
- vrcMainCfgSystemTimeMin Integer32,
- vrcMainCfgSystemTimeSec Integer32,
- vrcMainCfgEevShtSettingMin Integer32,
- vrcMainCfgEevShtSettingMax Integer32,
- vrcMainCfgEevValveCloseSht Integer32,
- vrcMainCfgEevMopPressSetting Integer32,
- vrcMainCfgLpdt Integer32,
- vrcMainCfgDeadBand Integer32,
- vrcMainCfgOnOffSwitch TruthValue,
- vrcMainCfgVacuumState TruthValue,
- vrcMainCfgControlMode INTEGER,
- vrcMainCfgManualRunEnable TruthValue,
- vrcMainCfgRemShutdownInput TruthValue,
- vrcMainCfgMonitorShutDownFlag TruthValue,
- vrcMainCfgFirstOnPassword Integer32,
- vrcMainCfgFilterMaintSetting TruthValue,
- vrcMainCfgFilterMaintRemindTime Integer32,
- vrcMainCfgFilterMaintRemindCtrl INTEGER,
- vrcMainCfgCommonAlarmOutputDir TruthValue,
- vrcMainCfgHpAbnAlarmSetting Integer32,
- vrcMainCfgLpAlarmCtrl INTEGER,
- vrcMainCfgHpAlarmCtrl INTEGER,
- vrcMainCfgLpFreqAlarmCtrl INTEGER,
- vrcMainCfgHpFreqAlarmCtrl INTEGER,
- vrcMainCfgLpSensorFailAlarmCtrl INTEGER,
- vrcMainCfgHpSensorFailAlarmCtrl INTEGER,
- vrcMainCfgHighWaterAlarmCtrl INTEGER,
- vrcMainCfgRemShutdownAlarmCtrl INTEGER,
- vrcMainCfgEevCommFailAlarmCtrl INTEGER
- }
- vrcMainCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcMainCfgEntry 1 }
- vrcMainCfgModelSelect OBJECT-TYPE
- SYNTAX INTEGER {
- tmLoc(1),
- r035Ap(2),
- r035Ak(3),
- scLoc(4),
- zeroULoc(5),
- r035Ep(6),
- r035Ek(7)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Model Selection:
- 1 = TMM-Local 220V 50/60HZ
- 2 = TMM-Global 208/230V 50/60HZ
- 3 = TMM-Global 120V 50/60HZ
- 4 = SC 220V 50/60HZ
- 5 = 0U 220V 50/60HZ
- 6 = SS 208/230V 50/60HZ
- 7 = SS 120V 50/60HZ"
- ::= { vrcMainCfgEntry 2 }
- vrcMainCfgSystemTimeYear OBJECT-TYPE
- SYNTAX Integer32(2000..2099)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - year"
- ::= { vrcMainCfgEntry 3 }
- vrcMainCfgSystemTimeMonth OBJECT-TYPE
- SYNTAX Integer32(1..12)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - month"
- ::= { vrcMainCfgEntry 4 }
- vrcMainCfgSystemTimeDay OBJECT-TYPE
- SYNTAX Integer32(1..31)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - day"
- ::= { vrcMainCfgEntry 5 }
- vrcMainCfgSystemTimeHour OBJECT-TYPE
- SYNTAX Integer32(0..23)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - hour"
- ::= { vrcMainCfgEntry 6 }
- vrcMainCfgSystemTimeMin OBJECT-TYPE
- SYNTAX Integer32(0..59)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - minutes"
- ::= { vrcMainCfgEntry 7 }
- vrcMainCfgSystemTimeSec OBJECT-TYPE
- SYNTAX Integer32(0..59)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "System time - seconds"
- ::= { vrcMainCfgEntry 8 }
- vrcMainCfgEevShtSettingMin OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Min Eev sht in tenths of a degree. Units are given by temperatureUnits
- field in deviceInfo. The settable range is determined by the current
- temperature units.
- Celsius: 50 to 200
- Fahrenheit: 90 to 359"
- ::= { vrcMainCfgEntry 9 }
- vrcMainCfgEevShtSettingMax OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Max Eev sht in tenths of a degree. Units are given by temperatureUnits
- field in deviceInfo. The settable range is determined by the current
- temperature units.
- Celsius: 50 to 200
- Fahrenheit: 90 to 359"
- ::= { vrcMainCfgEntry 10 }
- vrcMainCfgEevValveCloseSht OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Eev valve close sht in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The settable range is determined
- by the current temperature units.
- Celsius: 0 to 100
- Fahrenheit: 0 to 179"
- ::= { vrcMainCfgEntry 11 }
- vrcMainCfgEevMopPressSetting OBJECT-TYPE
- SYNTAX Integer32(0..200)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Eev mop pressure setting in tenths of a bar."
- ::= { vrcMainCfgEntry 12 }
- vrcMainCfgLpdt OBJECT-TYPE
- SYNTAX Integer32(30..600)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Low pressure dt in seconds"
- ::= { vrcMainCfgEntry 13 }
- vrcMainCfgDeadBand OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dead band in tenths of a degree. Units are given by temperatureUnits
- field in deviceInfo. The settable range is determined by the current
- temperature units.
- Celsius: 0 to 20
- Fahrenheit: 0 to 35"
- ::= { vrcMainCfgEntry 14 }
- vrcMainCfgOnOffSwitch OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "On-off switch"
- ::= { vrcMainCfgEntry 15 }
- vrcMainCfgVacuumState OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Vacuum state"
- ::= { vrcMainCfgEntry 16 }
- vrcMainCfgControlMode OBJECT-TYPE
- SYNTAX INTEGER {
- supply(1),
- return(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Control mode:
- 1 = supply
- 2 = return"
- ::= { vrcMainCfgEntry 17 }
- vrcMainCfgManualRunEnable OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Manual run enable"
- ::= { vrcMainCfgEntry 18 }
- vrcMainCfgRemShutdownInput OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Remote shutdown input"
- ::= { vrcMainCfgEntry 19 }
- vrcMainCfgMonitorShutDownFlag OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Monitor shutdown flag"
- ::= { vrcMainCfgEntry 20 }
- vrcMainCfgFirstOnPassword OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "First on password value"
- ::= { vrcMainCfgEntry 21 }
- vrcMainCfgFilterMaintSetting OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Filter maintenance setting"
- ::= { vrcMainCfgEntry 22 }
- vrcMainCfgFilterMaintRemindTime OBJECT-TYPE
- SYNTAX Integer32(30..360)
- UNITS "days"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Time between filter maintenance reminders in days"
- ::= { vrcMainCfgEntry 23 }
- vrcMainCfgFilterMaintRemindCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Filter maintenance reminder:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 24 }
- vrcMainCfgCommonAlarmOutputDir OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Common alarm output direction"
- ::= { vrcMainCfgEntry 25 }
- vrcMainCfgHpAbnAlarmSetting OBJECT-TYPE
- SYNTAX Integer32(300..360)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Abnormal high pressure alarm value in tenths of a bar"
- ::= { vrcMainCfgEntry 26 }
- vrcMainCfgLpAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Low pressure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 27 }
- vrcMainCfgHpAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "High pressure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 28 }
- vrcMainCfgLpFreqAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Low pressure frequently alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 29 }
- vrcMainCfgHpFreqAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "High pressure frequently alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 30 }
- vrcMainCfgLpSensorFailAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Low pressure sensor failure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 31 }
- vrcMainCfgHpSensorFailAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "High pressure sensor failure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 32 }
- vrcMainCfgHighWaterAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "High water alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 33 }
- vrcMainCfgRemShutdownAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Remote shutdown alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 34 }
- vrcMainCfgEevCommFailAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Eev communication failure alarm:
- 2 = suspend
- 3 = open"
- ::= { vrcMainCfgEntry 35 }
- --###########################################################################################--
- --vrcOutFanPtTable--
- --###########################################################################################--
- vrcOutFanPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcOutFanPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC out-fan status"
- ::= { vrc 4 }
- vrcOutFanPtEntry OBJECT-TYPE
- SYNTAX VrcOutFanPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcOutFanPtTable: each entry represents data for a VRC
- out-fan"
- INDEX { vrcOutFanPtIndex }
- ::= { vrcOutFanPtTable 1 }
- VrcOutFanPtEntry ::= SEQUENCE {
- vrcOutFanPtIndex Integer32,
- vrcOutFanPtName SnmpAdminString,
- vrcOutFanPtSpeed Integer32
- }
- vrcOutFanPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcOutFanPtEntry 1 }
- vrcOutFanPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Out-fan name (factory-assigned)"
- ::= { vrcOutFanPtEntry 2 }
- vrcOutFanPtSpeed OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Fan speed (percent)"
- ::= { vrcOutFanPtEntry 3 }
- --###########################################################################################--
- --vrcOutFanCfgTable--
- --###########################################################################################--
- vrcOutFanCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcOutFanCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC out-fan configuration"
- ::= { vrc 5 }
- vrcOutFanCfgEntry OBJECT-TYPE
- SYNTAX VrcOutFanCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcOutFanCfgTable: each entry contains config fields for
- a VRC out-fan"
- INDEX { vrcOutFanCfgIndex }
- ::= { vrcOutFanCfgTable 1 }
- VrcOutFanCfgEntry ::= SEQUENCE {
- vrcOutFanCfgIndex Integer32,
- vrcOutFanCfgStartPress Integer32,
- vrcOutFanCfgPressSetting Integer32,
- vrcOutFanCfgMinPowerVoltage Integer32,
- vrcOutFanCfgMaxPowerVoltage Integer32,
- vrcOutFanCfgSpeed Integer32
- }
- vrcOutFanCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcOutFanCfgEntry 1 }
- vrcOutFanCfgStartPress OBJECT-TYPE
- SYNTAX Integer32(190..250)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Out-fan start pressure in tenths of a bar"
- ::= { vrcOutFanCfgEntry 2 }
- vrcOutFanCfgPressSetting OBJECT-TYPE
- SYNTAX Integer32(50..80)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Out-fan pressure setting in tenths of a bar"
- ::= { vrcOutFanCfgEntry 3 }
- vrcOutFanCfgMinPowerVoltage OBJECT-TYPE
- SYNTAX Integer32(30..50)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Min out-fan voltage (percent)"
- ::= { vrcOutFanCfgEntry 4 }
- vrcOutFanCfgMaxPowerVoltage OBJECT-TYPE
- SYNTAX Integer32(60..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Max out-fan voltage (percent)"
- ::= { vrcOutFanCfgEntry 5 }
- vrcOutFanCfgSpeed OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Out-fan speed (percent)"
- ::= { vrcOutFanCfgEntry 6 }
- --###########################################################################################--
- --vrcInFanPtTable--
- --###########################################################################################--
- vrcInFanPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcInFanPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC in-fan status"
- ::= { vrc 6 }
- vrcInFanPtEntry OBJECT-TYPE
- SYNTAX VrcInFanPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcInFanPtTable: each entry represents data for a VRC in-
- fan"
- INDEX { vrcInFanPtIndex }
- ::= { vrcInFanPtTable 1 }
- VrcInFanPtEntry ::= SEQUENCE {
- vrcInFanPtIndex Integer32,
- vrcInFanPtName SnmpAdminString,
- vrcInFanPtRunTimeHours Integer32,
- vrcInFanPtStartStopCount Integer32
- }
- vrcInFanPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcInFanPtEntry 1 }
- vrcInFanPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In-fan name (factory-assigned)"
- ::= { vrcInFanPtEntry 2 }
- vrcInFanPtRunTimeHours OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- UNITS "hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In-fan run time in hours"
- ::= { vrcInFanPtEntry 3 }
- vrcInFanPtStartStopCount OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In-fan start/stop count"
- ::= { vrcInFanPtEntry 4 }
- --###########################################################################################--
- --vrcInFanCfgTable--
- --###########################################################################################--
- vrcInFanCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcInFanCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC in-fan configuration"
- ::= { vrc 7 }
- vrcInFanCfgEntry OBJECT-TYPE
- SYNTAX VrcInFanCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcInFanCfgTable: each entry contains config fields for a
- VRC in-fan"
- INDEX { vrcInFanCfgIndex }
- ::= { vrcInFanCfgTable 1 }
- VrcInFanCfgEntry ::= SEQUENCE {
- vrcInFanCfgIndex Integer32,
- vrcInFanCfgOutputStatus TruthValue,
- vrcInFanCfgLowSpeedStep Integer32,
- vrcInFanCfgHighSpeedStep Integer32,
- vrcInFanCfgMinSpeed Integer32,
- vrcInFanCfgStandardSpeed Integer32,
- vrcInFanCfgMinCfc Integer32,
- vrcInFanCfgStandardCfc Integer32,
- vrcInFanCfgStartDelay Integer32,
- vrcInFanCfgStopDelay Integer32,
- vrcInFanCfgReduceSpeedDelay Integer32,
- vrcInFanCfgJumpBand1 Integer32,
- vrcInFanCfgJumpBand2 Integer32,
- vrcInFanCfgJumpBand3 Integer32,
- vrcInFanCfgJumpBand4 Integer32,
- vrcInFanCfgJumpBand5 Integer32,
- vrcInFanCfgJumpFreq1 Integer32,
- vrcInFanCfgJumpFreq2 Integer32,
- vrcInFanCfgJumpFreq3 Integer32,
- vrcInFanCfgJumpFreq4 Integer32,
- vrcInFanCfgJumpFreq5 Integer32,
- vrcInFanCfgTempP Integer32,
- vrcInFanCfgTempI Integer32,
- vrcInFanCfgTempD Integer32
- }
- vrcInFanCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcInFanCfgEntry 1 }
- vrcInFanCfgOutputStatus OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan output status"
- ::= { vrcInFanCfgEntry 2 }
- vrcInFanCfgLowSpeedStep OBJECT-TYPE
- SYNTAX Integer32(1..20)
- UNITS "0.1%/s"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan low speed step in tenths of a percent per second"
- ::= { vrcInFanCfgEntry 3 }
- vrcInFanCfgHighSpeedStep OBJECT-TYPE
- SYNTAX Integer32(1..50)
- UNITS "0.1%/s"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan high speed step in tenths of a percent per second"
- ::= { vrcInFanCfgEntry 4 }
- vrcInFanCfgMinSpeed OBJECT-TYPE
- SYNTAX Integer32(30..80)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Min in-fan speed (percent)"
- ::= { vrcInFanCfgEntry 5 }
- vrcInFanCfgStandardSpeed OBJECT-TYPE
- SYNTAX Integer32(80..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Standard in-fan speed (percent)"
- ::= { vrcInFanCfgEntry 6 }
- vrcInFanCfgMinCfc OBJECT-TYPE
- SYNTAX Integer32(0..30)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Min in-fan cfc (percent)"
- ::= { vrcInFanCfgEntry 7 }
- vrcInFanCfgStandardCfc OBJECT-TYPE
- SYNTAX Integer32(85..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Standard in-fan cfc (percent)"
- ::= { vrcInFanCfgEntry 8 }
- vrcInFanCfgStartDelay OBJECT-TYPE
- SYNTAX Integer32(10..600)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan start delay in seconds"
- ::= { vrcInFanCfgEntry 9 }
- vrcInFanCfgStopDelay OBJECT-TYPE
- SYNTAX Integer32(10..300)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan stop delay in seconds"
- ::= { vrcInFanCfgEntry 10 }
- vrcInFanCfgReduceSpeedDelay OBJECT-TYPE
- SYNTAX Integer32(0..300)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan reduce speed delay in seconds"
- ::= { vrcInFanCfgEntry 11 }
- vrcInFanCfgJumpBand1 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump band 1 in tenths of a percent"
- ::= { vrcInFanCfgEntry 12 }
- vrcInFanCfgJumpBand2 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump band 2 in tenths of a percent"
- ::= { vrcInFanCfgEntry 13 }
- vrcInFanCfgJumpBand3 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump band 3 in tenths of a percent"
- ::= { vrcInFanCfgEntry 14 }
- vrcInFanCfgJumpBand4 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump band 4 in tenths of a percent"
- ::= { vrcInFanCfgEntry 15 }
- vrcInFanCfgJumpBand5 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump band 5 in tenths of a percent"
- ::= { vrcInFanCfgEntry 16 }
- vrcInFanCfgJumpFreq1 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump frequency 1 in tenths of a percent"
- ::= { vrcInFanCfgEntry 17 }
- vrcInFanCfgJumpFreq2 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump frequency 2 in tenths of a percent"
- ::= { vrcInFanCfgEntry 18 }
- vrcInFanCfgJumpFreq3 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump frequency 3 in tenths of a percent"
- ::= { vrcInFanCfgEntry 19 }
- vrcInFanCfgJumpFreq4 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump frequency 4 in tenths of a percent"
- ::= { vrcInFanCfgEntry 20 }
- vrcInFanCfgJumpFreq5 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan jump frequency 5 in tenths of a percent"
- ::= { vrcInFanCfgEntry 21 }
- vrcInFanCfgTempP OBJECT-TYPE
- SYNTAX Integer32(10..150)
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan temperature P in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo."
- ::= { vrcInFanCfgEntry 22 }
- vrcInFanCfgTempI OBJECT-TYPE
- SYNTAX Integer32(0..900)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan temperature I in seconds"
- ::= { vrcInFanCfgEntry 23 }
- vrcInFanCfgTempD OBJECT-TYPE
- SYNTAX Integer32(0..900)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "In-fan temperature D in seconds"
- ::= { vrcInFanCfgEntry 24 }
- --###########################################################################################--
- --vrcCompPtTable--
- --###########################################################################################--
- vrcCompPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcCompPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC compressor status"
- ::= { vrc 8 }
- vrcCompPtEntry OBJECT-TYPE
- SYNTAX VrcCompPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcCompPtTable: each entry represents data for a VRC
- compressor"
- INDEX { vrcCompPtIndex }
- ::= { vrcCompPtTable 1 }
- VrcCompPtEntry ::= SEQUENCE {
- vrcCompPtIndex Integer32,
- vrcCompPtName SnmpAdminString,
- vrcCompPtCapacity Integer32,
- vrcCompPtRunTimeHours Integer32,
- vrcCompPtStartStopCount Integer32,
- vrcCompPtDriverFaultU00 TruthValue,
- vrcCompPtDriverFaultU01 TruthValue,
- vrcCompPtDriverFaultU02 TruthValue,
- vrcCompPtDriverFaultU03 TruthValue,
- vrcCompPtDriverFaultU04 TruthValue,
- vrcCompPtDriverFaultU05 TruthValue,
- vrcCompPtDriverFaultU06 TruthValue,
- vrcCompPtDriverFaultU07 TruthValue,
- vrcCompPtDriverFaultU08 TruthValue,
- vrcCompPtDriverFaultU09 TruthValue,
- vrcCompPtDriverFaultU10 TruthValue,
- vrcCompPtDriverFaultU11 TruthValue,
- vrcCompPtDriverFaultU12 TruthValue,
- vrcCompPtDriverFaultU13 TruthValue,
- vrcCompPtDriverFaultU14 TruthValue,
- vrcCompPtDriverFaultU15 TruthValue,
- vrcCompPtDriverCommFailAlarm TruthValue,
- vrcCompPtFaultLockAlarm TruthValue
- }
- vrcCompPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcCompPtEntry 1 }
- vrcCompPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor name (factory-assigned)"
- ::= { vrcCompPtEntry 2 }
- vrcCompPtCapacity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor capacity value (percent)"
- ::= { vrcCompPtEntry 3 }
- vrcCompPtRunTimeHours OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- UNITS "hours"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor run time in hours"
- ::= { vrcCompPtEntry 4 }
- vrcCompPtStartStopCount OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor start/stop count"
- ::= { vrcCompPtEntry 5 }
- vrcCompPtDriverFaultU00 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U00 state"
- ::= { vrcCompPtEntry 6 }
- vrcCompPtDriverFaultU01 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U01 state"
- ::= { vrcCompPtEntry 7 }
- vrcCompPtDriverFaultU02 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U02 state"
- ::= { vrcCompPtEntry 8 }
- vrcCompPtDriverFaultU03 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U03 state"
- ::= { vrcCompPtEntry 9 }
- vrcCompPtDriverFaultU04 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U04 state"
- ::= { vrcCompPtEntry 10 }
- vrcCompPtDriverFaultU05 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U05 state"
- ::= { vrcCompPtEntry 11 }
- vrcCompPtDriverFaultU06 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U06 state"
- ::= { vrcCompPtEntry 12 }
- vrcCompPtDriverFaultU07 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U07 state"
- ::= { vrcCompPtEntry 13 }
- vrcCompPtDriverFaultU08 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U08 state"
- ::= { vrcCompPtEntry 14 }
- vrcCompPtDriverFaultU09 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U09 state"
- ::= { vrcCompPtEntry 15 }
- vrcCompPtDriverFaultU10 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U10 state"
- ::= { vrcCompPtEntry 16 }
- vrcCompPtDriverFaultU11 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U11 state"
- ::= { vrcCompPtEntry 17 }
- vrcCompPtDriverFaultU12 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U12 state"
- ::= { vrcCompPtEntry 18 }
- vrcCompPtDriverFaultU13 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U13 state"
- ::= { vrcCompPtEntry 19 }
- vrcCompPtDriverFaultU14 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U14 state"
- ::= { vrcCompPtEntry 20 }
- vrcCompPtDriverFaultU15 OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm U15 state"
- ::= { vrcCompPtEntry 21 }
- vrcCompPtDriverCommFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor driver communication failure alarm state"
- ::= { vrcCompPtEntry 22 }
- vrcCompPtFaultLockAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Compressor fault lock alarm state"
- ::= { vrcCompPtEntry 23 }
- --###########################################################################################--
- --vrcCompCfgTable--
- --###########################################################################################--
- vrcCompCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcCompCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC compressor configuration"
- ::= { vrc 9 }
- vrcCompCfgEntry OBJECT-TYPE
- SYNTAX VrcCompCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcCompCfgTable: each entry contains config fields for a
- VRC compressor"
- INDEX { vrcCompCfgIndex }
- ::= { vrcCompCfgTable 1 }
- VrcCompCfgEntry ::= SEQUENCE {
- vrcCompCfgIndex Integer32,
- vrcCompCfgOutputStatus TruthValue,
- vrcCompCfgOutputDeadBand Integer32,
- vrcCompCfgCapacityOutputValue Integer32,
- vrcCompCfgMinCapacity Integer32,
- vrcCompCfgStartCapacity Integer32,
- vrcCompCfgStandardCapacity Integer32,
- vrcCompCfgStartCfc Integer32,
- vrcCompCfgStopCfc Integer32,
- vrcCompCfgMinRunTime Integer32,
- vrcCompCfgMinStopTime Integer32,
- vrcCompCfgJumpBand1 Integer32,
- vrcCompCfgJumpBand2 Integer32,
- vrcCompCfgJumpBand3 Integer32,
- vrcCompCfgJumpBand4 Integer32,
- vrcCompCfgJumpBand5 Integer32,
- vrcCompCfgJumpFreq1 Integer32,
- vrcCompCfgJumpFreq2 Integer32,
- vrcCompCfgJumpFreq3 Integer32,
- vrcCompCfgJumpFreq4 Integer32,
- vrcCompCfgJumpFreq5 Integer32,
- vrcCompCfgTempP Integer32,
- vrcCompCfgTempI Integer32,
- vrcCompCfgTempD Integer32,
- vrcCompCfgDriverFaultAlmCtrl INTEGER,
- vrcCompCfgDriverCommFailAlmCtrl INTEGER,
- vrcCompCfgFaultLockAlmCtrl INTEGER
- }
- vrcCompCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcCompCfgEntry 1 }
- vrcCompCfgOutputStatus OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor output status"
- ::= { vrcCompCfgEntry 2 }
- vrcCompCfgOutputDeadBand OBJECT-TYPE
- SYNTAX Integer32(0..50)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor output dead band in tenths of a percent"
- ::= { vrcCompCfgEntry 3 }
- vrcCompCfgCapacityOutputValue OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor capacity output (percent)"
- ::= { vrcCompCfgEntry 4 }
- vrcCompCfgMinCapacity OBJECT-TYPE
- SYNTAX Integer32(15..50)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor min capacity (percent)"
- ::= { vrcCompCfgEntry 5 }
- vrcCompCfgStartCapacity OBJECT-TYPE
- SYNTAX Integer32(40..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor start capacity (percent)"
- ::= { vrcCompCfgEntry 6 }
- vrcCompCfgStandardCapacity OBJECT-TYPE
- SYNTAX Integer32(80..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor standard capacity (percent)"
- ::= { vrcCompCfgEntry 7 }
- vrcCompCfgStartCfc OBJECT-TYPE
- SYNTAX Integer32(1..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor start cfc (percent)"
- ::= { vrcCompCfgEntry 8 }
- vrcCompCfgStopCfc OBJECT-TYPE
- SYNTAX Integer32(-200..-50)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor stop cfc (percent)"
- ::= { vrcCompCfgEntry 9 }
- vrcCompCfgMinRunTime OBJECT-TYPE
- SYNTAX Integer32(0..30)
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor min run time in minutes"
- ::= { vrcCompCfgEntry 10 }
- vrcCompCfgMinStopTime OBJECT-TYPE
- SYNTAX Integer32(0..10)
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor min stop time in minutes"
- ::= { vrcCompCfgEntry 11 }
- vrcCompCfgJumpBand1 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump band 1 in tenths of a percent"
- ::= { vrcCompCfgEntry 12 }
- vrcCompCfgJumpBand2 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump band 2 in tenths of a percent"
- ::= { vrcCompCfgEntry 13 }
- vrcCompCfgJumpBand3 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump band 3 in tenths of a percent"
- ::= { vrcCompCfgEntry 14 }
- vrcCompCfgJumpBand4 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump band 4 in tenths of a percent"
- ::= { vrcCompCfgEntry 15 }
- vrcCompCfgJumpBand5 OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump band 5 in tenths of a percent"
- ::= { vrcCompCfgEntry 16 }
- vrcCompCfgJumpFreq1 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump frequency 1 in tenths of a percent"
- ::= { vrcCompCfgEntry 17 }
- vrcCompCfgJumpFreq2 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump frequency 2 in tenths of a percent"
- ::= { vrcCompCfgEntry 18 }
- vrcCompCfgJumpFreq3 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump frequency 3 in tenths of a percent"
- ::= { vrcCompCfgEntry 19 }
- vrcCompCfgJumpFreq4 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump frequency 4 in tenths of a percent"
- ::= { vrcCompCfgEntry 20 }
- vrcCompCfgJumpFreq5 OBJECT-TYPE
- SYNTAX Integer32(0..1000)
- UNITS "0.1%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor jump frequency 5 in tenths of a percent"
- ::= { vrcCompCfgEntry 21 }
- vrcCompCfgTempP OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor temperature P in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The settable range is determined
- by the current temperature units.
- Celsius: 10 to 150
- Fahrenheit: 18 to 269"
- ::= { vrcCompCfgEntry 22 }
- vrcCompCfgTempI OBJECT-TYPE
- SYNTAX Integer32(0..900)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor temperature I in seconds"
- ::= { vrcCompCfgEntry 23 }
- vrcCompCfgTempD OBJECT-TYPE
- SYNTAX Integer32(0..900)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor temperature D in seconds"
- ::= { vrcCompCfgEntry 24 }
- vrcCompCfgDriverFaultAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor driver fault alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcCompCfgEntry 25 }
- vrcCompCfgDriverCommFailAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor driver communication failure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcCompCfgEntry 26 }
- vrcCompCfgFaultLockAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Compressor fault lock alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcCompCfgEntry 27 }
- --###########################################################################################--
- --vrcReturnPtTable--
- --###########################################################################################--
- vrcReturnPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcReturnPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC return status"
- ::= { vrc 10 }
- vrcReturnPtEntry OBJECT-TYPE
- SYNTAX VrcReturnPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcReturnPtTable: each entry represents return data for a
- VRC"
- INDEX { vrcReturnPtIndex }
- ::= { vrcReturnPtTable 1 }
- VrcReturnPtEntry ::= SEQUENCE {
- vrcReturnPtIndex Integer32,
- vrcReturnPtName SnmpAdminString,
- vrcReturnPtTemp Integer32,
- vrcReturnPtHighTempAlarm TruthValue,
- vrcReturnPtTempSensorFailAlarm TruthValue
- }
- vrcReturnPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcReturnPtEntry 1 }
- vrcReturnPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Return name (factory-assigned)"
- ::= { vrcReturnPtEntry 2 }
- vrcReturnPtTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Return temperature value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The range is determined by the
- current temperature units.
- Celsius: -400 to 1000
- Fahrenheit: -400 to 2120"
- ::= { vrcReturnPtEntry 3 }
- vrcReturnPtHighTempAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Return high temperature alarm state"
- ::= { vrcReturnPtEntry 4 }
- vrcReturnPtTempSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Return temperature sensor failure alarm state"
- ::= { vrcReturnPtEntry 5 }
- --###########################################################################################--
- --vrcReturnCfgTable--
- --###########################################################################################--
- vrcReturnCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcReturnCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC return configuration"
- ::= { vrc 11 }
- vrcReturnCfgEntry OBJECT-TYPE
- SYNTAX VrcReturnCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcReturnCfgTable: each entry contains config fields for
- VRC return"
- INDEX { vrcReturnCfgIndex }
- ::= { vrcReturnCfgTable 1 }
- VrcReturnCfgEntry ::= SEQUENCE {
- vrcReturnCfgIndex Integer32,
- vrcReturnCfgOilCycle Integer32,
- vrcReturnCfgOilRunCapacity Integer32,
- vrcReturnCfgOilRunTime Integer32,
- vrcReturnCfgTempCalValue Integer32,
- vrcReturnCfgTempSetting Integer32,
- vrcReturnCfgHighTempAlarmValue Integer32,
- vrcReturnCfgHighTempAlarmCtrl INTEGER,
- vrcReturnCfgTempSensFailAlmCtrl INTEGER
- }
- vrcReturnCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcReturnCfgEntry 1 }
- vrcReturnCfgOilCycle OBJECT-TYPE
- SYNTAX Integer32(5..50)
- UNITS "decihours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return oil cycle in tenths of an hour"
- ::= { vrcReturnCfgEntry 2 }
- vrcReturnCfgOilRunCapacity OBJECT-TYPE
- SYNTAX Integer32(50..100)
- UNITS "%"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return Oil run capacity (percent)"
- ::= { vrcReturnCfgEntry 3 }
- vrcReturnCfgOilRunTime OBJECT-TYPE
- SYNTAX Integer32(0..10)
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return oil run time in minutes"
- ::= { vrcReturnCfgEntry 4 }
- vrcReturnCfgTempCalValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return temperature calibration value in tenths of a degree. Units are
- given by temperatureUnits field in deviceInfo. The settable range is
- determined by the current temperature units.
- Celsius: -100 to 100
- Fahrenheit: -179 to 179"
- ::= { vrcReturnCfgEntry 5 }
- vrcReturnCfgTempSetting OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return temperature setting in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The settable range is determined
- by the current temperature units.
- Celsius: 250 to 350
- Fahrenheit: 770 to 949"
- ::= { vrcReturnCfgEntry 6 }
- vrcReturnCfgHighTempAlarmValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return high temperature alarm value in tenths of a degree. Units are
- given by temperatureUnits field in deviceInfo. The settable range is
- determined by the current temperature units.
- Celsius: 300 to 450
- Fahrenheit: 860 to 1129"
- ::= { vrcReturnCfgEntry 7 }
- vrcReturnCfgHighTempAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return high temperature alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcReturnCfgEntry 8 }
- vrcReturnCfgTempSensFailAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Return temperature sensor failure alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcReturnCfgEntry 9 }
- --###########################################################################################--
- --vrcSupplyPtTable--
- --###########################################################################################--
- vrcSupplyPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcSupplyPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC supply status"
- ::= { vrc 12 }
- vrcSupplyPtEntry OBJECT-TYPE
- SYNTAX VrcSupplyPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcSupplyPtTable: each entry represents supply data for a
- VRC"
- INDEX { vrcSupplyPtIndex }
- ::= { vrcSupplyPtTable 1 }
- VrcSupplyPtEntry ::= SEQUENCE {
- vrcSupplyPtIndex Integer32,
- vrcSupplyPtName SnmpAdminString,
- vrcSupplyPtTemp Integer32,
- vrcSupplyPtLowTempAlarm TruthValue,
- vrcSupplyPtHighTempAlarm TruthValue,
- vrcSupplyPtTempSensorFailAlarm TruthValue
- }
- vrcSupplyPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcSupplyPtEntry 1 }
- vrcSupplyPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Supply name (factory-assigned)"
- ::= { vrcSupplyPtEntry 2 }
- vrcSupplyPtTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Supply temperature value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The range is determined by the
- current temperature units.
- Celsius: -400 to 1000
- Fahrenheit: -400 to 2120"
- ::= { vrcSupplyPtEntry 3 }
- vrcSupplyPtLowTempAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Supply low temperature alarm state"
- ::= { vrcSupplyPtEntry 4 }
- vrcSupplyPtHighTempAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Supply high temperature alarm state"
- ::= { vrcSupplyPtEntry 5 }
- vrcSupplyPtTempSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Supply temperature sensor failure alarm state"
- ::= { vrcSupplyPtEntry 6 }
- --###########################################################################################--
- --vrcSupplyCfgTable--
- --###########################################################################################--
- vrcSupplyCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcSupplyCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC supply configuration"
- ::= { vrc 13 }
- vrcSupplyCfgEntry OBJECT-TYPE
- SYNTAX VrcSupplyCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcSupplyCfgTable: each entry contains config fields for
- a VRC supply"
- INDEX { vrcSupplyCfgIndex }
- ::= { vrcSupplyCfgTable 1 }
- VrcSupplyCfgEntry ::= SEQUENCE {
- vrcSupplyCfgIndex Integer32,
- vrcSupplyCfgTempCalValue Integer32,
- vrcSupplyCfgTempSetting Integer32,
- vrcSupplyCfgLowTempAlarmValue Integer32,
- vrcSupplyCfgHighTempAlarmValue Integer32,
- vrcSupplyCfgLowTempAlmCtrl INTEGER,
- vrcSupplyCfgHighTempAlmCtrl INTEGER,
- vrcSupplyCfgTempSensFailAlmCtrl INTEGER
- }
- vrcSupplyCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcSupplyCfgEntry 1 }
- vrcSupplyCfgTempCalValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply temperature calibration value in tenths of a degree. Units are
- given by temperatureUnits field in deviceInfo. The settable range is
- determined by the current temperature units.
- Celsius: -100 to 100
- Fahrenheit: -179 to 179"
- ::= { vrcSupplyCfgEntry 2 }
- vrcSupplyCfgTempSetting OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply temperature setting in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The settable range is determined
- by the current temperature units.
- Celsius: 130 to 280
- Fahrenheit: 554 to 823"
- ::= { vrcSupplyCfgEntry 3 }
- vrcSupplyCfgLowTempAlarmValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply low temperature alarm value in tenths of a degree. Units are
- given by temperatureUnits field in deviceInfo. The settable range is
- determined by the current temperature units.
- Celsius: 50 to 200
- Fahrenheit: 410 to 679"
- ::= { vrcSupplyCfgEntry 4 }
- vrcSupplyCfgHighTempAlarmValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply high temperature alarm value in tenths of a degree. Units are
- given by temperatureUnits field in deviceInfo. The settable range is
- determined by the current temperature units.
- Celsius: 200 to 350
- Fahrenheit: 680 to 949"
- ::= { vrcSupplyCfgEntry 5 }
- vrcSupplyCfgLowTempAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply low temperature alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcSupplyCfgEntry 6 }
- vrcSupplyCfgHighTempAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply high temperature alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcSupplyCfgEntry 7 }
- vrcSupplyCfgTempSensFailAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Supply temperature sensor failure alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcSupplyCfgEntry 8 }
- --###########################################################################################--
- --vrcPowerPtTable--
- --###########################################################################################--
- vrcPowerPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcPowerPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC power status"
- ::= { vrc 14 }
- vrcPowerPtEntry OBJECT-TYPE
- SYNTAX VrcPowerPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcPowerPtTable: each entry represents power data for a
- VRC"
- INDEX { vrcPowerPtIndex }
- ::= { vrcPowerPtTable 1 }
- VrcPowerPtEntry ::= SEQUENCE {
- vrcPowerPtIndex Integer32,
- vrcPowerPtName SnmpAdminString,
- vrcPowerPtVoltage Integer32,
- vrcPowerPtFrequency Integer32,
- vrcPowerPtLowVoltageAlarm TruthValue,
- vrcPowerPtHighVoltageAlarm TruthValue,
- vrcPowerPtLossOfPhasePowerAlarm TruthValue,
- vrcPowerPtLossOfPowerAlarm TruthValue,
- vrcPowerPtFrequencyErrorAlarm TruthValue
- }
- vrcPowerPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcPowerPtEntry 1 }
- vrcPowerPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power name (factory-assigned)"
- ::= { vrcPowerPtEntry 2 }
- vrcPowerPtVoltage OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- UNITS "decivolts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power voltage measurement in tenths of a volt"
- ::= { vrcPowerPtEntry 3 }
- vrcPowerPtFrequency OBJECT-TYPE
- SYNTAX Integer32(-32768..32767)
- UNITS "decihertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power frequency measurement in tenths of hertz"
- ::= { vrcPowerPtEntry 4 }
- vrcPowerPtLowVoltageAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power low voltage alarm state"
- ::= { vrcPowerPtEntry 5 }
- vrcPowerPtHighVoltageAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power high voltage alarm state"
- ::= { vrcPowerPtEntry 6 }
- vrcPowerPtLossOfPhasePowerAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Phase power loss alarm state"
- ::= { vrcPowerPtEntry 7 }
- vrcPowerPtLossOfPowerAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power loss alarm state"
- ::= { vrcPowerPtEntry 8 }
- vrcPowerPtFrequencyErrorAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Power frequency error alarm state"
- ::= { vrcPowerPtEntry 9 }
- --###########################################################################################--
- --vrcPowerCfgTable--
- --###########################################################################################--
- vrcPowerCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcPowerCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC power configuration"
- ::= { vrc 15 }
- vrcPowerCfgEntry OBJECT-TYPE
- SYNTAX VrcPowerCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcPowerCfgTable: each entry contains config fields for
- VRC power"
- INDEX { vrcPowerCfgIndex }
- ::= { vrcPowerCfgTable 1 }
- VrcPowerCfgEntry ::= SEQUENCE {
- vrcPowerCfgIndex Integer32,
- vrcPowerCfgLowVoltageSetting Integer32,
- vrcPowerCfgHighVoltageSetting Integer32,
- vrcPowerCfgLowVoltageAlarmCtrl INTEGER,
- vrcPowerCfgHighVoltageAlarmCtrl INTEGER,
- vrcPowerCfgLossOfPowerAlarmCtrl INTEGER,
- vrcPowerCfgFreqErrorAlarmCtrl INTEGER
- }
- vrcPowerCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcPowerCfgEntry 1 }
- vrcPowerCfgLowVoltageSetting OBJECT-TYPE
- SYNTAX Integer32(100..230)
- UNITS "volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power low voltage setting in volts"
- ::= { vrcPowerCfgEntry 2 }
- vrcPowerCfgHighVoltageSetting OBJECT-TYPE
- SYNTAX Integer32(100..300)
- UNITS "volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power high voltage setting in volts"
- ::= { vrcPowerCfgEntry 3 }
- vrcPowerCfgLowVoltageAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power low voltage alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcPowerCfgEntry 4 }
- vrcPowerCfgHighVoltageAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power high voltage alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcPowerCfgEntry 5 }
- vrcPowerCfgLossOfPowerAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power loss alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcPowerCfgEntry 6 }
- vrcPowerCfgFreqErrorAlarmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- close(1),
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Power frequency error alarm control:
- 1 = close
- 2 = suspend
- 3 = open"
- ::= { vrcPowerCfgEntry 7 }
- --###########################################################################################--
- --vrcOutdoorPtTable--
- --###########################################################################################--
- vrcOutdoorPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcOutdoorPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC outdoor status"
- ::= { vrc 16 }
- vrcOutdoorPtEntry OBJECT-TYPE
- SYNTAX VrcOutdoorPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcOutdoorPtTable: each entry represents data for a VRC
- outdoor"
- INDEX { vrcOutdoorPtIndex }
- ::= { vrcOutdoorPtTable 1 }
- VrcOutdoorPtEntry ::= SEQUENCE {
- vrcOutdoorPtIndex Integer32,
- vrcOutdoorPtName SnmpAdminString,
- vrcOutdoorPtTemp Integer32
- }
- vrcOutdoorPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcOutdoorPtEntry 1 }
- vrcOutdoorPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Outdoor name (factory-assigned)"
- ::= { vrcOutdoorPtEntry 2 }
- vrcOutdoorPtTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Outdoor temperature value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The range is determined by the
- current temperature units.
- Celsius: -400 to 1000
- Fahrenheit: -400 to 2120"
- ::= { vrcOutdoorPtEntry 3 }
- --###########################################################################################--
- --vrcDischPtTable--
- --###########################################################################################--
- vrcDischPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcDischPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC discharge status"
- ::= { vrc 18 }
- vrcDischPtEntry OBJECT-TYPE
- SYNTAX VrcDischPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcDischPtTable: each entry represents discharge data for
- a VRC"
- INDEX { vrcDischPtIndex }
- ::= { vrcDischPtTable 1 }
- VrcDischPtEntry ::= SEQUENCE {
- vrcDischPtIndex Integer32,
- vrcDischPtName SnmpAdminString,
- vrcDischPtTemp Integer32,
- vrcDischPtPressure Integer32,
- vrcDischPtHighTempAlarm TruthValue,
- vrcDischPtHighTempFreqAlarm TruthValue,
- vrcDischPtTempSensorFailAlarm TruthValue
- }
- vrcDischPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcDischPtEntry 1 }
- vrcDischPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Discharge name (factory-assigned)"
- ::= { vrcDischPtEntry 2 }
- vrcDischPtTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge temperature value in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The range is determined by the
- current temperature units.
- Celsius: -400 to 1560
- Fahrenheit: -400 to 3128"
- ::= { vrcDischPtEntry 3 }
- vrcDischPtPressure OBJECT-TYPE
- SYNTAX Integer32(0..460)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge air pressure value in tenths of a bar"
- ::= { vrcDischPtEntry 4 }
- vrcDischPtHighTempAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Discharge high temperature alarm state"
- ::= { vrcDischPtEntry 5 }
- vrcDischPtHighTempFreqAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Discharge high temperature frequently alarm state"
- ::= { vrcDischPtEntry 6 }
- vrcDischPtTempSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Discharge temperature sensor failure alarm state"
- ::= { vrcDischPtEntry 7 }
- --###########################################################################################--
- --vrcDischCfgTable--
- --###########################################################################################--
- vrcDischCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcDischCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC discharge configuration"
- ::= { vrc 19 }
- vrcDischCfgEntry OBJECT-TYPE
- SYNTAX VrcDischCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcDischCfgTable: each entry contains config fields for
- VRC discharge"
- INDEX { vrcDischCfgIndex }
- ::= { vrcDischCfgTable 1 }
- VrcDischCfgEntry ::= SEQUENCE {
- vrcDischCfgIndex Integer32,
- vrcDischCfgTempCalValue Integer32,
- vrcDischCfgPressCalValue Integer32,
- vrcDischCfgHighTempAlmCtrl INTEGER,
- vrcDischCfgHighTempFreqAlmCtrl INTEGER,
- vrcDischCfgTempSensFailAlmCtrl INTEGER
- }
- vrcDischCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcDischCfgEntry 1 }
- vrcDischCfgTempCalValue OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge temperature calibration value in tenths of a degree. Units
- are given by temperatureUnits field in deviceInfo. The settable range
- is determined by the current temperature units.
- Celsius: -100 to 100
- Fahrenheit: -179 to 179"
- ::= { vrcDischCfgEntry 2 }
- vrcDischCfgPressCalValue OBJECT-TYPE
- SYNTAX Integer32(-100..100)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge pressure calibration value in tenths of a bar"
- ::= { vrcDischCfgEntry 3 }
- vrcDischCfgHighTempAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge high temperature alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcDischCfgEntry 4 }
- vrcDischCfgHighTempFreqAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge high temperature frequenctly alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcDischCfgEntry 5 }
- vrcDischCfgTempSensFailAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Discharge temperature sensor failure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcDischCfgEntry 6 }
- --###########################################################################################--
- --vrcSuctPtTable--
- --###########################################################################################--
- vrcSuctPtTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcSuctPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table that contains VRC suction status"
- ::= { vrc 20 }
- vrcSuctPtEntry OBJECT-TYPE
- SYNTAX VrcSuctPtEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcSuctPtTable: each entry represents suction data for a
- VRC"
- INDEX { vrcSuctPtIndex }
- ::= { vrcSuctPtTable 1 }
- VrcSuctPtEntry ::= SEQUENCE {
- vrcSuctPtIndex Integer32,
- vrcSuctPtName SnmpAdminString,
- vrcSuctPtTemp Integer32,
- vrcSuctPtPressure Integer32,
- vrcSuctPtSuperHeatTemp Integer32,
- vrcSuctPtTempSensorFailAlarm TruthValue
- }
- vrcSuctPtIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcSuctPtEntry 1 }
- vrcSuctPtName OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (1..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Suction name (factory-assigned)"
- ::= { vrcSuctPtEntry 2 }
- vrcSuctPtTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Suction temperature in tenths of a degree. Units are given by
- temperatureUnits field in deviceInfo. The range is determined by the
- current temperature units.
- Celsius: -400 to 1000
- Fahrenheit: -400 to 2120"
- ::= { vrcSuctPtEntry 3 }
- vrcSuctPtPressure OBJECT-TYPE
- SYNTAX Integer32(0..173)
- UNITS "decibars"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Suction air pressure in tenths of a bar"
- ::= { vrcSuctPtEntry 4 }
- vrcSuctPtSuperHeatTemp OBJECT-TYPE
- SYNTAX Integer32
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Suction super heat temperature in tenths of a degree. Units are given
- by temperatureUnits field in deviceInfo. The range is determined by
- the current temperature units.
- Celsius: -400 to 1000
- Fahrenheit: -400 to 2120"
- ::= { vrcSuctPtEntry 5 }
- vrcSuctPtTempSensorFailAlarm OBJECT-TYPE
- SYNTAX TruthValue
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Suction temperature sensor failure alarm state"
- ::= { vrcSuctPtEntry 6 }
- --###########################################################################################--
- --vrcSuctCfgTable--
- --###########################################################################################--
- vrcSuctCfgTable OBJECT-TYPE
- SYNTAX SEQUENCE OF VrcSuctCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table used for VRC suction configuration"
- ::= { vrc 21 }
- vrcSuctCfgEntry OBJECT-TYPE
- SYNTAX VrcSuctCfgEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the vrcSuctCfgTable: each entry contains config fields for
- VRC suction"
- INDEX { vrcSuctCfgIndex }
- ::= { vrcSuctCfgTable 1 }
- VrcSuctCfgEntry ::= SEQUENCE {
- vrcSuctCfgIndex Integer32,
- vrcSuctCfgPressCalValue Integer32,
- vrcSuctCfgTempSensFailAlmCtrl INTEGER
- }
- vrcSuctCfgIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Unique id for each entry in the table"
- ::= { vrcSuctCfgEntry 1 }
- vrcSuctCfgPressCalValue OBJECT-TYPE
- SYNTAX Integer32(-100..100)
- UNITS "decibars"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Suction pressure calibration value in tenths of a bar"
- ::= { vrcSuctCfgEntry 2 }
- vrcSuctCfgTempSensFailAlmCtrl OBJECT-TYPE
- SYNTAX INTEGER {
- suspend(2),
- open(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Suction temperature sensor failure alarm control:
- 2 = suspend
- 3 = open"
- ::= { vrcSuctCfgEntry 3 }
- --###########################################################################################--
- --Notifications--
- --###########################################################################################--
- trap OBJECT IDENTIFIER ::= { imd 32767 }
- trapPrefix OBJECT IDENTIFIER ::= { trap 0 }
- trapObj OBJECT IDENTIFIER ::= { trap 1 }
- trapSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- none(0),
- warning(1),
- alarm(2)
- }
- MAX-ACCESS accessible-for-notify
- STATUS current
- DESCRIPTION
- "Indicates the severity of the trap:
- 0 = None
- 1 = Warning
- 2 = Alarm"
- ::= { trapObj 1 }
- trapThreshType OBJECT-TYPE
- SYNTAX INTEGER {
- low(1),
- high(2)
- }
- MAX-ACCESS accessible-for-notify
- STATUS current
- DESCRIPTION
- "Only sent for threshold alarms. Identifies the threshold type:
- 1 = Low
- 2 = High"
- ::= { trapObj 2 }
- internalTestNOTIFY NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION "Test SNMP Trap"
- ::= { trapPrefix 10101 }
- --#####deviceInfo#####--
- --#####pdu#####--
- --#####pduMainTable#####--
- pduMainAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduMainAvail,
- trapSeverity,
- sysName,
- pduMainLabel
- }
- STATUS current
- DESCRIPTION "PDU availability trap"
- ::= { trapPrefix 10305 }
- pduMainAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduMainAvail,
- trapSeverity,
- sysName,
- pduMainLabel
- }
- STATUS current
- DESCRIPTION "PDU availability clear trap"
- ::= { trapPrefix 20305 }
- pduTotalRealPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduTotalRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total real power trap"
- ::= { trapPrefix 10309 }
- pduTotalRealPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduTotalRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total real power clear trap"
- ::= { trapPrefix 20309 }
- pduTotalApparentPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduTotalApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total apparent power trap"
- ::= { trapPrefix 10310 }
- pduTotalApparentPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduTotalApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total apparent power clear trap"
- ::= { trapPrefix 20310 }
- pduTotalPowerFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduTotalPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total power factor trap"
- ::= { trapPrefix 10311 }
- pduTotalPowerFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduTotalPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total power factor clear trap"
- ::= { trapPrefix 20311 }
- pduTotalEnergyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduTotalEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total energy trap"
- ::= { trapPrefix 10312 }
- pduTotalEnergyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduTotalEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduTotalLabel
- }
- STATUS current
- DESCRIPTION "PDU total energy clear trap"
- ::= { trapPrefix 20312 }
- --#####pduPhaseTable#####--
- pduPhaseVoltageNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase voltage trap"
- ::= { trapPrefix 10324 }
- pduPhaseVoltageCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase voltage clear trap"
- ::= { trapPrefix 20324 }
- pduPhaseCurrentNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase current trap"
- ::= { trapPrefix 10328 }
- pduPhaseCurrentCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase current clear trap"
- ::= { trapPrefix 20328 }
- pduPhaseRealPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase real power trap"
- ::= { trapPrefix 10332 }
- pduPhaseRealPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase real power clear trap"
- ::= { trapPrefix 20332 }
- pduPhaseApparentPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase apparent power trap"
- ::= { trapPrefix 10333 }
- pduPhaseApparentPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase apparent power clear trap"
- ::= { trapPrefix 20333 }
- pduPhasePowerFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhasePowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase power factor trap"
- ::= { trapPrefix 10334 }
- pduPhasePowerFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhasePowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase power factor clear trap"
- ::= { trapPrefix 20334 }
- pduPhaseEnergyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase energy trap"
- ::= { trapPrefix 10335 }
- pduPhaseEnergyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase energy clear trap"
- ::= { trapPrefix 20335 }
- pduPhaseBalanceNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseBalance,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase balance trap"
- ::= { trapPrefix 10337 }
- pduPhaseBalanceCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseBalance,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase balance clear trap"
- ::= { trapPrefix 20337 }
- pduPhaseCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseCurrentCrestFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase current crest factor trap"
- ::= { trapPrefix 10339 }
- pduPhaseCurrentCrestFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduPhaseCurrentCrestFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduPhaseLabel
- }
- STATUS current
- DESCRIPTION "PDU phase current crest factor clear trap"
- ::= { trapPrefix 20339 }
- --#####pduBreakerTable#####--
- pduBreakerCurrentNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker current trap"
- ::= { trapPrefix 10354 }
- pduBreakerCurrentCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker current clear trap"
- ::= { trapPrefix 20354 }
- pduBreakerVoltageNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker voltage trap"
- ::= { trapPrefix 10358 }
- pduBreakerVoltageCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker voltage clear trap"
- ::= { trapPrefix 20358 }
- pduBreakerRealPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker real power trap"
- ::= { trapPrefix 10362 }
- pduBreakerRealPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker real power clear trap"
- ::= { trapPrefix 20362 }
- pduBreakerApparentPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker apparent power trap"
- ::= { trapPrefix 10363 }
- pduBreakerApparentPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker apparent power clear trap"
- ::= { trapPrefix 20363 }
- pduBreakerPowerFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker power factor trap"
- ::= { trapPrefix 10364 }
- pduBreakerPowerFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker power factor clear trap"
- ::= { trapPrefix 20364 }
- pduBreakerEnergyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker energy trap"
- ::= { trapPrefix 10365 }
- pduBreakerEnergyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduBreakerEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduBreakerLabel
- }
- STATUS current
- DESCRIPTION "PDU breaker energy clear trap"
- ::= { trapPrefix 20365 }
- --#####pduLineTable#####--
- pduLineCurrentNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduLineCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduLineLabel
- }
- STATUS current
- DESCRIPTION "PDU line current trap"
- ::= { trapPrefix 10374 }
- pduLineCurrentCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduLineCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduLineLabel
- }
- STATUS current
- DESCRIPTION "PDU line current clear trap"
- ::= { trapPrefix 20374 }
- --#####pduOutletSwitchTable#####--
- --#####pduOutletMeterTable#####--
- pduOutletMeterVoltageNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet voltage trap"
- ::= { trapPrefix 10385 }
- pduOutletMeterVoltageCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet voltage clear trap"
- ::= { trapPrefix 20385 }
- pduOutletMeterCurrentNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet current trap"
- ::= { trapPrefix 10389 }
- pduOutletMeterCurrentCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet current clear trap"
- ::= { trapPrefix 20389 }
- pduOutletMeterRealPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet real power trap"
- ::= { trapPrefix 10393 }
- pduOutletMeterRealPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet real power clear trap"
- ::= { trapPrefix 20393 }
- pduOutletMeterApparentPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet apparent power trap"
- ::= { trapPrefix 10394 }
- pduOutletMeterApparentPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet apparent power clear trap"
- ::= { trapPrefix 20394 }
- pduOutletMeterPowerFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet power factor trap"
- ::= { trapPrefix 10395 }
- pduOutletMeterPowerFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterPowerFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet power factor clear trap"
- ::= { trapPrefix 20395 }
- pduOutletMeterEnergyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet energy trap"
- ::= { trapPrefix 10396 }
- pduOutletMeterEnergyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletMeterEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet energy clear trap"
- ::= { trapPrefix 20396 }
- pduOutletCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- pduOutletCurrentCrestFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet current crest factor trap"
- ::= { trapPrefix 10400 }
- pduOutletCurrentCrestFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- pduOutletCurrentCrestFactor,
- trapThreshType,
- trapSeverity,
- sysName,
- pduMainLabel,
- pduOutletMeterLabel
- }
- STATUS current
- DESCRIPTION "PDU outlet current crest factor clear trap"
- ::= { trapPrefix 20400 }
- --#####tempSensorTable#####--
- tempSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- tempSensorAvail,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT availability trap"
- ::= { trapPrefix 10404 }
- tempSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- tempSensorAvail,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT availability clear trap"
- ::= { trapPrefix 20404 }
- tempSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- tempSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT temperature trap"
- ::= { trapPrefix 10405 }
- tempSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- tempSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT temperature clear trap"
- ::= { trapPrefix 20405 }
- --#####airFlowSensorTable#####--
- airFlowSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorAvail,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 availability trap"
- ::= { trapPrefix 10504 }
- airFlowSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorAvail,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 availability clear trap"
- ::= { trapPrefix 20504 }
- airFlowSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 temperature trap"
- ::= { trapPrefix 10505 }
- airFlowSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 temperature clear trap"
- ::= { trapPrefix 20505 }
- airFlowSensorFlowNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorFlow,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 airflow trap"
- ::= { trapPrefix 10506 }
- airFlowSensorFlowCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorFlow,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 airflow clear trap"
- ::= { trapPrefix 20506 }
- airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 humidity trap"
- ::= { trapPrefix 10507 }
- airFlowSensorHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 humidity clear trap"
- ::= { trapPrefix 20507 }
- airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 dewpoint trap"
- ::= { trapPrefix 10508 }
- airFlowSensorDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 dewpoint clear trap"
- ::= { trapPrefix 20508 }
- --#####t3hdSensorTable#####--
- t3hdSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorAvail,
- trapSeverity,
- sysName,
- t3hdSensorLabel
- }
- STATUS current
- DESCRIPTION "T3HD availability trap"
- ::= { trapPrefix 10804 }
- t3hdSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorAvail,
- trapSeverity,
- sysName,
- t3hdSensorLabel
- }
- STATUS current
- DESCRIPTION "T3HD availability clear trap"
- ::= { trapPrefix 20804 }
- t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal temperature trap"
- ::= { trapPrefix 10806 }
- t3hdSensorIntTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal temperature clear trap"
- ::= { trapPrefix 20806 }
- t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal humidity trap"
- ::= { trapPrefix 10807 }
- t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal humidity clear trap"
- ::= { trapPrefix 20807 }
- t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal dewpoint trap"
- ::= { trapPrefix 10808 }
- t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal dewpoint clear trap"
- ::= { trapPrefix 20808 }
- t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtATemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtALabel
- }
- STATUS current
- DESCRIPTION "T3HD External A temperature trap"
- ::= { trapPrefix 10811 }
- t3hdSensorExtATempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtATemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtALabel
- }
- STATUS current
- DESCRIPTION "T3HD External A temperature clear trap"
- ::= { trapPrefix 20811 }
- t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtBTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtBLabel
- }
- STATUS current
- DESCRIPTION "T3HD External B temperature trap"
- ::= { trapPrefix 10814 }
- t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtBTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtBLabel
- }
- STATUS current
- DESCRIPTION "T3HD External B temperature clear trap"
- ::= { trapPrefix 20814 }
- --#####thdSensorTable#####--
- thdSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorAvail,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD availability trap"
- ::= { trapPrefix 10904 }
- thdSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorAvail,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD availability clear trap"
- ::= { trapPrefix 20904 }
- thdSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD temperature trap"
- ::= { trapPrefix 10905 }
- thdSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD temperature clear trap"
- ::= { trapPrefix 20905 }
- thdSensorHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD humidity trap"
- ::= { trapPrefix 10906 }
- thdSensorHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD humidity clear trap"
- ::= { trapPrefix 20906 }
- thdSensorDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD dewpoint trap"
- ::= { trapPrefix 10907 }
- thdSensorDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD dewpoint clear trap"
- ::= { trapPrefix 20907 }
- --#####a2dSensorTable#####--
- a2dSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorAvail,
- trapSeverity,
- sysName,
- a2dSensorLabel
- }
- STATUS current
- DESCRIPTION "A2D availability trap"
- ::= { trapPrefix 11104 }
- a2dSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorAvail,
- trapSeverity,
- sysName,
- a2dSensorLabel
- }
- STATUS current
- DESCRIPTION "A2D availability clear trap"
- ::= { trapPrefix 21104 }
- a2dSensorValueNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- a2dSensorLabel,
- a2dSensorAnalogLabel,
- a2dSensorDisplayValue
- }
- STATUS current
- DESCRIPTION "A2D measurement trap"
- ::= { trapPrefix 11105 }
- a2dSensorValueCLEAR NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- a2dSensorLabel,
- a2dSensorAnalogLabel,
- a2dSensorDisplayValue
- }
- STATUS current
- DESCRIPTION "A2D measurement clear trap"
- ::= { trapPrefix 21105 }
- --#####humiditySensorTable#####--
- humiditySensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- humiditySensorAvail,
- trapSeverity,
- sysName,
- humiditySensorLabel
- }
- STATUS current
- DESCRIPTION "Remote humidity availability trap"
- ::= { trapPrefix 11204 }
- humiditySensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- humiditySensorAvail,
- trapSeverity,
- sysName,
- humiditySensorLabel
- }
- STATUS current
- DESCRIPTION "Remote humidity availability clear trap"
- ::= { trapPrefix 21204 }
- humiditySensorValueNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- humiditySensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- humiditySensorLabel
- }
- STATUS current
- DESCRIPTION "Remote humidity value trap"
- ::= { trapPrefix 11205 }
- humiditySensorValueCLEAR NOTIFICATION-TYPE
- OBJECTS {
- humiditySensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- humiditySensorLabel
- }
- STATUS current
- DESCRIPTION "Remote humidity value clear trap"
- ::= { trapPrefix 21205 }
- --#####sn2dSensorTable#####--
- sn2dSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorAvail,
- trapSeverity,
- sysName,
- sn2dSensorLabel
- }
- STATUS current
- DESCRIPTION "SN-2D availability trap"
- ::= { trapPrefix 11304 }
- sn2dSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorAvail,
- trapSeverity,
- sysName,
- sn2dSensorLabel
- }
- STATUS current
- DESCRIPTION "SN-2D availability clear trap"
- ::= { trapPrefix 21304 }
- sn2dSensorDoor1StateNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorDoor1State,
- trapThreshType,
- trapSeverity,
- sysName,
- sn2dSensorLabel,
- sn2dSensorDoor1Label,
- sn2dSensorDoor1DisplayState
- }
- STATUS current
- DESCRIPTION "SN-2D Door switch 1 state trap"
- ::= { trapPrefix 11306 }
- sn2dSensorDoor1StateCLEAR NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorDoor1State,
- trapThreshType,
- trapSeverity,
- sysName,
- sn2dSensorLabel,
- sn2dSensorDoor1Label,
- sn2dSensorDoor1DisplayState
- }
- STATUS current
- DESCRIPTION "SN-2D Door switch 1 state clear trap"
- ::= { trapPrefix 21306 }
- sn2dSensorDoor2StateNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorDoor2State,
- trapThreshType,
- trapSeverity,
- sysName,
- sn2dSensorLabel,
- sn2dSensorDoor2Label,
- sn2dSensorDoor2DisplayState
- }
- STATUS current
- DESCRIPTION "SN-2D Door switch 2 state trap"
- ::= { trapPrefix 11309 }
- sn2dSensorDoor2StateCLEAR NOTIFICATION-TYPE
- OBJECTS {
- sn2dSensorDoor2State,
- trapThreshType,
- trapSeverity,
- sysName,
- sn2dSensorLabel,
- sn2dSensorDoor2Label,
- sn2dSensorDoor2DisplayState
- }
- STATUS current
- DESCRIPTION "SN-2D Door switch 2 state clear trap"
- ::= { trapPrefix 21309 }
- --#####cooling#####--
- --#####vrc#####--
- --#####vrcMainTable#####--
- vrcMainAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcMainAvail,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC availability trap"
- ::= { trapPrefix 13001 }
- vrcMainAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcMainAvail,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC availability clear trap"
- ::= { trapPrefix 23001 }
- --#####vrcMainPtTable#####--
- --#####vrcMainCfgTable#####--
- --#####vrcOutFanPtTable#####--
- vrcOutFanPtSpeedNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcOutFanPtSpeed,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC out-fan speed trap"
- ::= { trapPrefix 13002 }
- vrcOutFanPtSpeedCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcOutFanPtSpeed,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC out-fan speed clear trap"
- ::= { trapPrefix 23002 }
- --#####vrcOutFanCfgTable#####--
- --#####vrcInFanPtTable#####--
- --#####vrcInFanCfgTable#####--
- --#####vrcCompPtTable#####--
- vrcCompPtCapacityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcCompPtCapacity,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC compressor capacity trap"
- ::= { trapPrefix 13003 }
- vrcCompPtCapacityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcCompPtCapacity,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC compressor capacity clear trap"
- ::= { trapPrefix 23003 }
- --#####vrcCompCfgTable#####--
- --#####vrcReturnPtTable#####--
- vrcReturnPtTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcReturnPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC return temperature trap"
- ::= { trapPrefix 13004 }
- vrcReturnPtTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcReturnPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC return temperature clear trap"
- ::= { trapPrefix 23004 }
- --#####vrcReturnCfgTable#####--
- --#####vrcSupplyPtTable#####--
- vrcSupplyPtTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcSupplyPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC supply temperature trap"
- ::= { trapPrefix 13005 }
- vrcSupplyPtTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcSupplyPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC supply temperature clear trap"
- ::= { trapPrefix 23005 }
- --#####vrcSupplyCfgTable#####--
- --#####vrcPowerPtTable#####--
- vrcPowerPtVoltageNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcPowerPtVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC power voltage trap"
- ::= { trapPrefix 13006 }
- vrcPowerPtVoltageCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcPowerPtVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC power voltage clear trap"
- ::= { trapPrefix 23006 }
- vrcPowerPtFrequencyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcPowerPtFrequency,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC power frequency trap"
- ::= { trapPrefix 13007 }
- vrcPowerPtFrequencyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcPowerPtFrequency,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC power frequency clear trap"
- ::= { trapPrefix 23007 }
- --#####vrcPowerCfgTable#####--
- --#####vrcOutdoorPtTable#####--
- vrcOutdoorPtTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcOutdoorPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC outdoor temperature trap"
- ::= { trapPrefix 13008 }
- vrcOutdoorPtTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcOutdoorPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC outdoor temperature clear trap"
- ::= { trapPrefix 23008 }
- --#####vrcDischPtTable#####--
- vrcDischPtTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcDischPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC discharge temperature trap"
- ::= { trapPrefix 13009 }
- vrcDischPtTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcDischPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC discharge temperature clear trap"
- ::= { trapPrefix 23009 }
- vrcDischPtPressureNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcDischPtPressure,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC discharge pressure trap"
- ::= { trapPrefix 13010 }
- vrcDischPtPressureCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcDischPtPressure,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC discharge pressure clear trap"
- ::= { trapPrefix 23010 }
- --#####vrcDischCfgTable#####--
- --#####vrcSuctPtTable#####--
- vrcSuctPtTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcSuctPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC suction temperature trap"
- ::= { trapPrefix 13011 }
- vrcSuctPtTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcSuctPtTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC suction temperature clear trap"
- ::= { trapPrefix 23011 }
- vrcSuctPtPressureNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- vrcSuctPtPressure,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC suction pressure trap"
- ::= { trapPrefix 13012 }
- vrcSuctPtPressureCLEAR NOTIFICATION-TYPE
- OBJECTS {
- vrcSuctPtPressure,
- trapThreshType,
- trapSeverity,
- sysName,
- vrcMainLabel
- }
- STATUS current
- DESCRIPTION "VRC suction pressure clear trap"
- ::= { trapPrefix 23012 }
- --#####vrcSuctCfgTable#####--
- --###########################################################################################--
- --common group--
- --###########################################################################################--
- common OBJECT IDENTIFIER ::= { vertiv 42 }
- identity OBJECT IDENTIFIER ::= { common 1 }
- i03 OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "Value given for sysObjectID on IMD3 units"
- ::= { identity 53 }
- r05 OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "Value given for sysObjectID on R-Series units"
- ::= { identity 15 }
- END