- -- Vertiv
- -- ITEI MIB
- ------------------------------------------------------------
- DCS-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,Integer32, Counter32, enterprises FROM SNMPv2-SMI
- TEXTUAL-CONVENTION, DisplayString, DateAndTime FROM SNMPv2-TC;
- ------------------------------------------------------------
- -- Node definitions
- ------------------------------------------------------------
- dcs MODULE-IDENTITY
- LAST-UPDATED "201808160000Z"
- ORGANIZATION "Vertiv"
- CONTACT-INFO "vertivc.service@vertivco.com"
- REVISION "201808160000Z"
- DESCRIPTION "Vertiv device MIB"
- ::= { enp 3 }
- enp OBJECT IDENTIFIER ::= { enterprises 13400 }
- ------------------------------------------------------------
- -- Textual conventions
- ------------------------------------------------------------
- AlarmSeverity ::= TEXTUAL-CONVENTION
- STATUS current
- DESCRIPTION "
- The severity of the alarm. One of
- (1) informational
- (2) warning
- (3) critical"
- SYNTAX INTEGER {
- informational(1),
- warning(2),
- critical(3) }
- AlarmStatusChange ::= TEXTUAL-CONVENTION
- STATUS current
- DESCRIPTION "
- Indicates 'activated' (0) or 'deactivated' (1) alarm events."
- SYNTAX INTEGER {
- activated(0),
- deactivated(1) }
- ------------------------------------------------------------
- -- System Info{ 13400.3.1 }
- ------------------------------------------------------------
- systemInfo OBJECT IDENTIFIER ::= { dcs 1 }
- systemLoaction OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Where is this Uint"
- ::= { systemInfo 1 }
- systemEquipNum OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "System Equipment Number"
- ::= { systemInfo 2 }
- systemEquipListTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SystemEquipListEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "System Equipment List Table"
- ::= { systemInfo 3 }
- systemEquipListEntry OBJECT-TYPE
- SYNTAX SystemEquipListEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "System Equipment List Entry"
- INDEX { systemEquipListIndex }
- ::= { systemEquipListTable 1 }
- SystemEquipListEntry ::= SEQUENCE {
- systemEquipListIndex Integer32,
- systemEquipTypeName DisplayString,
- systemEquipID Integer32,
- systemEquipTypeID Integer32}
- systemEquipListIndex OBJECT-TYPE
- SYNTAX Integer32(1..64)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "System Equipment List Index"
- ::= { systemEquipListEntry 1 }
- systemEquipTypeName OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "System Equipment Type Name"
- ::= { systemEquipListEntry 2 }
- systemEquipID OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "System Equipment ID"
- ::= { systemEquipListEntry 3 }
- systemEquipTypeID OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "System Equipment Type ID"
- ::= { systemEquipListEntry 4 }
- ------------------------------------------------------------
- -- System { 13400.3.1.100 }
- ------------------------------------------------------------
- rdua-System OBJECT IDENTIFIER ::= { systemInfo 100 }
- rduaSystemTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RduaSystemEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "rduaSystemTable"
- ::= { rdua-System 1 }
- rduaSystemEntry OBJECT-TYPE
- SYNTAX RduaSystemEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "rduaSystemEntry"
- INDEX { rduaSystemIndex }
- ::= { rduaSystemTable 1 }
- RduaSystemEntry ::= SEQUENCE {
- rduaSystemIndex Integer32,
- rduaSystemsSystemstatus INTEGER,
- rduaSystemsUnitInternalStatus INTEGER,
- rduaSystemsRunningConfigType INTEGER,
- rduaSystemsAutoManState INTEGER,
- rduaSystemsOutgoingAlarmBlocked INTEGER,
- rduaSystemsDatastatstartclock INTEGER,
- rduaSystemsDatastatperiod INTEGER }
- rduaSystemIndex OBJECT-TYPE
- SYNTAX Integer32(1..8)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "rduaSystem System Entry Index."
- ::= { rduaSystemEntry 1 }
- rduaSystemsSystemstatus OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "rduaSystemsSystemstatus status."
- ::= { rduaSystemEntry 2 }
- rduaSystemsUnitInternalStatus OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "rduaSystemsUnitInternalStatus status."
- ::= { rduaSystemEntry 3 }
- rduaSystemsRunningConfigType OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "rduaSystemsRunningConfigType status."
- ::= { rduaSystemEntry 4 }
- rduaSystemsAutoManState OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "rduaSystemsAuto/ManState status."
- ::= { rduaSystemEntry 5 }
- rduaSystemsOutgoingAlarmBlocked OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "rduaSystemsOutgoingAlarmBlocked status."
- ::= { rduaSystemEntry 6 }
- rduaSystemsDatastatstartclock OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "rduaSystemsDatastatstartclock oclock."
- ::= { rduaSystemEntry 7 }
- rduaSystemsDatastatperiod OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "rduaSystemsDatastatperiod h."
- ::= { rduaSystemEntry 8 }
- ------------------------------------------------------------
- -- Env { 13400.3.5 }
- ------------------------------------------------------------
- env OBJECT IDENTIFIER ::= { dcs 5 }
- ------------------------------------------------------------
- -- Tdicom { 13400.3.5.541 }
- ------------------------------------------------------------
- env-Tdicom OBJECT IDENTIFIER ::= { env 541 }
- envTdicomTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EnvTdicomEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "envTdicomTable"
- ::= { env-Tdicom 1 }
- envTdicomEntry OBJECT-TYPE
- SYNTAX EnvTdicomEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "envTdicomEntry"
- INDEX { envTdicomIndex }
- ::= { envTdicomTable 1 }
- EnvTdicomEntry ::= SEQUENCE {
- envTdicomIndex Integer32,
- envTdicom_2_FrontTemp Integer32,
- envTdicom_3_RearTemp Integer32,
- envTdicom_4_FrontDoor INTEGER,
- envTdicom_5_RearDoor INTEGER,
- envTdicom_6_Water INTEGER,
- envTdicom_7_FrontTempAlarmStatus INTEGER,
- envTdicom_8_RearTempAlarmStatus INTEGER,
- envTdicom_9_FrontSensorCommStatus INTEGER,
- envTdicom_10_RearSensorCommStatus INTEGER,
- envTdicom_11_4DICommStatus INTEGER,
- envTdicom_12_FrontSensorCommStatus INTEGER,
- envTdicom_13_FrontTempAlarmhystersis Integer32,
- envTdicom_14_RearTempAlarmhystersis Integer32,
- envTdicom_15_HighFrontTempAlarmlimit Integer32,
- envTdicom_16_HighRearTempAlarmlimit Integer32,
- envTdicom_17_LowFrontTempAlarmlimit Integer32,
- envTdicom_18_LightningArresterStatus INTEGER,
- envTdicom_19_OutsideCabinetTemp Integer32,
- envTdicom_20_OutsideCabinetHum Integer32 }
- envTdicomIndex OBJECT-TYPE
- SYNTAX Integer32(1..20)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom System Entry Index."
- ::= { envTdicomEntry 1 }
- envTdicom_2_FrontTemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_1_FrontTemp stored as 0.1℃."
- ::= { envTdicomEntry 2 }
- envTdicom_3_RearTemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_2_RearTemp stored as 0.1℃."
- ::= { envTdicomEntry 3 }
- envTdicom_4_FrontDoor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1),
- uninstalled(2),
- leave(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_3_FrontDoor status."
- ::= { envTdicomEntry 4 }
- envTdicom_5_RearDoor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1),
- uninstalled(2),
- leave(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_4_RearDoor status."
- ::= { envTdicomEntry 5 }
- envTdicom_6_Water OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1),
- uninstalled(2),
- leave(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_5_Water status."
- ::= { envTdicomEntry 6 }
- envTdicom_7_FrontTempAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- hightemp(1),
- lowtemp(2),
- invalid(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_6_FrontTempAlarmStatus status."
- ::= { envTdicomEntry 7 }
- envTdicom_8_RearTempAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- hightemp(1),
- lowtemp(2),
- invalid(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_7_RearTempAlarmStatus status."
- ::= { envTdicomEntry 8 }
- envTdicom_9_FrontSensorCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- failure(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_8_FrontSensorCommStatus status."
- ::= { envTdicomEntry 9 }
- envTdicom_10_RearSensorCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- failure(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_9_RearSensorCommStatus status."
- ::= { envTdicomEntry 10 }
- envTdicom_11_4DICommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- failure(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_10_4DICommStatus status."
- ::= { envTdicomEntry 11 }
- envTdicom_12_FrontSensorCommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- frontsensorcommstatus(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_11_FrontSensorCommStatus status."
- ::= { envTdicomEntry 12 }
- envTdicom_13_FrontTempAlarmhystersis OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_12_FrontTempAlarmhystersis stored as 1℃."
- ::= { envTdicomEntry 13 }
- envTdicom_14_RearTempAlarmhystersis OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_13_RearTempAlarmhystersis stored as 1℃."
- ::= { envTdicomEntry 14 }
- envTdicom_15_HighFrontTempAlarmlimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_14_HighFrontTempAlarmlimit stored as 1℃."
- ::= { envTdicomEntry 15 }
- envTdicom_16_HighRearTempAlarmlimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_15_HighRearTempAlarmlimit stored as 1℃."
- ::= { envTdicomEntry 16 }
- envTdicom_17_LowFrontTempAlarmlimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envTdicom_16_LowFrontTempAlarmlimit stored as 1℃."
- ::= { envTdicomEntry 17 }
- envTdicom_18_LightningArresterStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1),
- uninstalled(2),
- leave(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_17_LightningArresterStatus status."
- ::= { envTdicomEntry 18 }
- envTdicom_19_OutsideCabinetTemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_18_OutsideCabinetTemp stored as 0.1℃."
- ::= { envTdicomEntry 19 }
- envTdicom_20_OutsideCabinetHum OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envTdicom_19_OutsideCabinetHum stored as 0.1%."
- ::= { envTdicomEntry 20 }
- ------------------------------------------------------------
- -- 4dosensor { 13400.3.5.519 }
- ------------------------------------------------------------
- env-4dosensor OBJECT IDENTIFIER ::= { env 519 }
- env4dosensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Env4dosensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "env4dosensorTable"
- ::= { env-4dosensor 1 }
- env4dosensorEntry OBJECT-TYPE
- SYNTAX Env4dosensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "env4dosensorEntry"
- INDEX { env4dosensorIndex }
- ::= { env4dosensorTable 1 }
- Env4dosensorEntry ::= SEQUENCE {
- env4dosensorIndex Integer32,
- env4dosensor_2_RedLightStatus INTEGER,
- env4dosensor_3_BlueLightStatus INTEGER,
- env4dosensor_4_FanStatus INTEGER,
- env4dosensor_5_4DOF0CommunicateStatus INTEGER,
- env4dosensor_6_FanStatus INTEGER,
- env4dosensor_7_4DOF0CommOvertimeValue INTEGER }
- env4dosensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..7)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "env4dosensor System Entry Index."
- ::= { env4dosensorEntry 1 }
- env4dosensor_2_RedLightStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "env4dosensor_1_RedLightStatus status."
- ::= { env4dosensorEntry 2 }
- env4dosensor_3_BlueLightStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "env4dosensor_2_BlueLightStatus status."
- ::= { env4dosensorEntry 3 }
- env4dosensor_4_FanStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "env4dosensor_3_FanStatus status."
- ::= { env4dosensorEntry 5 }
- env4dosensor_5_4DOF0CommunicateStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- failure(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "env4dosensor_4_4DOF0CommunicateStatus status."
- ::= { env4dosensorEntry 42 }
- env4dosensor_6_FanStatus OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "env4dosensor_5_FanStatus status."
- ::= { env4dosensorEntry 49 }
- env4dosensor_7_4DOF0CommOvertimeValue OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "env4dosensor_6_4DOF0CommOvertimeValue stored as 1Min."
- ::= { env4dosensorEntry 62 }
- ------------------------------------------------------------
- -- Ups { 13400.3.4 }
- ------------------------------------------------------------
- ups OBJECT IDENTIFIER ::= { dcs 4 }
- ------------------------------------------------------------
- -- Ita2com { 13400.3.4.491 }
- ------------------------------------------------------------
- ups-Ita2com OBJECT IDENTIFIER ::= { ups 491 }
- upsIta2comTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsIta2comEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "upsIta2comTable"
- ::= { ups-Ita2com 1 }
- upsIta2comEntry OBJECT-TYPE
- SYNTAX UpsIta2comEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "upsIta2comEntry"
- INDEX { upsIta2comIndex }
- ::= { upsIta2comTable 1 }
- UpsIta2comEntry ::= SEQUENCE {
- upsIta2comIndex Integer32,
- upsIta2com_2_PhaseAInputVoltage Integer32,
- upsIta2com_3_PhaseBInputVoltage Integer32,
- upsIta2com_4_PhaseCInputVoltage Integer32,
- upsIta2com_5_PhaseAOutputVoltage Integer32,
- upsIta2com_6_PhaseBOutputVoltage Integer32,
- upsIta2com_7_PhaseCOutputVoltage Integer32,
- upsIta2com_8_PhaseAOutputCurrent Integer32,
- upsIta2com_9_PhaseBOutputCurrent Integer32,
- upsIta2com_10_PhaseCOutputCurrent Integer32,
- upsIta2com_11_OutputFrequency Integer32,
- upsIta2com_12_InputPhaseNumber INTEGER,
- upsIta2com_13_LineAbInputVoltage Integer32,
- upsIta2com_14_LineBcInputVoltage Integer32,
- upsIta2com_15_LineCaInputVoltage Integer32,
- upsIta2com_16_PhaseAInputCurrent Integer32,
- upsIta2com_17_PhaseBInputCurrent Integer32,
- upsIta2com_18_PhaseCInputCurrent Integer32,
- upsIta2com_19_SystemInputFrequency Integer32,
- upsIta2com_20_PhaseAInputPowerFactor Integer32,
- upsIta2com_21_PhaseBInputPowerFactor Integer32,
- upsIta2com_22_PhaseCInputPowerFactor Integer32,
- upsIta2com_23_BypassAVoltageA Integer32,
- upsIta2com_24_BypassBVoltageB Integer32,
- upsIta2com_25_BypassCVoltageC Integer32,
- upsIta2com_26_BypassLineAbVoltage Integer32,
- upsIta2com_27_BypassLineBcVoltage Integer32,
- upsIta2com_28_BypassLineCaVoltage Integer32,
- upsIta2com_29_BypassFrequency Integer32,
- upsIta2com_30_BusvoltageP Integer32,
- upsIta2com_31_BusvoltageN Integer32,
- upsIta2com_32_OutputPhaseNumber INTEGER,
- upsIta2com_33_PhaseAOutputPowerFactor Integer32,
- upsIta2com_34_PhaseBOutputPowerFactor Integer32,
- upsIta2com_35_PhaseCOutputPowerFactor Integer32,
- upsIta2com_36_LPhaseAOutputPeakRatio Integer32,
- upsIta2com_37_LPhaseBOutputPeakRatio Integer32,
- upsIta2com_38_LPhaseCOutputPeakRatio Integer32,
- upsIta2com_39_LPhaseAOutputActivePower Integer32,
- upsIta2com_40_LPhaseBOutputActivePower Integer32,
- upsIta2com_41_LPhaseCOutputActivePower Integer32,
- upsIta2com_42_LPhaseAOutputApparentPower Integer32,
- upsIta2com_43_LPhaseBOutputApparentPower Integer32,
- upsIta2com_44_LPhaseCOutputApparentPower Integer32,
- upsIta2com_45_LPhaseAOutputLoadPercent Integer32,
- upsIta2com_46_LPhaseBOutputLoadPercent Integer32,
- upsIta2com_47_LPhaseCOutputLoadPercent Integer32,
- upsIta2com_48_SPhaseAOutputPowerFactor Integer32,
- upsIta2com_49_SPhaseBOutputPowerFactor Integer32,
- upsIta2com_50_SPhaseCOutputPowerFactor Integer32,
- upsIta2com_51_SPhaseAOutputActivePower Integer32,
- upsIta2com_52_SPhaseBOutputActivePower Integer32,
- upsIta2com_53_SPhaseCOutputActivePower Integer32,
- upsIta2com_54_SPhaseAOutputApparentPower Integer32,
- upsIta2com_55_SPhaseBOutputApparentPower Integer32,
- upsIta2com_56_SPhaseCOutputApparentPower Integer32,
- upsIta2com_57_ParallelMachineNumber Integer32,
- upsIta2com_58_UpsRunningTime Integer32,
- upsIta2com_59_BatVoltage Integer32,
- upsIta2com_60_BatChargingCurrent Integer32,
- upsIta2com_61_BatDischargeCurrent Integer32,
- upsIta2com_62_NegativeBatVoltage Integer32,
- upsIta2com_63_NegativeBatChargeCurrent Integer32,
- upsIta2com_64_NegativeBatDischargeCurrent Integer32,
- upsIta2com_65_BatBackupTime Integer32,
- upsIta2com_66_Battemp Integer32,
- upsIta2com_67_Ambienttemp Integer32,
- upsIta2com_68_BatCurrentCapacity Integer32,
- upsIta2com_69_BatDischargeTimes Integer32,
- upsIta2com_70_BatHelth Integer32,
- upsIta2com_71_InputPower Integer32,
- upsIta2com_72_OutputPower Integer32,
- upsIta2com_73_BatRunningTime Integer32,
- upsIta2com_74_BatDischargingTime Integer32,
- upsIta2com_75_PowerSupply INTEGER,
- upsIta2com_76_InputPowerStatus INTEGER,
- upsIta2com_77_BatStatus INTEGER,
- upsIta2com_78_BatNegativeGroupStatus INTEGER,
- upsIta2com_79_ChargerStatus INTEGER,
- upsIta2com_80_ParallelSystemPowerState INTEGER,
- upsIta2com_81_IneerNetworkconnectStatus INTEGER,
- upsIta2com_82_Outlet1SwitchStatus INTEGER,
- upsIta2com_83_Outlet2SwitchStatus INTEGER,
- upsIta2com_84_InputAbnormal INTEGER,
- upsIta2com_85_SystemOvertemp INTEGER,
- upsIta2com_86_SystemBatLowPreWarning INTEGER,
- upsIta2com_87_InputPhaseReversed INTEGER,
- upsIta2com_88_InputNeutralLost INTEGER,
- upsIta2com_89_InputGroundLost INTEGER,
- upsIta2com_90_RectifierOverload INTEGER,
- upsIta2com_91_BatCabinetNotConnected INTEGER,
- upsIta2com_92_InverterOverload INTEGER,
- upsIta2com_93_LbsAbnormal INTEGER,
- upsIta2com_94_OutputPending INTEGER,
- upsIta2com_95_OutputDisabled INTEGER,
- upsIta2com_96_BypassAbnormal INTEGER,
- upsIta2com_97_BypassAbnormalInEcoMode INTEGER,
- upsIta2com_98_BypassPhaseReversed INTEGER,
- upsIta2com_99_BypassOvercurrent INTEGER,
- upsIta2com_100_BypassCableconnectAbnormal INTEGER,
- upsIta2com_101_BatReversed INTEGER,
- upsIta2com_102_BatLowPreWarning INTEGER,
- upsIta2com_103_BatVoltAbnormal INTEGER,
- upsIta2com_104_NoBat INTEGER,
- upsIta2com_105_BatOvertemp INTEGER,
- upsIta2com_106_BatAging INTEGER,
- upsIta2com_107_BatTestFailure INTEGER,
- upsIta2com_108_BatSeriesNotQualified INTEGER,
- upsIta2com_109_FanFailure INTEGER,
- upsIta2com_110_Repo INTEGER,
- upsIta2com_111_ElectricLeakAlarm INTEGER,
- upsIta2com_112_VersionIncompatible INTEGER,
- upsIta2com_113_OutputLpeShort INTEGER,
- upsIta2com_114_LossOfRedundancy INTEGER,
- upsIta2com_115_SystemOverload INTEGER,
- upsIta2com_116_LoadSharingAbnormal INTEGER,
- upsIta2com_117_SystemParallelSetsAsync INTEGER,
- upsIta2com_118_LocalParallelSetsAsync INTEGER,
- upsIta2com_119_OnMaintenanceBypass INTEGER,
- upsIta2com_120_BatMode INTEGER,
- upsIta2com_121_BypassMode INTEGER,
- upsIta2com_122_ParallelNoAbnormal INTEGER,
- upsIta2com_123_BypassCableconnectAbnormal INTEGER,
- upsIta2com_124_OnIntelligentSleepMode INTEGER,
- upsIta2com_125_BatCabinetConnectAbnormal INTEGER,
- upsIta2com_126_SystemFault INTEGER,
- upsIta2com_127_EodTurnOff INTEGER,
- upsIta2com_128_Bypassdisable INTEGER,
- upsIta2com_129_UPShasnooutput INTEGER,
- upsIta2com_130_Outputvoltageabnormal INTEGER,
- upsIta2com_131_Localoutputisdisconnected INTEGER,
- upsIta2com_132_Turnonfailed INTEGER,
- upsIta2com_133_Inputfrequencyabnormal INTEGER,
- upsIta2com_134_Fanagingtimealarm INTEGER,
- upsIta2com_135_Bypassovercurrenttimeout INTEGER,
- upsIta2com_136_BatDCgroundfault INTEGER,
- upsIta2com_137_Systemredundantoverload INTEGER,
- upsIta2com_138_BatCommfail INTEGER,
- upsIta2com_139_BatummatchtheUPS INTEGER,
- upsIta2com_140_BatAddrsetwrong INTEGER,
- upsIta2com_141_Batmodelnotqualified INTEGER,
- upsIta2com_142_BatSNabnormal INTEGER,
- upsIta2com_143_Batcabinetconnectabnormal INTEGER,
- upsIta2com_144_BatCANconnectabnormal INTEGER,
- upsIta2com_145_BatNoexceedthelimit INTEGER,
- upsIta2com_146_BatgrouplessForbiddischarge INTEGER,
- upsIta2com_147_Ambienttemplowprealarm INTEGER,
- upsIta2com_148_Ambienttemphighprealarm INTEGER,
- upsIta2com_149_DcBusAbnormal INTEGER,
- upsIta2com_150_RectifierFault INTEGER,
- upsIta2com_151_DcDcFault INTEGER,
- upsIta2com_152_ChargerFault INTEGER,
- upsIta2com_153_InputBackfeed INTEGER,
- upsIta2com_154_InverterFault INTEGER,
- upsIta2com_155_InverterRelayWelded INTEGER,
- upsIta2com_156_BypassBackfeed INTEGER,
- upsIta2com_157_AuxiliaryPowerFault INTEGER,
- upsIta2com_158_InternalCommFault INTEGER,
- upsIta2com_159_OutputShortCircuit INTEGER,
- upsIta2com_160_OutputOffAndVoltageIsNotZero INTEGER,
- upsIta2com_161_ParallelCommBreakdown INTEGER,
- upsIta2com_162_ParallelCableconnectAbnormal INTEGER,
- upsIta2com_163_Systemfault INTEGER,
- upsIta2com_164_Rectifiersoftstartfail INTEGER,
- upsIta2com_165_DSPfault INTEGER,
- upsIta2com_166_Year INTEGER,
- upsIta2com_167_Month INTEGER,
- upsIta2com_168_Day INTEGER,
- upsIta2com_169_Hour INTEGER,
- upsIta2com_170_Minute INTEGER,
- upsIta2com_171_Second INTEGER,
- upsIta2com_172_InputBackfeed INTEGER,
- upsIta2com_173_BypassBackfeed INTEGER,
- upsIta2com_174_Addr1Batmoduleonline INTEGER,
- upsIta2com_175_Addr2Batmoduleonline INTEGER,
- upsIta2com_176_Addr3Batmoduleonline INTEGER,
- upsIta2com_177_Addr4Batmoduleonline INTEGER,
- upsIta2com_178_Addr5Batmoduleonline INTEGER,
- upsIta2com_179_Addr6Batmoduleonline INTEGER,
- upsIta2com_180_Addr7Batmoduleonline INTEGER,
- upsIta2com_181_Addr8Batmoduleonline INTEGER,
- upsIta2com_182_Addr9Batmoduleonline INTEGER,
- upsIta2com_183_Addr10Batmoduleonline INTEGER,
- upsIta2com_184_Addr11Batmoduleonline INTEGER,
- upsIta2com_185_Addr12Batmoduleonline INTEGER,
- upsIta2com_186_Addr13Batmoduleonline INTEGER,
- upsIta2com_187_Addr14Batmoduleonline INTEGER,
- upsIta2com_188_Addr15Batmoduleonline INTEGER,
- upsIta2com_189_Addr16Batmoduleonline INTEGER,
- upsIta2com_190_Addr1Batstatus INTEGER,
- upsIta2com_191_Addr1lithiumBatvoltage Integer32,
- upsIta2com_192_Addr1lithiumBatcurrent Integer32,
- upsIta2com_193_Addr1lithiumBatSOC Integer32,
- upsIta2com_194_Addr1lithiumBatSOH Integer32,
- upsIta2com_195_Addr1lithiumBatcellmaxvoltage Integer32,
- upsIta2com_196_Addr1lithiumBatcellminvoltage Integer32,
- upsIta2com_197_Addr1lithiumBatcellmaxtemp Integer32,
- upsIta2com_198_Addr1lithiumBatcellmintemp Integer32,
- upsIta2com_199_Addr2Batstatus INTEGER,
- upsIta2com_200_Addr2lithiumBatvoltage Integer32,
- upsIta2com_201_Addr2lithiumBatcurrent Integer32,
- upsIta2com_202_Addr2lithiumBatSOC Integer32,
- upsIta2com_203_Addr2lithiumBatSOH Integer32,
- upsIta2com_204_Addr2lithiumBatcellmaxvoltage Integer32,
- upsIta2com_205_Addr2lithiumBatcellminvoltage Integer32,
- upsIta2com_206_Addr2lithiumBatcellmaxtemp Integer32,
- upsIta2com_207_Addr2lithiumBatcellmintemp Integer32,
- upsIta2com_208_Addr3Batstatus INTEGER,
- upsIta2com_209_Addr3lithiumBatvoltage Integer32,
- upsIta2com_210_Addr3lithiumBatcurrent Integer32,
- upsIta2com_211_Addr3lithiumBatSOC Integer32,
- upsIta2com_212_Addr3lithiumBatSOH Integer32,
- upsIta2com_213_Addr3lithiumBatcellmaxvoltage Integer32,
- upsIta2com_214_Addr3lithiumBatcellminvoltage Integer32,
- upsIta2com_215_Addr3lithiumBatcellmaxtemp Integer32,
- upsIta2com_216_Addr3lithiumBatcellmintemp Integer32,
- upsIta2com_217_Addr4Batstatus INTEGER,
- upsIta2com_218_Addr4lithiumBatvoltage Integer32,
- upsIta2com_219_Addr4lithiumBatcurrent Integer32,
- upsIta2com_220_Addr4lithiumBatSOC Integer32,
- upsIta2com_221_Addr4lithiumBatSOH Integer32,
- upsIta2com_222_Addr4lithiumBatcellmaxvoltage Integer32,
- upsIta2com_223_Addr4lithiumBatcellminvoltage Integer32,
- upsIta2com_224_Addr4lithiumBatcellmaxtemp Integer32,
- upsIta2com_225_Addr4lithiumBatcellmintemp Integer32,
- upsIta2com_226_Addr5Batstatus INTEGER,
- upsIta2com_227_Addr5lithiumBatvoltage Integer32,
- upsIta2com_228_Addr5LithiumBatCurrent Integer32,
- upsIta2com_229_Addr5lithiumBatSOC Integer32,
- upsIta2com_230_Addr5lithiumBatSOH Integer32,
- upsIta2com_231_Addr5lithiumBatcellmaxvoltage Integer32,
- upsIta2com_232_Addr5lithiumBatcellminvoltage Integer32,
- upsIta2com_233_Addr5lithiumBatcellmaxtemp Integer32,
- upsIta2com_234_Addr5lithiumBatcellmintemp Integer32,
- upsIta2com_235_Addr6Batstatus INTEGER,
- upsIta2com_236_Addr6lithiumBatvoltage Integer32,
- upsIta2com_237_Addr6lithiumBatcurrent Integer32,
- upsIta2com_238_Addr6lithiumBatSOC Integer32,
- upsIta2com_239_Addr6lithiumBatSOH Integer32,
- upsIta2com_240_Addr6lithiumBatcellmaxvoltage Integer32,
- upsIta2com_241_Addr6lithiumBatcellminvoltage Integer32,
- upsIta2com_242_Addr6lithiumBatcellmaxtemp Integer32,
- upsIta2com_243_Addr6lithiumBatcellmintemp Integer32,
- upsIta2com_244_Addr7Batstatus INTEGER,
- upsIta2com_245_Addr7lithiumBatvoltage Integer32,
- upsIta2com_246_Addr7lithiumBatcurrent Integer32,
- upsIta2com_247_Addr7lithiumBatSOC Integer32,
- upsIta2com_248_Addr7lithiumBatSOH Integer32,
- upsIta2com_249_Addr7lithiumBatcellmaxvoltage Integer32,
- upsIta2com_250_Addr7lithiumBatcellminvoltage Integer32,
- upsIta2com_251_Addr7lithiumBatcellmaxtemp Integer32,
- upsIta2com_252_Addr7lithiumBatcellmintemp Integer32,
- upsIta2com_253_Addr8Batstatus INTEGER,
- upsIta2com_254_Addr8lithiumBatvoltage Integer32,
- upsIta2com_255_Addr8lithiumBatcurrent Integer32,
- upsIta2com_256_Addr8lithiumBatSOC Integer32,
- upsIta2com_257_Addr8lithiumBatSOH Integer32,
- upsIta2com_258_Addr8lithiumBatcellmaxvoltage Integer32,
- upsIta2com_259_Addr8lithiumBatcellminvoltage Integer32,
- upsIta2com_260_Addr8lithiumBatcellmaxtemp Integer32,
- upsIta2com_261_Addr8lithiumBatcellmintemp Integer32,
- upsIta2com_262_Addr9Batstatus INTEGER,
- upsIta2com_263_Addr9lithiumBatvoltage Integer32,
- upsIta2com_264_Addr9lithiumBatcurrent Integer32,
- upsIta2com_265_Addr9lithiumBatSOC Integer32,
- upsIta2com_266_Addr9lithiumBatSOH Integer32,
- upsIta2com_267_Addr9lithiumBatcellmaxvoltage Integer32,
- upsIta2com_268_Addr9lithiumBatcellminvoltage Integer32,
- upsIta2com_269_Addr9lithiumBatcellmaxtemp Integer32,
- upsIta2com_270_Addr9lithiumBatcellmintemp Integer32,
- upsIta2com_271_Addr10Batstatus INTEGER,
- upsIta2com_272_Addr10lithiumBatvoltage Integer32,
- upsIta2com_273_Addr10lithiumBatcurrent Integer32,
- upsIta2com_274_Addr10lithiumBatSOC Integer32,
- upsIta2com_275_Addr10lithiumBatSOH Integer32,
- upsIta2com_276_Addr10lithiumBatcellmaxvoltage Integer32,
- upsIta2com_277_Addr10lithiumBatcellminvoltage Integer32,
- upsIta2com_278_Addr10lithiumBatcellmaxtemp Integer32,
- upsIta2com_279_Addr10lithiumBatcellmintemp Integer32,
- upsIta2com_280_Addr11Batstatus INTEGER,
- upsIta2com_281_Addr11lithiumBatvoltage Integer32,
- upsIta2com_282_Addr11lithiumBatcurrent Integer32,
- upsIta2com_283_Addr11lithiumBatSOC Integer32,
- upsIta2com_284_Addr11lithiumBatSOH Integer32,
- upsIta2com_285_Addr11lithiumBatcellmaxvoltage Integer32,
- upsIta2com_286_Addr11lithiumBatcellminvoltage Integer32,
- upsIta2com_287_Addr11lithiumBatcellmaxtemp Integer32,
- upsIta2com_288_Addr11lithiumBatcellmintemp Integer32,
- upsIta2com_289_Addr12Batstatus INTEGER,
- upsIta2com_290_Addr12lithiumBatvoltage Integer32,
- upsIta2com_291_Addr12lithiumBatcurrent Integer32,
- upsIta2com_292_Addr12lithiumBatSOC Integer32,
- upsIta2com_293_Addr12lithiumBatSOH Integer32,
- upsIta2com_294_Addr12lithiumBatcellmaxvoltage Integer32,
- upsIta2com_295_Addr12lithiumBatcellminvoltage Integer32,
- upsIta2com_296_Addr12lithiumBatcellmaxtemp Integer32,
- upsIta2com_297_Addr12lithiumBatcellmintemp Integer32,
- upsIta2com_298_Addr13Batstatus INTEGER,
- upsIta2com_299_Addr13lithiumBatvoltage Integer32,
- upsIta2com_300_Addr13lithiumBatcurrent Integer32,
- upsIta2com_301_Addr13lithiumBatSOC Integer32,
- upsIta2com_302_Addr13lithiumBatSOH Integer32,
- upsIta2com_303_Addr13lithiumBatcellmaxvoltage Integer32,
- upsIta2com_304_Addr13lithiumBatcellminvoltage Integer32,
- upsIta2com_305_Addr13lithiumBatcellmaxtemp Integer32,
- upsIta2com_306_Addr13lithiumBatcellmintemp Integer32,
- upsIta2com_307_Addr14Batstatus INTEGER,
- upsIta2com_308_Addr14lithiumBatvoltage Integer32,
- upsIta2com_309_Addr14LithiumBatCurrent Integer32,
- upsIta2com_310_Addr14lithiumBatSOC Integer32,
- upsIta2com_311_Addr14lithiumBatSOH Integer32,
- upsIta2com_312_Addr14lithiumBatcellmaxvoltage Integer32,
- upsIta2com_313_Addr14lithiumBatcellminvoltage Integer32,
- upsIta2com_314_Addr14lithiumBatcellmaxtemp Integer32,
- upsIta2com_315_Addr14lithiumBatcellmintemp Integer32,
- upsIta2com_316_Addr15Batstatus INTEGER,
- upsIta2com_317_Addr15lithiumBatvoltage Integer32,
- upsIta2com_318_Addr15lithiumBatcurrent Integer32,
- upsIta2com_319_Addr15lithiumBatSOC Integer32,
- upsIta2com_320_Addr15lithiumBatSOH Integer32,
- upsIta2com_321_Addr15lithiumBatcellmaxvoltage Integer32,
- upsIta2com_322_Addr15lithiumBatcellminvoltage Integer32,
- upsIta2com_323_Addr15lithiumBatcellmaxtemp Integer32,
- upsIta2com_324_Addr15lithiumBatcellmintemp Integer32,
- upsIta2com_325_Addr16Batstatus INTEGER,
- upsIta2com_326_Addr16lithiumBatvoltage Integer32,
- upsIta2com_327_Addr16lithiumBatcurrent Integer32,
- upsIta2com_328_Addr16lithiumBatSOC Integer32,
- upsIta2com_329_Addr16lithiumBatSOH Integer32,
- upsIta2com_330_Addr16lithiumBatcellmaxvoltage Integer32,
- upsIta2com_331_Addr16lithiumBatcellminvoltage Integer32,
- upsIta2com_332_Addr16lithiumBatcellmaxtemp Integer32,
- upsIta2com_333_Addr16lithiumBatcellmintemp Integer32,
- upsIta2com_334_Addr1Batalarmnumber Integer32,
- upsIta2com_335_Addr1Bathighvolt INTEGER,
- upsIta2com_336_Addr1Batlowvolt INTEGER,
- upsIta2com_337_Addr1Bathighcellvolt INTEGER,
- upsIta2com_338_Addr1Batlowcellvolt INTEGER,
- upsIta2com_339_Addr1Batchargehighcelltemp INTEGER,
- upsIta2com_340_Addr1Batchargelowcelltemp INTEGER,
- upsIta2com_341_Addr1Batchargeovercurrent INTEGER,
- upsIta2com_342_Addr1Batdischargeovercurrent INTEGER,
- upsIta2com_343_Addr1BatAddrconflict INTEGER,
- upsIta2com_344_Addr1Batportreverse INTEGER,
- upsIta2com_345_Addr1BatBMSrelayinvalid INTEGER,
- upsIta2com_346_Addr1Batsafetyundervoltage INTEGER,
- upsIta2com_347_Addr1Batdischargehighcelltemp INTEGER,
- upsIta2com_348_Addr1Batdischargelowcelltemp INTEGER,
- upsIta2com_349_Addr1Batparallelchargehightemp INTEGER,
- upsIta2com_350_Addr1BatinternalCommabnormal INTEGER,
- upsIta2com_351_Addr1Batconditionfail INTEGER,
- upsIta2com_352_Addr1BatLowinsulationresistance INTEGER,
- upsIta2com_353_Addr1BatLargepressurediff INTEGER,
- upsIta2com_354_Addr1BatBatfailure INTEGER,
- upsIta2com_355_Addr1BatVoltageacquisitfailure INTEGER,
- upsIta2com_356_Addr1BatCurrentcolllectfailure INTEGER,
- upsIta2com_357_Addr1BatTempcolllectfailure INTEGER,
- upsIta2com_358_Addr1BatAddrSeterror INTEGER,
- upsIta2com_359_Addr1BatLargegrouppressurediff INTEGER,
- upsIta2com_360_Addr1BatMOSFETfailure INTEGER,
- upsIta2com_361_Addr1Battempabnormal INTEGER,
- upsIta2com_362_Addr1Batcablefault INTEGER,
- upsIta2com_363_Addr1BatShortcircuit INTEGER,
- upsIta2com_364_Addr1BatOtherfailures INTEGER,
- upsIta2com_365_Addr1BatCommcablefailure INTEGER,
- upsIta2com_366_Addr1BatMOSFETtempishigh INTEGER,
- upsIta2com_367_Addr1BatFuseblown INTEGER,
- upsIta2com_368_Addr1BatWaitingforcharging INTEGER,
- upsIta2com_369_Addr1BatBataging INTEGER,
- upsIta2com_370_Addr1Batboxconnectabnormal INTEGER,
- upsIta2com_371_Addr1batBatterySoftincompatible INTEGER,
- upsIta2com_372_Addr1batEOL INTEGER,
- upsIta2com_373_Addr1batSamplingfailure INTEGER,
- upsIta2com_374_Addr1batHardwareprotection INTEGER,
- upsIta2com_375_Addr1batBatterycapacitylow INTEGER,
- upsIta2com_376_Addr2Batalarmnumber Integer32,
- upsIta2com_377_Addr2Bathighvolt INTEGER,
- upsIta2com_378_Addr2Batlowvolt INTEGER,
- upsIta2com_379_Addr2Bathighcellvolt INTEGER,
- upsIta2com_380_Addr2Batlowcellvolt INTEGER,
- upsIta2com_381_Addr2Batchargehighcelltemp INTEGER,
- upsIta2com_382_Addr2Batchargelowcelltemp INTEGER,
- upsIta2com_383_Addr2Batchargeovercurrent INTEGER,
- upsIta2com_384_Addr2Batdischargeovercurrent INTEGER,
- upsIta2com_385_Addr2BatAddrconflict INTEGER,
- upsIta2com_386_Addr2Batportreverse INTEGER,
- upsIta2com_387_Addr2BatBMSrelayinvalid INTEGER,
- upsIta2com_388_Addr2Batsafetyundervoltage INTEGER,
- upsIta2com_389_Addr2Batdischargehighcelltemp INTEGER,
- upsIta2com_390_Addr2Batdischargelowcelltemp INTEGER,
- upsIta2com_391_Addr2Batparallelchargehightemp INTEGER,
- upsIta2com_392_Addr2BatinternalCommabnormal INTEGER,
- upsIta2com_393_Addr2Batconditionfail INTEGER,
- upsIta2com_394_Addr2BatLowinsulationresistance INTEGER,
- upsIta2com_395_Addr2BatLargepressurediff INTEGER,
- upsIta2com_396_Addr2BatBatfailure INTEGER,
- upsIta2com_397_Addr2BatVoltageacquisitfailure INTEGER,
- upsIta2com_398_Addr2BatCurrentcolllectfailure INTEGER,
- upsIta2com_399_Addr2BatTempcolllectfailure INTEGER,
- upsIta2com_400_Addr2BatAddrSeterror INTEGER,
- upsIta2com_401_Addr2BatLargegrouppressurediff INTEGER,
- upsIta2com_402_Addr2BatMOSFETfailure INTEGER,
- upsIta2com_403_Addr2Battempabnormal INTEGER,
- upsIta2com_404_Addr2Batcablefault INTEGER,
- upsIta2com_405_Addr2BatShortcircuit INTEGER,
- upsIta2com_406_Addr2BatOtherfailures INTEGER,
- upsIta2com_407_Addr2BatCommcablefailure INTEGER,
- upsIta2com_408_Addr2BatMOSFETtempishigh INTEGER,
- upsIta2com_409_Addr2BatFuseblown INTEGER,
- upsIta2com_410_Addr2BatWaitingforcharging INTEGER,
- upsIta2com_411_Addr2BatBataging INTEGER,
- upsIta2com_412_Addr2Batboxconnectabnormal INTEGER,
- upsIta2com_413_Addr2batBatterySoftincompatible INTEGER,
- upsIta2com_414_Addr2batEOL INTEGER,
- upsIta2com_415_Addr2batSamplingfailure INTEGER,
- upsIta2com_416_Addr2batHardwareprotection INTEGER,
- upsIta2com_417_Addr2batBatterycapacitylow INTEGER,
- upsIta2com_418_Addr3Batalarmnumber Integer32,
- upsIta2com_419_Addr3Bathighvolt INTEGER,
- upsIta2com_420_Addr3Batlowvolt INTEGER,
- upsIta2com_421_Addr3Bathighcellvolt INTEGER,
- upsIta2com_422_Addr3Batlowcellvolt INTEGER,
- upsIta2com_423_Addr3Batchargehighcelltemp INTEGER,
- upsIta2com_424_Addr3Batchargelowcelltemp INTEGER,
- upsIta2com_425_Addr3Batchargeovercurrent INTEGER,
- upsIta2com_426_Addr3Batdischargeovercurrent INTEGER,
- upsIta2com_427_Addr3BatAddrconflict INTEGER,
- upsIta2com_428_Addr3Batportreverse INTEGER,
- upsIta2com_429_Addr3BatBMSrelayinvalid INTEGER,
- upsIta2com_430_Addr3Batsafetyundervoltage INTEGER,
- upsIta2com_431_Addr3Batdischargehighcelltemp INTEGER,
- upsIta2com_432_Addr3Batdischargelowcelltemp INTEGER,
- upsIta2com_433_Addr3Batparallelchargehightemp INTEGER,
- upsIta2com_434_Addr3BatinternalCommabnormal INTEGER,
- upsIta2com_435_Addr3Batconditionfail INTEGER,
- upsIta2com_436_Addr3BatLowinsulationresistance INTEGER,
- upsIta2com_437_Addr3BatLargepressurediff INTEGER,
- upsIta2com_438_Addr3BatBatfailure INTEGER,
- upsIta2com_439_Addr3BatVoltageacquisitfailure INTEGER,
- upsIta2com_440_Addr3BatCurrentcolllectfailure INTEGER,
- upsIta2com_441_Addr3BatTempcolllectfailure INTEGER,
- upsIta2com_442_Addr3BatAddrSeterror INTEGER,
- upsIta2com_443_Addr3BatLargegrouppressurediff INTEGER,
- upsIta2com_444_Addr3BatMOSFETfailure INTEGER,
- upsIta2com_445_Addr3Battempabnormal INTEGER,
- upsIta2com_446_Addr3Batcablefault INTEGER,
- upsIta2com_447_Addr3BatShortcircuit INTEGER,
- upsIta2com_448_Addr3BatOtherfailures INTEGER,
- upsIta2com_449_Addr3BatCommcablefailure INTEGER,
- upsIta2com_450_Addr3BatMOSFETtempishigh INTEGER,
- upsIta2com_451_Addr3BatFuseblown INTEGER,
- upsIta2com_452_Addr3BatWaitingforcharging INTEGER,
- upsIta2com_453_Addr3BatBataging INTEGER,
- upsIta2com_454_Addr3Batboxconnectabnormal INTEGER,
- upsIta2com_455_Addr3batBatterySoftincompatible INTEGER,
- upsIta2com_456_Addr3batEOL INTEGER,
- upsIta2com_457_Addr3batSamplingfailure INTEGER,
- upsIta2com_458_Addr3batHardwareprotection INTEGER,
- upsIta2com_459_Addr3batBatterycapacitylow INTEGER,
- upsIta2com_460_Addr4Batalarmnumber Integer32,
- upsIta2com_461_Addr4Bathighvolt INTEGER,
- upsIta2com_462_Addr4Batlowvolt INTEGER,
- upsIta2com_463_Addr4Bathighcellvolt INTEGER,
- upsIta2com_464_Addr4Batlowcellvolt INTEGER,
- upsIta2com_465_Addr4Batchargehighcelltemp INTEGER,
- upsIta2com_466_Addr4Batchargelowcelltemp INTEGER,
- upsIta2com_467_Addr4Batchargeovercurrent INTEGER,
- upsIta2com_468_Addr4Batdischargeovercurrent INTEGER,
- upsIta2com_469_Addr4BatAddrconflict INTEGER,
- upsIta2com_470_Addr4Batportreverse INTEGER,
- upsIta2com_471_Addr4BatBMSrelayinvalid INTEGER,
- upsIta2com_472_Addr4Batsafetyundervoltage INTEGER,
- upsIta2com_473_Addr4Batdischargehighcelltemp INTEGER,
- upsIta2com_474_Addr4Batdischargelowcelltemp INTEGER,
- upsIta2com_475_Addr4Batparallelchargehightemp INTEGER,
- upsIta2com_476_Addr4BatinternalCommabnormal INTEGER,
- upsIta2com_477_Addr4Batconditionfail INTEGER,
- upsIta2com_478_Addr4BatLowinsulationresistance INTEGER,
- upsIta2com_479_Addr4BatLargepressurediff INTEGER,
- upsIta2com_480_Addr4BatBatfailure INTEGER,
- upsIta2com_481_Addr4BatVoltageacquisitfailure INTEGER,
- upsIta2com_482_Addr4BatCurrentcolllectfailure INTEGER,
- upsIta2com_483_Addr4BatTempcolllectfailure INTEGER,
- upsIta2com_484_Addr4BatAddrSeterror INTEGER,
- upsIta2com_485_Addr4BatLargegrouppressurediff INTEGER,
- upsIta2com_486_Addr4BatMOSFETfailure INTEGER,
- upsIta2com_487_Addr4Battempabnormal INTEGER,
- upsIta2com_488_Addr4Batcablefault INTEGER,
- upsIta2com_489_Addr4BatShortcircuit INTEGER,
- upsIta2com_490_Addr4BatOtherfailures INTEGER,
- upsIta2com_491_Addr4BatCommcablefailure INTEGER,
- upsIta2com_492_Addr4BatMOSFETtempishigh INTEGER,
- upsIta2com_493_Addr4BatFuseblown INTEGER,
- upsIta2com_494_Addr4BatWaitingforcharging INTEGER,
- upsIta2com_495_Addr4BatBataging INTEGER,
- upsIta2com_496_Addr4Batboxconnectabnormal INTEGER,
- upsIta2com_497_Addr4batBatterySoftincompatible INTEGER,
- upsIta2com_498_Addr4batEOL INTEGER,
- upsIta2com_499_Addr4batSamplingfailure INTEGER,
- upsIta2com_500_Addr4batHardwareprotection INTEGER,
- upsIta2com_501_Addr4batBatterycapacitylow INTEGER,
- upsIta2com_502_Addr5Batalarmnumber Integer32,
- upsIta2com_503_Addr5Bathighvolt INTEGER,
- upsIta2com_504_Addr5Batlowvolt INTEGER,
- upsIta2com_505_Addr5Bathighcellvolt INTEGER,
- upsIta2com_506_Addr5Batlowcellvolt INTEGER,
- upsIta2com_507_Addr5Batchargehighcelltemp INTEGER,
- upsIta2com_508_Addr5Batchargelowcelltemp INTEGER,
- upsIta2com_509_Addr5Batchargeovercurrent INTEGER,
- upsIta2com_510_Addr5Batdischargeovercurrent INTEGER,
- upsIta2com_511_Addr5BatAddrconflict INTEGER,
- upsIta2com_512_Addr5Batportreverse INTEGER,
- upsIta2com_513_Addr5BatBMSrelayinvalid INTEGER,
- upsIta2com_514_Addr5Batsafetyundervoltage INTEGER,
- upsIta2com_515_Addr5Batdischargehighcelltemp INTEGER,
- upsIta2com_516_Addr5Batdischargelowcelltemp INTEGER,
- upsIta2com_517_Addr5Batparallelchargehightemp INTEGER,
- upsIta2com_518_Addr5BatinternalCommabnormal INTEGER,
- upsIta2com_519_Addr5Batconditionfail INTEGER,
- upsIta2com_520_Addr5BatLowinsulationresistance INTEGER,
- upsIta2com_521_Addr5BatLargepressurediff INTEGER,
- upsIta2com_522_Addr5BatBatfailure INTEGER,
- upsIta2com_523_Addr5BatVoltageacquisitfailure INTEGER,
- upsIta2com_524_Addr5BatCurrentcolllectfailure INTEGER,
- upsIta2com_525_Addr5BatTempcolllectfailure INTEGER,
- upsIta2com_526_Addr5BatAddrSeterror INTEGER,
- upsIta2com_527_Addr5BatLargegrouppressurediff INTEGER,
- upsIta2com_528_Addr5BatMOSFETfailure INTEGER,
- upsIta2com_529_Addr5Battempabnormal INTEGER,
- upsIta2com_530_Addr5Batcablefault INTEGER,
- upsIta2com_531_Addr5BatShortcircuit INTEGER,
- upsIta2com_532_Addr5BatOtherfailures INTEGER,
- upsIta2com_533_Addr5BatCommcablefailure INTEGER,
- upsIta2com_534_Addr5BatMOSFETtempishigh INTEGER,
- upsIta2com_535_Addr5BatFuseblown INTEGER,
- upsIta2com_536_Addr5BatWaitingforcharging INTEGER,
- upsIta2com_537_Addr5BatBataging INTEGER,
- upsIta2com_538_Addr5Batboxconnectabnormal INTEGER,
- upsIta2com_539_Addr5batBatterySoftincompatible INTEGER,
- upsIta2com_540_Addr5batEOL INTEGER,
- upsIta2com_541_Addr5batSamplingfailure INTEGER,
- upsIta2com_542_Addr5batHardwareprotection INTEGER,
- upsIta2com_543_Addr5batBatterycapacitylow INTEGER,
- upsIta2com_544_Addr6Batalarmnumber Integer32,
- upsIta2com_545_Addr6Bathighvolt INTEGER,
- upsIta2com_546_Addr6Batlowvolt INTEGER,
- upsIta2com_547_Addr6Bathighcellvolt INTEGER,
- upsIta2com_548_Addr6Batlowcellvolt INTEGER,
- upsIta2com_549_Addr6Batchargehighcelltemp INTEGER,
- upsIta2com_550_Addr6Batchargelowcelltemp INTEGER,
- upsIta2com_551_Addr6Batchargeovercurrent INTEGER,
- upsIta2com_552_Addr6Batdischargeovercurrent INTEGER,
- upsIta2com_553_Addr6BatAddrconflict INTEGER,
- upsIta2com_554_Addr6Batportreverse INTEGER,
- upsIta2com_555_Addr6BatBMSrelayinvalid INTEGER,
- upsIta2com_556_Addr6Batsafetyundervoltage INTEGER,
- upsIta2com_557_Addr6Batdischargehighcelltemp INTEGER,
- upsIta2com_558_Addr6Batdischargelowcelltemp INTEGER,
- upsIta2com_559_Addr6Batparallelchargehightemp INTEGER,
- upsIta2com_560_Addr6BatinternalCommabnormal INTEGER,
- upsIta2com_561_Addr6Batconditionfail INTEGER,
- upsIta2com_562_Addr6BatLowinsulationresistance INTEGER,
- upsIta2com_563_Addr6BatLargepressurediff INTEGER,
- upsIta2com_564_Addr6BatBatfailure INTEGER,
- upsIta2com_565_Addr6BatVoltageacquisitfailure INTEGER,
- upsIta2com_566_Addr6BatCurrentcolllectfailure INTEGER,
- upsIta2com_567_Addr6BatTempcolllectfailure INTEGER,
- upsIta2com_568_Addr6BatAddrSeterror INTEGER,
- upsIta2com_569_Addr6BatLargegrouppressurediff INTEGER,
- upsIta2com_570_Addr6BatMOSFETfailure INTEGER,
- upsIta2com_571_Addr6Battempabnormal INTEGER,
- upsIta2com_572_Addr6Batcablefault INTEGER,
- upsIta2com_573_Addr6BatShortcircuit INTEGER,
- upsIta2com_574_Addr6BatOtherfailures INTEGER,
- upsIta2com_575_Addr6BatCommcablefailure INTEGER,
- upsIta2com_576_Addr6BatMOSFETtempishigh INTEGER,
- upsIta2com_577_Addr6BatFuseblown INTEGER,
- upsIta2com_578_Addr6BatWaitingforcharging INTEGER,
- upsIta2com_579_Addr6BatBataging INTEGER,
- upsIta2com_580_Addr6Batboxconnectabnormal INTEGER,
- upsIta2com_581_Addr6batBatterySoftincompatible INTEGER,
- upsIta2com_582_Addr6batEOL INTEGER,
- upsIta2com_583_Addr6batSamplingfailure INTEGER,
- upsIta2com_584_Addr6batHardwareprotection INTEGER,
- upsIta2com_585_Addr6batBatterycapacitylow INTEGER,
- upsIta2com_586_Addr7Batalarmnumber Integer32,
- upsIta2com_587_Addr7Bathighvolt INTEGER,
- upsIta2com_588_Addr7Batlowvolt INTEGER,
- upsIta2com_589_Addr7Bathighcellvolt INTEGER,
- upsIta2com_590_Addr7Batlowcellvolt INTEGER,
- upsIta2com_591_Addr7Batchargehighcelltemp INTEGER,
- upsIta2com_592_Addr7Batchargelowcelltemp INTEGER,
- upsIta2com_593_Addr7Batchargeovercurrent INTEGER,
- upsIta2com_594_Addr7Batdischargeovercurrent INTEGER,
- upsIta2com_595_Addr7BatAddrconflict INTEGER,
- upsIta2com_596_Addr7Batportreverse INTEGER,
- upsIta2com_597_Addr7BatBMSrelayinvalid INTEGER,
- upsIta2com_598_Addr7Batsafetyundervoltage INTEGER,
- upsIta2com_599_Addr7Batdischargehighcelltemp INTEGER,
- upsIta2com_600_Addr7Batdischargelowcelltemp INTEGER,
- upsIta2com_601_Addr7Batparallelchargehightemp INTEGER,
- upsIta2com_602_Addr7BatinternalCommabnormal INTEGER,
- upsIta2com_603_Addr7Batconditionfail INTEGER,
- upsIta2com_604_Addr7BatLowinsulationresistance INTEGER,
- upsIta2com_605_Addr7BatLargepressurediff INTEGER,
- upsIta2com_606_Addr7BatBatfailure INTEGER,
- upsIta2com_607_Addr7BatVoltageacquisitfailure INTEGER,
- upsIta2com_608_Addr7BatCurrentcolllectfailure INTEGER,
- upsIta2com_609_Addr7BatTempcolllectfailure INTEGER,
- upsIta2com_610_Addr7BatAddrSeterror INTEGER,
- upsIta2com_611_Addr7BatLargegrouppressurediff INTEGER,
- upsIta2com_612_Addr7BatMOSFETfailure INTEGER,
- upsIta2com_613_Addr7Battempabnormal INTEGER,
- upsIta2com_614_Addr7Batcablefault INTEGER,
- upsIta2com_615_Addr7BatShortcircuit INTEGER,
- upsIta2com_616_Addr7BatOtherfailures INTEGER,
- upsIta2com_617_Addr7BatCommcablefailure INTEGER,
- upsIta2com_618_Addr7BatMOSFETtempishigh INTEGER,
- upsIta2com_619_Addr7BatFuseblown INTEGER,
- upsIta2com_620_Addr7BatWaitingforcharging INTEGER,
- upsIta2com_621_Addr7BatBataging INTEGER,
- upsIta2com_622_Addr7Batboxconnectabnormal INTEGER,
- upsIta2com_623_Addr7batBatterySoftincompatible INTEGER,
- upsIta2com_624_Addr7batEOL INTEGER,
- upsIta2com_625_Addr7batSamplingfailure INTEGER,
- upsIta2com_626_Addr7batHardwareprotection INTEGER,
- upsIta2com_627_Addr7batBatterycapacitylow INTEGER,
- upsIta2com_628_Addr8Batalarmnumber Integer32,
- upsIta2com_629_Addr8Bathighvolt INTEGER,
- upsIta2com_630_Addr8Batlowvolt INTEGER,
- upsIta2com_631_Addr8Bathighcellvolt INTEGER,
- upsIta2com_632_Addr8Batlowcellvolt INTEGER,
- upsIta2com_633_Addr8Batchargehighcelltemp INTEGER,
- upsIta2com_634_Addr8Batchargelowcelltemp INTEGER,
- upsIta2com_635_Addr8Batchargeovercurrent INTEGER,
- upsIta2com_636_Addr8Batdischargeovercurrent INTEGER,
- upsIta2com_637_Addr8BatAddrconflict INTEGER,
- upsIta2com_638_Addr8Batportreverse INTEGER,
- upsIta2com_639_Addr8BatBMSrelayinvalid INTEGER,
- upsIta2com_640_Addr8Batsafetyundervoltage INTEGER,
- upsIta2com_641_Addr8Batdischargehighcelltemp INTEGER,
- upsIta2com_642_Addr8Batdischargelowcelltemp INTEGER,
- upsIta2com_643_Addr8Batparallelchargehightemp INTEGER,
- upsIta2com_644_Addr8BatinternalCommabnormal INTEGER,
- upsIta2com_645_Addr8Batconditionfail INTEGER,
- upsIta2com_646_Addr8BatLowinsulationresistance INTEGER,
- upsIta2com_647_Addr8BatLargepressurediff INTEGER,
- upsIta2com_648_Addr8BatBatfailure INTEGER,
- upsIta2com_649_Addr8BatVoltageacquisitfailure INTEGER,
- upsIta2com_650_Addr8BatCurrentcolllectfailure INTEGER,
- upsIta2com_651_Addr8BatTempcolllectfailure INTEGER,
- upsIta2com_652_Addr8BatAddrSeterror INTEGER,
- upsIta2com_653_Addr8BatLargegrouppressurediff INTEGER,
- upsIta2com_654_Addr8BatMOSFETfailure INTEGER,
- upsIta2com_655_Addr8Battempabnormal INTEGER,
- upsIta2com_656_Addr8Batcablefault INTEGER,
- upsIta2com_657_Addr8BatShortcircuit INTEGER,
- upsIta2com_658_Addr8BatOtherfailures INTEGER,
- upsIta2com_659_Addr8BatCommcablefailure INTEGER,
- upsIta2com_660_Addr8BatMOSFETtempishigh INTEGER,
- upsIta2com_661_Addr8BatFuseblown INTEGER,
- upsIta2com_662_Addr8BatWaitingforcharging INTEGER,
- upsIta2com_663_Addr8BatBataging INTEGER,
- upsIta2com_664_Addr8Batboxconnectabnormal INTEGER,
- upsIta2com_665_Addr8batBatterySoftincompatible INTEGER,
- upsIta2com_666_Addr8batEOL INTEGER,
- upsIta2com_667_Addr8batSamplingfailure INTEGER,
- upsIta2com_668_Addr8batHardwareprotection INTEGER,
- upsIta2com_669_Addr8batBatterycapacitylow INTEGER,
- upsIta2com_670_Addr9Batalarmnumber Integer32,
- upsIta2com_671_Addr9Bathighvolt INTEGER,
- upsIta2com_672_Addr9Batlowvolt INTEGER,
- upsIta2com_673_Addr9Bathighcellvolt INTEGER,
- upsIta2com_674_Addr9Batlowcellvolt INTEGER,
- upsIta2com_675_Addr9Batchargehighcelltemp INTEGER,
- upsIta2com_676_Addr9Batchargelowcelltemp INTEGER,
- upsIta2com_677_Addr9Batchargeovercurrent INTEGER,
- upsIta2com_678_Addr9Batdischargeovercurrent INTEGER,
- upsIta2com_679_Addr9BatAddrconflict INTEGER,
- upsIta2com_680_Addr9Batportreverse INTEGER,
- upsIta2com_681_Addr9BatBMSrelayinvalid INTEGER,
- upsIta2com_682_Addr9Batsafetyundervoltage INTEGER,
- upsIta2com_683_Addr9Batdischargehighcelltemp INTEGER,
- upsIta2com_684_Addr9Batdischargelowcelltemp INTEGER,
- upsIta2com_685_Addr9Batparallelchargehightemp INTEGER,
- upsIta2com_686_Addr9BatinternalCommabnormal INTEGER,
- upsIta2com_687_Addr9Batconditionfail INTEGER,
- upsIta2com_688_Addr9BatLowinsulationresistance INTEGER,
- upsIta2com_689_Addr9BatLargepressurediff INTEGER,
- upsIta2com_690_Addr9BatBatfailure INTEGER,
- upsIta2com_691_Addr9BatVoltageacquisitfailure INTEGER,
- upsIta2com_692_Addr9BatCurrentcolllectfailure INTEGER,
- upsIta2com_693_Addr9BatTempcolllectfailure INTEGER,
- upsIta2com_694_Addr9BatAddrSeterror INTEGER,
- upsIta2com_695_Addr9BatLargegrouppressurediff INTEGER,
- upsIta2com_696_Addr9BatMOSFETfailure INTEGER,
- upsIta2com_697_Addr9Battempabnormal INTEGER,
- upsIta2com_698_Addr9Batcablefault INTEGER,
- upsIta2com_699_Addr9BatShortcircuit INTEGER,
- upsIta2com_700_Addr9BatOtherfailures INTEGER,
- upsIta2com_701_Addr9BatCommcablefailure INTEGER,
- upsIta2com_702_Addr9BatMOSFETtempishigh INTEGER,
- upsIta2com_703_Addr9BatFuseblown INTEGER,
- upsIta2com_704_Addr9BatWaitingforcharging INTEGER,
- upsIta2com_705_Addr9BatBataging INTEGER,
- upsIta2com_706_Addr9Batboxconnectabnormal INTEGER,
- upsIta2com_707_Addr9batBatterySoftincompatible INTEGER,
- upsIta2com_708_Addr9batEOL INTEGER,
- upsIta2com_709_Addr9batSamplingfailure INTEGER,
- upsIta2com_710_Addr9batHardwareprotection INTEGER,
- upsIta2com_711_Addr9batBatterycapacitylow INTEGER,
- upsIta2com_712_Addr10Batalarmnumber Integer32,
- upsIta2com_713_Addr10Bathighvolt INTEGER,
- upsIta2com_714_Addr10Batlowvolt INTEGER,
- upsIta2com_715_Addr10Bathighcellvolt INTEGER,
- upsIta2com_716_Addr10Batlowcellvolt INTEGER,
- upsIta2com_717_Addr10Batchargehighcelltemp INTEGER,
- upsIta2com_718_Addr10Batchargelowcelltemp INTEGER,
- upsIta2com_719_Addr10Batchargeovercurrent INTEGER,
- upsIta2com_720_Addr10Batdischargeovercurrent INTEGER,
- upsIta2com_721_Addr10BatAddrconflict INTEGER,
- upsIta2com_722_Addr10Batportreverse INTEGER,
- upsIta2com_723_Addr10BatBMSrelayinvalid INTEGER,
- upsIta2com_724_Addr10Batsafetyundervoltage INTEGER,
- upsIta2com_725_Addr10Batdischargehighcelltemp INTEGER,
- upsIta2com_726_Addr10Batdischargelowcelltemp INTEGER,
- upsIta2com_727_Addr10Batparallelchargehightemp INTEGER,
- upsIta2com_728_Addr10BatinternalCommabnormal INTEGER,
- upsIta2com_729_Addr10Batconditionfail INTEGER,
- upsIta2com_730_Addr10BatLowinsulationresistanc INTEGER,
- upsIta2com_731_Addr10BatLargepressurediff INTEGER,
- upsIta2com_732_Addr10BatBatfailure INTEGER,
- upsIta2com_733_Addr10BatVoltageacquisitfailure INTEGER,
- upsIta2com_734_Addr10BatCurrentcolllectfailure INTEGER,
- upsIta2com_735_Addr10BatTempcolllectfailure INTEGER,
- upsIta2com_736_Addr10BatAddrSeterror INTEGER,
- upsIta2com_737_Addr10BatLargegrouppressurediff INTEGER,
- upsIta2com_738_Addr10BatMOSFETfailure INTEGER,
- upsIta2com_739_Addr10Battempabnormal INTEGER,
- upsIta2com_740_Addr10Batcablefault INTEGER,
- upsIta2com_741_Addr10BatShortcircuit INTEGER,
- upsIta2com_742_Addr10BatOtherfailures INTEGER,
- upsIta2com_743_Addr10BatCommcablefailure INTEGER,
- upsIta2com_744_Addr10BatMOSFETtempishigh INTEGER,
- upsIta2com_745_Addr10BatFuseblown INTEGER,
- upsIta2com_746_Addr10BatWaitingforcharging INTEGER,
- upsIta2com_747_Addr10BatBataging INTEGER,
- upsIta2com_748_Addr10Batboxconnectabnormal INTEGER,
- upsIta2com_749_Addr10batBatterySoftincompatibl INTEGER,
- upsIta2com_750_Addr10batEOL INTEGER,
- upsIta2com_751_Addr10batSamplingfailure INTEGER,
- upsIta2com_752_Addr10batHardwareprotection INTEGER,
- upsIta2com_753_Addr10batBatterycapacitylow INTEGER,
- upsIta2com_754_Addr11Batalarmnumber Integer32,
- upsIta2com_755_Addr11Bathighvolt INTEGER,
- upsIta2com_756_Addr11Batlowvolt INTEGER,
- upsIta2com_757_Addr11Bathighcellvolt INTEGER,
- upsIta2com_758_Addr11Batlowcellvolt INTEGER,
- upsIta2com_759_Addr11Batchargehighcelltemp INTEGER,
- upsIta2com_760_Addr11Batchargelowcelltemp INTEGER,
- upsIta2com_761_Addr11Batchargeovercurrent INTEGER,
- upsIta2com_762_Addr11Batdischargeovercurrent INTEGER,
- upsIta2com_763_Addr11BatAddrconflict INTEGER,
- upsIta2com_764_Addr11Batportreverse INTEGER,
- upsIta2com_765_Addr11BatBMSrelayinvalid INTEGER,
- upsIta2com_766_Addr11Batsafetyundervoltage INTEGER,
- upsIta2com_767_Addr11Batdischargehighcelltemp INTEGER,
- upsIta2com_768_Addr11Batdischargelowcelltemp INTEGER,
- upsIta2com_769_Addr11Batparallelchargehightemp INTEGER,
- upsIta2com_770_Addr11BatinternalCommabnormal INTEGER,
- upsIta2com_771_Addr11Batconditionfail INTEGER,
- upsIta2com_772_Addr11BatLowinsulationresistanc INTEGER,
- upsIta2com_773_Addr11BatLargepressurediff INTEGER,
- upsIta2com_774_Addr11BatBatfailure INTEGER,
- upsIta2com_775_Addr11BatVoltageacquisitfailure INTEGER,
- upsIta2com_776_Addr11BatCurrentcolllectfailure INTEGER,
- upsIta2com_777_Addr11BatTempcolllectfailure INTEGER,
- upsIta2com_778_Addr11BatAddrSeterror INTEGER,
- upsIta2com_779_Addr11BatLargegrouppressurediff INTEGER,
- upsIta2com_780_Addr11BatMOSFETfailure INTEGER,
- upsIta2com_781_Addr11Battempabnormal INTEGER,
- upsIta2com_782_Addr11Batcablefault INTEGER,
- upsIta2com_783_Addr11BatShortcircuit INTEGER,
- upsIta2com_784_Addr11BatOtherfailures INTEGER,
- upsIta2com_785_Addr11BatCommcablefailure INTEGER,
- upsIta2com_786_Addr11BatMOSFETtempishigh INTEGER,
- upsIta2com_787_Addr11BatFuseblown INTEGER,
- upsIta2com_788_Addr11BatWaitingforcharging INTEGER,
- upsIta2com_789_Addr11BatBataging INTEGER,
- upsIta2com_790_Addr11Batboxconnectabnormal INTEGER,
- upsIta2com_791_Addr11batBatterySoftincompatibl INTEGER,
- upsIta2com_792_Addr11batEOL INTEGER,
- upsIta2com_793_Addr11batSamplingfailure INTEGER,
- upsIta2com_794_Addr11batHardwareprotection INTEGER,
- upsIta2com_795_Addr11batBatterycapacitylow INTEGER,
- upsIta2com_796_Addr12Batalarmnumber Integer32,
- upsIta2com_797_Addr12Bathighvolt INTEGER,
- upsIta2com_798_Addr12Batlowvolt INTEGER,
- upsIta2com_799_Addr12Bathighcellvolt INTEGER,
- upsIta2com_800_Addr12Batlowcellvolt INTEGER,
- upsIta2com_801_Addr12Batchargehighcelltemp INTEGER,
- upsIta2com_802_Addr12Batchargelowcelltemp INTEGER,
- upsIta2com_803_Addr12Batchargeovercurrent INTEGER,
- upsIta2com_804_Addr12Batdischargeovercurrent INTEGER,
- upsIta2com_805_Addr12BatAddrconflict INTEGER,
- upsIta2com_806_Addr12Batportreverse INTEGER,
- upsIta2com_807_Addr12BatBMSrelayinvalid INTEGER,
- upsIta2com_808_Addr12Batsafetyundervoltage INTEGER,
- upsIta2com_809_Addr12Batdischargehighcelltemp INTEGER,
- upsIta2com_810_Addr12Batdischargelowcelltemp INTEGER,
- upsIta2com_811_Addr12Batparallelchargehightemp INTEGER,
- upsIta2com_812_Addr12BatinternalCommabnormal INTEGER,
- upsIta2com_813_Addr12Batconditionfail INTEGER,
- upsIta2com_814_Addr12BatLowinsulationresistanc INTEGER,
- upsIta2com_815_Addr12BatLargepressurediff INTEGER,
- upsIta2com_816_Addr12BatBatfailure INTEGER,
- upsIta2com_817_Addr12BatVoltageacquisitfailure INTEGER,
- upsIta2com_818_Addr12BatCurrentcolllectfailure INTEGER,
- upsIta2com_819_Addr12BatTempcolllectfailure INTEGER,
- upsIta2com_820_Addr12BatAddrSeterror INTEGER,
- upsIta2com_821_Addr12BatLargegrouppressurediff INTEGER,
- upsIta2com_822_Addr12BatMOSFETfailure INTEGER,
- upsIta2com_823_Addr12Battempabnormal INTEGER,
- upsIta2com_824_Addr12Batcablefault INTEGER,
- upsIta2com_825_Addr12BatShortcircuit INTEGER,
- upsIta2com_826_Addr12BatOtherfailures INTEGER,
- upsIta2com_827_Addr12BatCommcablefailure INTEGER,
- upsIta2com_828_Addr12BatMOSFETtempishigh INTEGER,
- upsIta2com_829_Addr12BatFuseblown INTEGER,
- upsIta2com_830_Addr12BatWaitingforcharging INTEGER,
- upsIta2com_831_Addr12BatBataging INTEGER,
- upsIta2com_832_Addr12Batboxconnectabnormal INTEGER,
- upsIta2com_833_Addr12batBatterySoftincompatibl INTEGER,
- upsIta2com_834_Addr12batEOL INTEGER,
- upsIta2com_835_Addr12batSamplingfailure INTEGER,
- upsIta2com_836_Addr12batHardwareprotection INTEGER,
- upsIta2com_837_Addr12batBatterycapacitylow INTEGER,
- upsIta2com_838_Addr13Batalarmnumber Integer32,
- upsIta2com_839_Addr13Bathighvolt INTEGER,
- upsIta2com_840_Addr13Batlowvolt INTEGER,
- upsIta2com_841_Addr13Bathighcellvolt INTEGER,
- upsIta2com_842_Addr13Batlowcellvolt INTEGER,
- upsIta2com_843_Addr13Batchargehighcelltemp INTEGER,
- upsIta2com_844_Addr13Batchargelowcelltemp INTEGER,
- upsIta2com_845_Addr13Batchargeovercurrent INTEGER,
- upsIta2com_846_Addr13Batdischargeovercurrent INTEGER,
- upsIta2com_847_Addr13BatAddrconflict INTEGER,
- upsIta2com_848_Addr13Batportreverse INTEGER,
- upsIta2com_849_Addr13BatBMSrelayinvalid INTEGER,
- upsIta2com_850_Addr13Batsafetyundervoltage INTEGER,
- upsIta2com_851_Addr13Batdischargehighcelltemp INTEGER,
- upsIta2com_852_Addr13Batdischargelowcelltemp INTEGER,
- upsIta2com_853_Addr13Batparallelchargehightemp INTEGER,
- upsIta2com_854_Addr13BatinternalCommabnormal INTEGER,
- upsIta2com_855_Addr13Batconditionfail INTEGER,
- upsIta2com_856_Addr13BatLowinsulationresistanc INTEGER,
- upsIta2com_857_Addr13BatLargepressurediff INTEGER,
- upsIta2com_858_Addr13BatBatfailure INTEGER,
- upsIta2com_859_Addr13BatVoltageacquisitfailure INTEGER,
- upsIta2com_860_Addr13BatCurrentcolllectfailure INTEGER,
- upsIta2com_861_Addr13BatTempcolllectfailure INTEGER,
- upsIta2com_862_Addr13BatAddrSeterror INTEGER,
- upsIta2com_863_Addr13BatLargegrouppressurediff INTEGER,
- upsIta2com_864_Addr13BatMOSFETfailure INTEGER,
- upsIta2com_865_Addr13Battempabnormal INTEGER,
- upsIta2com_866_Addr13Batcablefault INTEGER,
- upsIta2com_867_Addr13BatShortcircuit INTEGER,
- upsIta2com_868_Addr13BatOtherfailures INTEGER,
- upsIta2com_869_Addr13BatCommcablefailure INTEGER,
- upsIta2com_870_Addr13BatMOSFETtempishigh INTEGER,
- upsIta2com_871_Addr13BatFuseblown INTEGER,
- upsIta2com_872_Addr13BatWaitingforcharging INTEGER,
- upsIta2com_873_Addr13BatBataging INTEGER,
- upsIta2com_874_Addr13Batboxconnectabnormal INTEGER,
- upsIta2com_875_Addr13batBatterySoftincompatibl INTEGER,
- upsIta2com_876_Addr13batEOL INTEGER,
- upsIta2com_877_Addr13batSamplingfailure INTEGER,
- upsIta2com_878_Addr13batHardwareprotection INTEGER,
- upsIta2com_879_Addr13batBatterycapacitylow INTEGER,
- upsIta2com_880_Addr14Batalarmnumber Integer32,
- upsIta2com_881_Addr14Bathighvolt INTEGER,
- upsIta2com_882_Addr14Batlowvolt INTEGER,
- upsIta2com_883_Addr14Bathighcellvolt INTEGER,
- upsIta2com_884_Addr14Batlowcellvolt INTEGER,
- upsIta2com_885_Addr14Batchargehighcelltemp INTEGER,
- upsIta2com_886_Addr14Batchargelowcelltemp INTEGER,
- upsIta2com_887_Addr14Batchargeovercurrent INTEGER,
- upsIta2com_888_Addr14Batdischargeovercurrent INTEGER,
- upsIta2com_889_Addr14BatAddrconflict INTEGER,
- upsIta2com_890_Addr14Batportreverse INTEGER,
- upsIta2com_891_Addr14BatBMSrelayinvalid INTEGER,
- upsIta2com_892_Addr14Batsafetyundervoltage INTEGER,
- upsIta2com_893_Addr14Batdischargehighcelltemp INTEGER,
- upsIta2com_894_Addr14Batdischargelowcelltemp INTEGER,
- upsIta2com_895_Addr14Batparallelchargehightemp INTEGER,
- upsIta2com_896_Addr14BatinternalCommabnormal INTEGER,
- upsIta2com_897_Addr14Batconditionfail INTEGER,
- upsIta2com_898_Addr14BatLowinsulationresistanc INTEGER,
- upsIta2com_899_Addr14BatLargepressurediff INTEGER,
- upsIta2com_900_Addr14BatBatfailure INTEGER,
- upsIta2com_901_Addr14BatVoltageacquisitfailure INTEGER,
- upsIta2com_902_Addr14BatCurrentcolllectfailure INTEGER,
- upsIta2com_903_Addr14BatTempcolllectfailure INTEGER,
- upsIta2com_904_Addr14BatAddrSeterror INTEGER,
- upsIta2com_905_Addr14BatLargegrouppressurediff INTEGER,
- upsIta2com_906_Addr14BatMOSFETfailure INTEGER,
- upsIta2com_907_Addr14Battempabnormal INTEGER,
- upsIta2com_908_Addr14Batcablefault INTEGER,
- upsIta2com_909_Addr14BatShortcircuit INTEGER,
- upsIta2com_910_Addr14BatOtherfailures INTEGER,
- upsIta2com_911_Addr14BatCommcablefailure INTEGER,
- upsIta2com_912_Addr14BatMOSFETtempishigh INTEGER,
- upsIta2com_913_Addr14BatFuseblown INTEGER,
- upsIta2com_914_Addr14BatWaitingforcharging INTEGER,
- upsIta2com_915_Addr14BatBataging INTEGER,
- upsIta2com_916_Addr14Batboxconnectabnormal INTEGER,
- upsIta2com_917_Addr14batBatterySoftincompatibl INTEGER,
- upsIta2com_918_Addr14batEOL INTEGER,
- upsIta2com_919_Addr14batSamplingfailure INTEGER,
- upsIta2com_920_Addr14batHardwareprotection INTEGER,
- upsIta2com_921_Addr14batBatterycapacitylow INTEGER,
- upsIta2com_922_Addr15Batalarmnumber Integer32,
- upsIta2com_923_Addr15Bathighvolt INTEGER,
- upsIta2com_924_Addr15Batlowvolt INTEGER,
- upsIta2com_925_Addr15Bathighcellvolt INTEGER,
- upsIta2com_926_Addr15Batlowcellvolt INTEGER,
- upsIta2com_927_Addr15Batchargehighcelltemp INTEGER,
- upsIta2com_928_Addr15Batchargelowcelltemp INTEGER,
- upsIta2com_929_Addr15Batchargeovercurrent INTEGER,
- upsIta2com_930_Addr15Batdischargeovercurrent INTEGER,
- upsIta2com_931_Addr15BatAddrconflict INTEGER,
- upsIta2com_932_Addr15Batportreverse INTEGER,
- upsIta2com_933_Addr15BatBMSrelayinvalid INTEGER,
- upsIta2com_934_Addr15Batsafetyundervoltage INTEGER,
- upsIta2com_935_Addr15Batdischargehighcelltemp INTEGER,
- upsIta2com_936_Addr15Batdischargelowcelltemp INTEGER,
- upsIta2com_937_Addr15Batparallelchargehightemp INTEGER,
- upsIta2com_938_Addr15BatinternalCommabnormal INTEGER,
- upsIta2com_939_Addr15Batconditionfail INTEGER,
- upsIta2com_940_Addr15BatLowinsulationresistanc INTEGER,
- upsIta2com_941_Addr15BatLargepressurediff INTEGER,
- upsIta2com_942_Addr15BatBatfailure INTEGER,
- upsIta2com_943_Addr15BatVoltageacquisitfailure INTEGER,
- upsIta2com_944_Addr15BatCurrentcolllectfailure INTEGER,
- upsIta2com_945_Addr15BatTempcolllectfailure INTEGER,
- upsIta2com_946_Addr15BatAddrSeterror INTEGER,
- upsIta2com_947_Addr15BatLargegrouppressurediff INTEGER,
- upsIta2com_948_Addr15BatMOSFETfailure INTEGER,
- upsIta2com_949_Addr15Battempabnormal INTEGER,
- upsIta2com_950_Addr15Batcablefault INTEGER,
- upsIta2com_951_Addr15BatShortcircuit INTEGER,
- upsIta2com_952_Addr15BatOtherfailures INTEGER,
- upsIta2com_953_Addr15BatCommcablefailure INTEGER,
- upsIta2com_954_Addr15BatMOSFETtempishigh INTEGER,
- upsIta2com_955_Addr15BatFuseblown INTEGER,
- upsIta2com_956_Addr15BatWaitingforcharging INTEGER,
- upsIta2com_957_Addr15BatBataging INTEGER,
- upsIta2com_958_Addr15Batboxconnectabnormal INTEGER,
- upsIta2com_959_Addr15batBatterySoftincompatibl INTEGER,
- upsIta2com_960_Addr15batEOL INTEGER,
- upsIta2com_961_Addr15batSamplingfailure INTEGER,
- upsIta2com_962_Addr15batHardwareprotection INTEGER,
- upsIta2com_963_Addr15batBatterycapacitylow INTEGER,
- upsIta2com_964_Addr16Batalarmnumber Integer32,
- upsIta2com_965_Addr16Bathighvolt INTEGER,
- upsIta2com_966_Addr16Batlowvolt INTEGER,
- upsIta2com_967_Addr16Bathighcellvolt INTEGER,
- upsIta2com_968_Addr16Batlowcellvolt INTEGER,
- upsIta2com_969_Addr16Batchargehighcelltemp INTEGER,
- upsIta2com_970_Addr16Batchargelowcelltemp INTEGER,
- upsIta2com_971_Addr16Batchargeovercurrent INTEGER,
- upsIta2com_972_Addr16Batdischargeovercurrent INTEGER,
- upsIta2com_973_Addr16BatAddrconflict INTEGER,
- upsIta2com_974_Addr16Batportreverse INTEGER,
- upsIta2com_975_Addr16BatBMSrelayinvalid INTEGER,
- upsIta2com_976_Addr16Batsafetyundervoltage INTEGER,
- upsIta2com_977_Addr16Batdischargehighcelltemp INTEGER,
- upsIta2com_978_Addr16Batdischargelowcelltemp INTEGER,
- upsIta2com_979_Addr16Batparallelchargehightemp INTEGER,
- upsIta2com_980_Addr16BatinternalCommabnormal INTEGER,
- upsIta2com_981_Addr16Batconditionfail INTEGER,
- upsIta2com_982_Addr16BatLowinsulationresistanc INTEGER,
- upsIta2com_983_Addr16BatLargepressurediff INTEGER,
- upsIta2com_984_Addr16BatBatfailure INTEGER,
- upsIta2com_985_Addr16BatVoltageacquisitfailure INTEGER,
- upsIta2com_986_Addr16BatCurrentcolllectfailure INTEGER,
- upsIta2com_987_Addr16BatTempcolllectfailure INTEGER,
- upsIta2com_988_Addr16BatAddrSeterror INTEGER,
- upsIta2com_989_Addr16BatLargegrouppressurediff INTEGER,
- upsIta2com_990_Addr16BatMOSFETfailure INTEGER,
- upsIta2com_991_Addr16Battempabnormal INTEGER,
- upsIta2com_992_Addr16Batcablefault INTEGER,
- upsIta2com_993_Addr16BatShortcircuit INTEGER,
- upsIta2com_994_Addr16BatOtherfailures INTEGER,
- upsIta2com_995_Addr16BatCommcablefailure INTEGER,
- upsIta2com_996_Addr16BatMOSFETtempishigh INTEGER,
- upsIta2com_997_Addr16BatFuseblown INTEGER,
- upsIta2com_998_Addr16BatWaitingforcharging INTEGER,
- upsIta2com_999_Addr16BatBataging INTEGER,
- upsIta2com_1000_Addr16Batboxconnectabnormal INTEGER,
- upsIta2com_1001_Addr16batBatterySoftincompatibl INTEGER,
- upsIta2com_1002_Addr16batEOL INTEGER,
- upsIta2com_1003_Addr16batSamplingfailure INTEGER,
- upsIta2com_1004_Addr16batHardwareprotection INTEGER,
- upsIta2com_1005_Addr16batBatterycapacitylow INTEGER,
- upsIta2com_1006_Addr1Batcuralarmnumber Integer32,
- upsIta2com_1007_Addr2Batcuralarmnumber Integer32,
- upsIta2com_1008_Addr3Batcuralarmnumber Integer32,
- upsIta2com_1009_Addr4Batcuralarmnumber Integer32,
- upsIta2com_1010_Addr5Batcuralarmnumber Integer32,
- upsIta2com_1011_Addr6Batcuralarmnumber Integer32,
- upsIta2com_1012_Addr7Batcuralarmnumber Integer32,
- upsIta2com_1013_Addr8Batcuralarmnumber Integer32,
- upsIta2com_1014_Addr9Batcuralarmnumber Integer32,
- upsIta2com_1015_Addr10Batcuralarmnumber Integer32,
- upsIta2com_1016_Addr11Batcuralarmnumber Integer32,
- upsIta2com_1017_Addr12Batcuralarmnumber Integer32,
- upsIta2com_1018_Addr13Batcuralarmnumber Integer32,
- upsIta2com_1019_Addr14Batcuralarmnumber Integer32,
- upsIta2com_1020_Addr15Batcuralarmnumber Integer32,
- upsIta2com_1021_Addr16Batcuralarmnumber Integer32,
- upsIta2com_1022_StanderBatteryStatus INTEGER,
- upsIta2com_1023_Commtatus INTEGER,
- upsIta2com_1024_RemoteBatSelftest INTEGER,
- upsIta2com_1025_BatSelfTestCommand INTEGER,
- upsIta2com_1026_TurnOffUpsOutput INTEGER,
- upsIta2com_1027_TurnOnUpsInstantly INTEGER,
- upsIta2com_1028_TurnOffUpsInstantly INTEGER,
- upsIta2com_1029_SetTime INTEGER,
- upsIta2com_1030_OpenInverterWithDelay INTEGER,
- upsIta2com_1031_CloseOutputWithDelay INTEGER,
- upsIta2com_1032_DelayedShutdownCancellation INTEGER,
- upsIta2com_1033_ForcedtowakeuplithiumBat INTEGER,
- upsIta2com_1034_DelayTimeOfSelfStart Integer32,
- upsIta2com_1035_DelayTimeOfRemoteShutDown Integer32,
- upsIta2com_1036_IntervalOfBatSelfTest INTEGER,
- upsIta2com_1037_UpsWorkingMode INTEGER,
- upsIta2com_1038_SelfStartSet INTEGER,
- upsIta2com_1039_SetsRedundance INTEGER,
- upsIta2com_1040_RemoteOpenDelayTime Integer32,
- upsIta2com_1041_LogNumberSet Integer32 }
- upsIta2comIndex OBJECT-TYPE
- SYNTAX Integer32(1..1041)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com System Entry Index."
- ::= { upsIta2comEntry 1 }
- upsIta2com_2_PhaseAInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1_PhaseAInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 2 }
- upsIta2com_3_PhaseBInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_2_PhaseBInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 3 }
- upsIta2com_4_PhaseCInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_3_PhaseCInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 4 }
- upsIta2com_5_PhaseAOutputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_4_PhaseAOutputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 5 }
- upsIta2com_6_PhaseBOutputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_5_PhaseBOutputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 6 }
- upsIta2com_7_PhaseCOutputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_6_PhaseCOutputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 7 }
- upsIta2com_8_PhaseAOutputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_7_PhaseAOutputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 8 }
- upsIta2com_9_PhaseBOutputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_8_PhaseBOutputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 9 }
- upsIta2com_10_PhaseCOutputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_9_PhaseCOutputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 10 }
- upsIta2com_11_OutputFrequency OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_10_OutputFrequency stored as 0.1Hz."
- ::= { upsIta2comEntry 11 }
- upsIta2com_12_InputPhaseNumber OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(0),
- simplex(1),
- duplex(2),
- threephase(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_11_InputPhaseNumber status."
- ::= { upsIta2comEntry 12 }
- upsIta2com_13_LineAbInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_12_LineAbInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 13 }
- upsIta2com_14_LineBcInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_13_LineBcInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 14 }
- upsIta2com_15_LineCaInputVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_14_LineCaInputVoltage stored as 0.1V."
- ::= { upsIta2comEntry 15 }
- upsIta2com_16_PhaseAInputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_15_PhaseAInputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 16 }
- upsIta2com_17_PhaseBInputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_16_PhaseBInputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 17 }
- upsIta2com_18_PhaseCInputCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_17_PhaseCInputCurrent stored as 0.1A."
- ::= { upsIta2comEntry 18 }
- upsIta2com_19_SystemInputFrequency OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_18_SystemInputFrequency stored as 0.1Hz."
- ::= { upsIta2comEntry 19 }
- upsIta2com_20_PhaseAInputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_19_PhaseAInputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 20 }
- upsIta2com_21_PhaseBInputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_20_PhaseBInputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 21 }
- upsIta2com_22_PhaseCInputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_21_PhaseCInputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 22 }
- upsIta2com_23_BypassAVoltageA OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_22_BypassAVoltageA stored as 0.1V."
- ::= { upsIta2comEntry 23 }
- upsIta2com_24_BypassBVoltageB OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_23_BypassBVoltageB stored as 0.1V."
- ::= { upsIta2comEntry 24 }
- upsIta2com_25_BypassCVoltageC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_24_BypassCVoltageC stored as 0.1V."
- ::= { upsIta2comEntry 25 }
- upsIta2com_26_BypassLineAbVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_25_BypassLineAbVoltage stored as 0.1V."
- ::= { upsIta2comEntry 26 }
- upsIta2com_27_BypassLineBcVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_26_BypassLineBcVoltage stored as 0.1V."
- ::= { upsIta2comEntry 27 }
- upsIta2com_28_BypassLineCaVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_27_BypassLineCaVoltage stored as 0.1V."
- ::= { upsIta2comEntry 28 }
- upsIta2com_29_BypassFrequency OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_28_BypassFrequency stored as 0.1Hz."
- ::= { upsIta2comEntry 29 }
- upsIta2com_30_BusvoltageP OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_29_BusvoltageP stored as 0.1V."
- ::= { upsIta2comEntry 30 }
- upsIta2com_31_BusvoltageN OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_30_BusvoltageN stored as 0.1V."
- ::= { upsIta2comEntry 31 }
- upsIta2com_32_OutputPhaseNumber OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(0),
- simplex(1),
- duplex(2),
- threephase(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_31_OutputPhaseNumber status."
- ::= { upsIta2comEntry 32 }
- upsIta2com_33_PhaseAOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_32_PhaseAOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 33 }
- upsIta2com_34_PhaseBOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_33_PhaseBOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 34 }
- upsIta2com_35_PhaseCOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_34_PhaseCOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 35 }
- upsIta2com_36_LPhaseAOutputPeakRatio OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_35_LPhaseAOutputPeakRatio stored as 0.1."
- ::= { upsIta2comEntry 36 }
- upsIta2com_37_LPhaseBOutputPeakRatio OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_36_LPhaseBOutputPeakRatio stored as 0.1."
- ::= { upsIta2comEntry 37 }
- upsIta2com_38_LPhaseCOutputPeakRatio OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_37_LPhaseCOutputPeakRatio stored as 0.1."
- ::= { upsIta2comEntry 38 }
- upsIta2com_39_LPhaseAOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_38_LPhaseAOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 39 }
- upsIta2com_40_LPhaseBOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_39_LPhaseBOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 40 }
- upsIta2com_41_LPhaseCOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_40_LPhaseCOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 41 }
- upsIta2com_42_LPhaseAOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_41_LPhaseAOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 42 }
- upsIta2com_43_LPhaseBOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_42_LPhaseBOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 43 }
- upsIta2com_44_LPhaseCOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_43_LPhaseCOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 44 }
- upsIta2com_45_LPhaseAOutputLoadPercent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_44_LPhaseAOutputLoadPercent stored as 0.1%."
- ::= { upsIta2comEntry 45 }
- upsIta2com_46_LPhaseBOutputLoadPercent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_45_LPhaseBOutputLoadPercent stored as 0.1%."
- ::= { upsIta2comEntry 46 }
- upsIta2com_47_LPhaseCOutputLoadPercent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_46_LPhaseCOutputLoadPercent stored as 0.1%."
- ::= { upsIta2comEntry 47 }
- upsIta2com_48_SPhaseAOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_47_SPhaseAOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 48 }
- upsIta2com_49_SPhaseBOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_48_SPhaseBOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 49 }
- upsIta2com_50_SPhaseCOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_49_SPhaseCOutputPowerFactor stored as 0.1."
- ::= { upsIta2comEntry 50 }
- upsIta2com_51_SPhaseAOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_50_SPhaseAOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 51 }
- upsIta2com_52_SPhaseBOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_51_SPhaseBOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 52 }
- upsIta2com_53_SPhaseCOutputActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_52_SPhaseCOutputActivePower stored as 0.1kW."
- ::= { upsIta2comEntry 53 }
- upsIta2com_54_SPhaseAOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_53_SPhaseAOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 54 }
- upsIta2com_55_SPhaseBOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_54_SPhaseBOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 55 }
- upsIta2com_56_SPhaseCOutputApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_55_SPhaseCOutputApparentPower stored as 0.1kVA."
- ::= { upsIta2comEntry 56 }
- upsIta2com_57_ParallelMachineNumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_56_ParallelMachineNumber stored as 0.1."
- ::= { upsIta2comEntry 57 }
- upsIta2com_58_UpsRunningTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_57_UpsRunningTime stored as 0.1Day."
- ::= { upsIta2comEntry 58 }
- upsIta2com_59_BatVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_58_BatVoltage stored as 0.1V."
- ::= { upsIta2comEntry 59 }
- upsIta2com_60_BatChargingCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_59_BatChargingCurrent stored as 0.1A."
- ::= { upsIta2comEntry 60 }
- upsIta2com_61_BatDischargeCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_60_BatDischargeCurrent stored as 0.1A."
- ::= { upsIta2comEntry 61 }
- upsIta2com_62_NegativeBatVoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_61_NegativeBatVoltage stored as 0.1V."
- ::= { upsIta2comEntry 62 }
- upsIta2com_63_NegativeBatChargeCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_62_NegativeBatChargeCurrent stored as 0.1A."
- ::= { upsIta2comEntry 63 }
- upsIta2com_64_NegativeBatDischargeCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_63_NegativeBatDischargeCurrent stored as 0.1A."
- ::= { upsIta2comEntry 64 }
- upsIta2com_65_BatBackupTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_64_BatBackupTime stored as 0.1min."
- ::= { upsIta2comEntry 65 }
- upsIta2com_66_Battemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_65_Battemp stored as 0.1℃."
- ::= { upsIta2comEntry 66 }
- upsIta2com_67_Ambienttemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_66_Ambienttemp stored as 0.1℃."
- ::= { upsIta2comEntry 67 }
- upsIta2com_68_BatCurrentCapacity OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_67_BatCurrentCapacity stored as 0.1%."
- ::= { upsIta2comEntry 68 }
- upsIta2com_69_BatDischargeTimes OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_68_BatDischargeTimes stored as 0.1."
- ::= { upsIta2comEntry 69 }
- upsIta2com_70_BatHelth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_69_BatHelth stored as 0.1%."
- ::= { upsIta2comEntry 70 }
- upsIta2com_71_InputPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_70_InputPower stored as 0.1kWh."
- ::= { upsIta2comEntry 71 }
- upsIta2com_72_OutputPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_71_OutputPower stored as 0.1kWh."
- ::= { upsIta2comEntry 72 }
- upsIta2com_73_BatRunningTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_72_BatRunningTime stored as 0.01Hour."
- ::= { upsIta2comEntry 73 }
- upsIta2com_74_BatDischargingTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_73_BatDischargingTime stored as 0.01Hour."
- ::= { upsIta2comEntry 74 }
- upsIta2com_75_PowerSupply OBJECT-TYPE
- SYNTAX INTEGER {
- upsshutdown(0),
- utilityonline(1),
- onbat(2),
- onbypass(3),
- upsonunionmode(4) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_74_PowerSupply status."
- ::= { upsIta2comEntry 75 }
- upsIta2com_76_InputPowerStatus OBJECT-TYPE
- SYNTAX INTEGER {
- utilityonline(0),
- onbat(1),
- upsonunionmode(2),
- upsshutdown(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_75_InputPowerStatus status."
- ::= { upsIta2comEntry 76 }
- upsIta2com_77_BatStatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- floatcharging(1),
- equalizationcharging(2),
- discharging(3),
- selftesting(4),
- nobat(5),
- full(6),
- precharge(7),
- fastcharging(8) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_76_BatStatus status."
- ::= { upsIta2comEntry 77 }
- upsIta2com_78_BatNegativeGroupStatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- floatcharging(1),
- equalizationcharging(2),
- discharging(3),
- selftesting(4),
- nobat(5),
- full(6),
- precharge(7),
- fastcharging(8) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_77_BatNegativeGroupStatus status."
- ::= { upsIta2comEntry 78 }
- upsIta2com_79_ChargerStatus OBJECT-TYPE
- SYNTAX INTEGER {
- chargeron(0),
- chargeroff(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_78_ChargerStatus status."
- ::= { upsIta2comEntry 79 }
- upsIta2com_80_ParallelSystemPowerState OBJECT-TYPE
- SYNTAX INTEGER {
- maininverterpowersupply(0),
- onbat(1),
- onbypass(2),
- upsshutdown(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_79_ParallelSystemPowerState status."
- ::= { upsIta2comEntry 80 }
- upsIta2com_81_IneerNetworkconnectStatus OBJECT-TYPE
- SYNTAX INTEGER {
- connected(0),
- disconnected(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_80_IneerNetworkconnectStatus status."
- ::= { upsIta2comEntry 81 }
- upsIta2com_82_Outlet1SwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- turnedon(0),
- turnedoff(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_81_Outlet1SwitchStatus status."
- ::= { upsIta2comEntry 82 }
- upsIta2com_83_Outlet2SwitchStatus OBJECT-TYPE
- SYNTAX INTEGER {
- turnedon(0),
- turnedoff(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_82_Outlet2SwitchStatus status."
- ::= { upsIta2comEntry 83 }
- upsIta2com_84_InputAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_83_InputAbnormal status."
- ::= { upsIta2comEntry 84 }
- upsIta2com_85_SystemOvertemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_84_SystemOvertemp status."
- ::= { upsIta2comEntry 85 }
- upsIta2com_86_SystemBatLowPreWarning OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_85_SystemBatLowPreWarning status."
- ::= { upsIta2comEntry 86 }
- upsIta2com_87_InputPhaseReversed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_86_InputPhaseReversed status."
- ::= { upsIta2comEntry 87 }
- upsIta2com_88_InputNeutralLost OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_87_InputNeutralLost status."
- ::= { upsIta2comEntry 88 }
- upsIta2com_89_InputGroundLost OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_88_InputGroundLost status."
- ::= { upsIta2comEntry 89 }
- upsIta2com_90_RectifierOverload OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_89_RectifierOverload status."
- ::= { upsIta2comEntry 90 }
- upsIta2com_91_BatCabinetNotConnected OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_90_BatCabinetNotConnected status."
- ::= { upsIta2comEntry 91 }
- upsIta2com_92_InverterOverload OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_91_InverterOverload status."
- ::= { upsIta2comEntry 92 }
- upsIta2com_93_LbsAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_92_LbsAbnormal status."
- ::= { upsIta2comEntry 93 }
- upsIta2com_94_OutputPending OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_93_OutputPending status."
- ::= { upsIta2comEntry 94 }
- upsIta2com_95_OutputDisabled OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_94_OutputDisabled status."
- ::= { upsIta2comEntry 95 }
- upsIta2com_96_BypassAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_95_BypassAbnormal status."
- ::= { upsIta2comEntry 96 }
- upsIta2com_97_BypassAbnormalInEcoMode OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_96_BypassAbnormalInEcoMode status."
- ::= { upsIta2comEntry 97 }
- upsIta2com_98_BypassPhaseReversed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_97_BypassPhaseReversed status."
- ::= { upsIta2comEntry 98 }
- upsIta2com_99_BypassOvercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_98_BypassOvercurrent status."
- ::= { upsIta2comEntry 99 }
- upsIta2com_100_BypassCableconnectAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_99_BypassCableconnectAbnormal status."
- ::= { upsIta2comEntry 100 }
- upsIta2com_101_BatReversed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_100_BatReversed status."
- ::= { upsIta2comEntry 101 }
- upsIta2com_102_BatLowPreWarning OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_101_BatLowPreWarning status."
- ::= { upsIta2comEntry 102 }
- upsIta2com_103_BatVoltAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_102_BatVoltAbnormal status."
- ::= { upsIta2comEntry 103 }
- upsIta2com_104_NoBat OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_103_NoBat status."
- ::= { upsIta2comEntry 104 }
- upsIta2com_105_BatOvertemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_104_BatOvertemp status."
- ::= { upsIta2comEntry 105 }
- upsIta2com_106_BatAging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_105_BatAging status."
- ::= { upsIta2comEntry 106 }
- upsIta2com_107_BatTestFailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_106_BatTestFailure status."
- ::= { upsIta2comEntry 107 }
- upsIta2com_108_BatSeriesNotQualified OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_107_BatSeriesNotQualified status."
- ::= { upsIta2comEntry 108 }
- upsIta2com_109_FanFailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_108_FanFailure status."
- ::= { upsIta2comEntry 109 }
- upsIta2com_110_Repo OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_109_Repo status."
- ::= { upsIta2comEntry 110 }
- upsIta2com_111_ElectricLeakAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_110_ElectricLeakAlarm status."
- ::= { upsIta2comEntry 111 }
- upsIta2com_112_VersionIncompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_111_VersionIncompatible status."
- ::= { upsIta2comEntry 112 }
- upsIta2com_113_OutputLpeShort OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_112_OutputLpeShort status."
- ::= { upsIta2comEntry 113 }
- upsIta2com_114_LossOfRedundancy OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_113_LossOfRedundancy status."
- ::= { upsIta2comEntry 114 }
- upsIta2com_115_SystemOverload OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_114_SystemOverload status."
- ::= { upsIta2comEntry 115 }
- upsIta2com_116_LoadSharingAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_115_LoadSharingAbnormal status."
- ::= { upsIta2comEntry 116 }
- upsIta2com_117_SystemParallelSetsAsync OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_116_SystemParallelSetsAsync status."
- ::= { upsIta2comEntry 117 }
- upsIta2com_118_LocalParallelSetsAsync OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_117_LocalParallelSetsAsync status."
- ::= { upsIta2comEntry 118 }
- upsIta2com_119_OnMaintenanceBypass OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_118_OnMaintenanceBypass status."
- ::= { upsIta2comEntry 119 }
- upsIta2com_120_BatMode OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_119_BatMode status."
- ::= { upsIta2comEntry 120 }
- upsIta2com_121_BypassMode OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_120_BypassMode status."
- ::= { upsIta2comEntry 121 }
- upsIta2com_122_ParallelNoAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_121_ParallelNoAbnormal status."
- ::= { upsIta2comEntry 122 }
- upsIta2com_123_BypassCableconnectAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_122_BypassCableconnectAbnormal status."
- ::= { upsIta2comEntry 123 }
- upsIta2com_124_OnIntelligentSleepMode OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_123_OnIntelligentSleepMode status."
- ::= { upsIta2comEntry 124 }
- upsIta2com_125_BatCabinetConnectAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_124_BatCabinetConnectAbnormal status."
- ::= { upsIta2comEntry 125 }
- upsIta2com_126_SystemFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_125_SystemFault status."
- ::= { upsIta2comEntry 126 }
- upsIta2com_127_EodTurnOff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- abnormal(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_126_EodTurnOff status."
- ::= { upsIta2comEntry 127 }
- upsIta2com_128_Bypassdisable OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_127_Bypassdisable status."
- ::= { upsIta2comEntry 128 }
- upsIta2com_129_UPShasnooutput OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_128_UPShasnooutput status."
- ::= { upsIta2comEntry 129 }
- upsIta2com_130_Outputvoltageabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_129_Outputvoltageabnormal status."
- ::= { upsIta2comEntry 130 }
- upsIta2com_131_Localoutputisdisconnected OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_130_Localoutputisdisconnected status."
- ::= { upsIta2comEntry 131 }
- upsIta2com_132_Turnonfailed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_131_Turnonfailed status."
- ::= { upsIta2comEntry 132 }
- upsIta2com_133_Inputfrequencyabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_132_Inputfrequencyabnormal status."
- ::= { upsIta2comEntry 133 }
- upsIta2com_134_Fanagingtimealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_133_Fanagingtimealarm status."
- ::= { upsIta2comEntry 134 }
- upsIta2com_135_Bypassovercurrenttimeout OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_134_Bypassovercurrenttimeout status."
- ::= { upsIta2comEntry 135 }
- upsIta2com_136_BatDCgroundfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_135_BatDCgroundfault status."
- ::= { upsIta2comEntry 136 }
- upsIta2com_137_Systemredundantoverload OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_136_Systemredundantoverload status."
- ::= { upsIta2comEntry 137 }
- upsIta2com_138_BatCommfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_137_BatCommfail status."
- ::= { upsIta2comEntry 138 }
- upsIta2com_139_BatummatchtheUPS OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_138_BatummatchtheUPS status."
- ::= { upsIta2comEntry 139 }
- upsIta2com_140_BatAddrsetwrong OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_139_BatAddrsetwrong status."
- ::= { upsIta2comEntry 140 }
- upsIta2com_141_Batmodelnotqualified OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_140_Batmodelnotqualified status."
- ::= { upsIta2comEntry 141 }
- upsIta2com_142_BatSNabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_141_BatSNabnormal status."
- ::= { upsIta2comEntry 142 }
- upsIta2com_143_Batcabinetconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_142_Batcabinetconnectabnormal status."
- ::= { upsIta2comEntry 143 }
- upsIta2com_144_BatCANconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_143_BatCANconnectabnormal status."
- ::= { upsIta2comEntry 144 }
- upsIta2com_145_BatNoexceedthelimit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_144_BatNoexceedthelimit status."
- ::= { upsIta2comEntry 145 }
- upsIta2com_146_BatgrouplessForbiddischarge OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_145_BatgrouplessForbiddischarge status."
- ::= { upsIta2comEntry 146 }
- upsIta2com_147_Ambienttemplowprealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_146_Ambienttemplowprealarm status."
- ::= { upsIta2comEntry 147 }
- upsIta2com_148_Ambienttemphighprealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_147_Ambienttemphighprealarm status."
- ::= { upsIta2comEntry 148 }
- upsIta2com_149_DcBusAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_148_DcBusAbnormal status."
- ::= { upsIta2comEntry 149 }
- upsIta2com_150_RectifierFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_149_RectifierFault status."
- ::= { upsIta2comEntry 150 }
- upsIta2com_151_DcDcFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_150_DcDcFault status."
- ::= { upsIta2comEntry 151 }
- upsIta2com_152_ChargerFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_151_ChargerFault status."
- ::= { upsIta2comEntry 152 }
- upsIta2com_153_InputBackfeed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_152_InputBackfeed status."
- ::= { upsIta2comEntry 153 }
- upsIta2com_154_InverterFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_153_InverterFault status."
- ::= { upsIta2comEntry 154 }
- upsIta2com_155_InverterRelayWelded OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_154_InverterRelayWelded status."
- ::= { upsIta2comEntry 155 }
- upsIta2com_156_BypassBackfeed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_155_BypassBackfeed status."
- ::= { upsIta2comEntry 156 }
- upsIta2com_157_AuxiliaryPowerFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_156_AuxiliaryPowerFault status."
- ::= { upsIta2comEntry 157 }
- upsIta2com_158_InternalCommFault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_157_InternalCommFault status."
- ::= { upsIta2comEntry 158 }
- upsIta2com_159_OutputShortCircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_158_OutputShortCircuit status."
- ::= { upsIta2comEntry 159 }
- upsIta2com_160_OutputOffAndVoltageIsNotZero OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_159_OutputOffAndVoltageIsNotZero status."
- ::= { upsIta2comEntry 160 }
- upsIta2com_161_ParallelCommBreakdown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_160_ParallelCommBreakdown status."
- ::= { upsIta2comEntry 161 }
- upsIta2com_162_ParallelCableconnectAbnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_161_ParallelCableconnectAbnormal status."
- ::= { upsIta2comEntry 162 }
- upsIta2com_163_Systemfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_162_Systemfault status."
- ::= { upsIta2comEntry 163 }
- upsIta2com_164_Rectifiersoftstartfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_163_Rectifiersoftstartfail status."
- ::= { upsIta2comEntry 164 }
- upsIta2com_165_DSPfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_164_DSPfault status."
- ::= { upsIta2comEntry 165 }
- upsIta2com_166_Year OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_165_Year stored as 1."
- ::= { upsIta2comEntry 166 }
- upsIta2com_167_Month OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_166_Month stored as 1."
- ::= { upsIta2comEntry 167 }
- upsIta2com_168_Day OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_167_Day stored as 1."
- ::= { upsIta2comEntry 168 }
- upsIta2com_169_Hour OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_168_Hour stored as 1."
- ::= { upsIta2comEntry 170 }
- upsIta2com_170_Minute OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_169_Minute stored as 1."
- ::= { upsIta2comEntry 171 }
- upsIta2com_171_Second OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_170_Second stored as 1."
- ::= { upsIta2comEntry 172 }
- upsIta2com_172_InputBackfeed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_171_InputBackfeed status."
- ::= { upsIta2comEntry 173 }
- upsIta2com_173_BypassBackfeed OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_172_BypassBackfeed status."
- ::= { upsIta2comEntry 174 }
- upsIta2com_174_Addr1Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_173_Addr1Batmoduleonline status."
- ::= { upsIta2comEntry 175 }
- upsIta2com_175_Addr2Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_174_Addr2Batmoduleonline status."
- ::= { upsIta2comEntry 176 }
- upsIta2com_176_Addr3Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_175_Addr3Batmoduleonline status."
- ::= { upsIta2comEntry 177 }
- upsIta2com_177_Addr4Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_176_Addr4Batmoduleonline status."
- ::= { upsIta2comEntry 178 }
- upsIta2com_178_Addr5Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_177_Addr5Batmoduleonline status."
- ::= { upsIta2comEntry 179 }
- upsIta2com_179_Addr6Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_178_Addr6Batmoduleonline status."
- ::= { upsIta2comEntry 180 }
- upsIta2com_180_Addr7Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_179_Addr7Batmoduleonline status."
- ::= { upsIta2comEntry 181 }
- upsIta2com_181_Addr8Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_180_Addr8Batmoduleonline status."
- ::= { upsIta2comEntry 182 }
- upsIta2com_182_Addr9Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_181_Addr9Batmoduleonline status."
- ::= { upsIta2comEntry 183 }
- upsIta2com_183_Addr10Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_182_Addr10Batmoduleonline status."
- ::= { upsIta2comEntry 184 }
- upsIta2com_184_Addr11Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_183_Addr11Batmoduleonline status."
- ::= { upsIta2comEntry 185 }
- upsIta2com_185_Addr12Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_184_Addr12Batmoduleonline status."
- ::= { upsIta2comEntry 186 }
- upsIta2com_186_Addr13Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_185_Addr13Batmoduleonline status."
- ::= { upsIta2comEntry 187 }
- upsIta2com_187_Addr14Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_186_Addr14Batmoduleonline status."
- ::= { upsIta2comEntry 188 }
- upsIta2com_188_Addr15Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_187_Addr15Batmoduleonline status."
- ::= { upsIta2comEntry 189 }
- upsIta2com_189_Addr16Batmoduleonline OBJECT-TYPE
- SYNTAX INTEGER {
- disconnect(0),
- online(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_188_Addr16Batmoduleonline status."
- ::= { upsIta2comEntry 190 }
- upsIta2com_190_Addr1Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_189_Addr1Batstatus status."
- ::= { upsIta2comEntry 191 }
- upsIta2com_191_Addr1lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_190_Addr1lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 192 }
- upsIta2com_192_Addr1lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_191_Addr1lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 193 }
- upsIta2com_193_Addr1lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_192_Addr1lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 194 }
- upsIta2com_194_Addr1lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_193_Addr1lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 195 }
- upsIta2com_195_Addr1lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_194_Addr1lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 196 }
- upsIta2com_196_Addr1lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_195_Addr1lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 197 }
- upsIta2com_197_Addr1lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_196_Addr1lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 198 }
- upsIta2com_198_Addr1lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_197_Addr1lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 199 }
- upsIta2com_199_Addr2Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_198_Addr2Batstatus status."
- ::= { upsIta2comEntry 200 }
- upsIta2com_200_Addr2lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_199_Addr2lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 201 }
- upsIta2com_201_Addr2lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_200_Addr2lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 202 }
- upsIta2com_202_Addr2lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_201_Addr2lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 203 }
- upsIta2com_203_Addr2lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_202_Addr2lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 204 }
- upsIta2com_204_Addr2lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_203_Addr2lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 205 }
- upsIta2com_205_Addr2lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_204_Addr2lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 206 }
- upsIta2com_206_Addr2lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_205_Addr2lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 207 }
- upsIta2com_207_Addr2lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_206_Addr2lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 208 }
- upsIta2com_208_Addr3Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_207_Addr3Batstatus status."
- ::= { upsIta2comEntry 209 }
- upsIta2com_209_Addr3lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_208_Addr3lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 210 }
- upsIta2com_210_Addr3lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_209_Addr3lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 211 }
- upsIta2com_211_Addr3lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_210_Addr3lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 212 }
- upsIta2com_212_Addr3lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_211_Addr3lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 213 }
- upsIta2com_213_Addr3lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_212_Addr3lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 214 }
- upsIta2com_214_Addr3lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_213_Addr3lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 215 }
- upsIta2com_215_Addr3lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_214_Addr3lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 216 }
- upsIta2com_216_Addr3lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_215_Addr3lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 217 }
- upsIta2com_217_Addr4Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_216_Addr4Batstatus status."
- ::= { upsIta2comEntry 218 }
- upsIta2com_218_Addr4lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_217_Addr4lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 219 }
- upsIta2com_219_Addr4lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_218_Addr4lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 220 }
- upsIta2com_220_Addr4lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_219_Addr4lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 221 }
- upsIta2com_221_Addr4lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_220_Addr4lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 222 }
- upsIta2com_222_Addr4lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_221_Addr4lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 223 }
- upsIta2com_223_Addr4lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_222_Addr4lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 224 }
- upsIta2com_224_Addr4lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_223_Addr4lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 225 }
- upsIta2com_225_Addr4lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_224_Addr4lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 226 }
- upsIta2com_226_Addr5Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_225_Addr5Batstatus status."
- ::= { upsIta2comEntry 227 }
- upsIta2com_227_Addr5lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_226_Addr5lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 228 }
- upsIta2com_228_Addr5LithiumBatCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_227_Addr5LithiumBatCurrent stored as 0.01A."
- ::= { upsIta2comEntry 229 }
- upsIta2com_229_Addr5lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_228_Addr5lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 230 }
- upsIta2com_230_Addr5lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_229_Addr5lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 231 }
- upsIta2com_231_Addr5lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_230_Addr5lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 232 }
- upsIta2com_232_Addr5lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_231_Addr5lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 233 }
- upsIta2com_233_Addr5lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_232_Addr5lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 234 }
- upsIta2com_234_Addr5lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_233_Addr5lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 235 }
- upsIta2com_235_Addr6Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_234_Addr6Batstatus status."
- ::= { upsIta2comEntry 236 }
- upsIta2com_236_Addr6lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_235_Addr6lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 237 }
- upsIta2com_237_Addr6lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_236_Addr6lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 238 }
- upsIta2com_238_Addr6lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_237_Addr6lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 239 }
- upsIta2com_239_Addr6lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_238_Addr6lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 240 }
- upsIta2com_240_Addr6lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_239_Addr6lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 241 }
- upsIta2com_241_Addr6lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_240_Addr6lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 242 }
- upsIta2com_242_Addr6lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_241_Addr6lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 243 }
- upsIta2com_243_Addr6lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_242_Addr6lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 244 }
- upsIta2com_244_Addr7Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_243_Addr7Batstatus status."
- ::= { upsIta2comEntry 245 }
- upsIta2com_245_Addr7lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_244_Addr7lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 246 }
- upsIta2com_246_Addr7lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_245_Addr7lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 247 }
- upsIta2com_247_Addr7lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_246_Addr7lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 248 }
- upsIta2com_248_Addr7lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_247_Addr7lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 249 }
- upsIta2com_249_Addr7lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_248_Addr7lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 250 }
- upsIta2com_250_Addr7lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_249_Addr7lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 251 }
- upsIta2com_251_Addr7lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_250_Addr7lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 252 }
- upsIta2com_252_Addr7lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_251_Addr7lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 253 }
- upsIta2com_253_Addr8Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_252_Addr8Batstatus status."
- ::= { upsIta2comEntry 254 }
- upsIta2com_254_Addr8lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_253_Addr8lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 255 }
- upsIta2com_255_Addr8lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_254_Addr8lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 256 }
- upsIta2com_256_Addr8lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_255_Addr8lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 257 }
- upsIta2com_257_Addr8lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_256_Addr8lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 258 }
- upsIta2com_258_Addr8lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_257_Addr8lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 259 }
- upsIta2com_259_Addr8lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_258_Addr8lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 260 }
- upsIta2com_260_Addr8lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_259_Addr8lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 261 }
- upsIta2com_261_Addr8lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_260_Addr8lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 262 }
- upsIta2com_262_Addr9Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_261_Addr9Batstatus status."
- ::= { upsIta2comEntry 263 }
- upsIta2com_263_Addr9lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_262_Addr9lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 264 }
- upsIta2com_264_Addr9lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_263_Addr9lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 265 }
- upsIta2com_265_Addr9lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_264_Addr9lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 266 }
- upsIta2com_266_Addr9lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_265_Addr9lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 267 }
- upsIta2com_267_Addr9lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_266_Addr9lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 268 }
- upsIta2com_268_Addr9lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_267_Addr9lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 269 }
- upsIta2com_269_Addr9lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_268_Addr9lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 270 }
- upsIta2com_270_Addr9lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_269_Addr9lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 271 }
- upsIta2com_271_Addr10Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_270_Addr10Batstatus status."
- ::= { upsIta2comEntry 272 }
- upsIta2com_272_Addr10lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_271_Addr10lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 273 }
- upsIta2com_273_Addr10lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_272_Addr10lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 274 }
- upsIta2com_274_Addr10lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_273_Addr10lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 275 }
- upsIta2com_275_Addr10lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_274_Addr10lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 276 }
- upsIta2com_276_Addr10lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_275_Addr10lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 277 }
- upsIta2com_277_Addr10lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_276_Addr10lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 278 }
- upsIta2com_278_Addr10lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_277_Addr10lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 279 }
- upsIta2com_279_Addr10lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_278_Addr10lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 280 }
- upsIta2com_280_Addr11Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_279_Addr11Batstatus status."
- ::= { upsIta2comEntry 281 }
- upsIta2com_281_Addr11lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_280_Addr11lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 282 }
- upsIta2com_282_Addr11lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_281_Addr11lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 283 }
- upsIta2com_283_Addr11lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_282_Addr11lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 284 }
- upsIta2com_284_Addr11lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_283_Addr11lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 285 }
- upsIta2com_285_Addr11lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_284_Addr11lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 286 }
- upsIta2com_286_Addr11lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_285_Addr11lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 287 }
- upsIta2com_287_Addr11lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_286_Addr11lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 288 }
- upsIta2com_288_Addr11lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_287_Addr11lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 289 }
- upsIta2com_289_Addr12Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_288_Addr12Batstatus status."
- ::= { upsIta2comEntry 290 }
- upsIta2com_290_Addr12lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_289_Addr12lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 291 }
- upsIta2com_291_Addr12lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_290_Addr12lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 292 }
- upsIta2com_292_Addr12lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_291_Addr12lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 293 }
- upsIta2com_293_Addr12lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_292_Addr12lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 294 }
- upsIta2com_294_Addr12lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_293_Addr12lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 295 }
- upsIta2com_295_Addr12lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_294_Addr12lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 296 }
- upsIta2com_296_Addr12lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_295_Addr12lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 297 }
- upsIta2com_297_Addr12lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_296_Addr12lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 298 }
- upsIta2com_298_Addr13Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_297_Addr13Batstatus status."
- ::= { upsIta2comEntry 299 }
- upsIta2com_299_Addr13lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_298_Addr13lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 300 }
- upsIta2com_300_Addr13lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_299_Addr13lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 301 }
- upsIta2com_301_Addr13lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_300_Addr13lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 302 }
- upsIta2com_302_Addr13lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_301_Addr13lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 303 }
- upsIta2com_303_Addr13lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_302_Addr13lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 304 }
- upsIta2com_304_Addr13lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_303_Addr13lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 305 }
- upsIta2com_305_Addr13lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_304_Addr13lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 306 }
- upsIta2com_306_Addr13lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_305_Addr13lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 307 }
- upsIta2com_307_Addr14Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_306_Addr14Batstatus status."
- ::= { upsIta2comEntry 308 }
- upsIta2com_308_Addr14lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_307_Addr14lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 309 }
- upsIta2com_309_Addr14LithiumBatCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_308_Addr14LithiumBatCurrent stored as 0.01A."
- ::= { upsIta2comEntry 310 }
- upsIta2com_310_Addr14lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_309_Addr14lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 311 }
- upsIta2com_311_Addr14lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_310_Addr14lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 312 }
- upsIta2com_312_Addr14lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_311_Addr14lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 313 }
- upsIta2com_313_Addr14lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_312_Addr14lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 314 }
- upsIta2com_314_Addr14lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_313_Addr14lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 315 }
- upsIta2com_315_Addr14lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_314_Addr14lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 316 }
- upsIta2com_316_Addr15Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_315_Addr15Batstatus status."
- ::= { upsIta2comEntry 317 }
- upsIta2com_317_Addr15lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_316_Addr15lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 318 }
- upsIta2com_318_Addr15lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_317_Addr15lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 319 }
- upsIta2com_319_Addr15lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_318_Addr15lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 320 }
- upsIta2com_320_Addr15lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_319_Addr15lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 321 }
- upsIta2com_321_Addr15lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_320_Addr15lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 322 }
- upsIta2com_322_Addr15lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_321_Addr15lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 323 }
- upsIta2com_323_Addr15lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_322_Addr15lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 324 }
- upsIta2com_324_Addr15lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_323_Addr15lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 325 }
- upsIta2com_325_Addr16Batstatus OBJECT-TYPE
- SYNTAX INTEGER {
- idle(0),
- charging(1),
- discharging(2),
- balance(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_324_Addr16Batstatus status."
- ::= { upsIta2comEntry 326 }
- upsIta2com_326_Addr16lithiumBatvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_325_Addr16lithiumBatvoltage stored as 0.01V."
- ::= { upsIta2comEntry 327 }
- upsIta2com_327_Addr16lithiumBatcurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_326_Addr16lithiumBatcurrent stored as 0.01A."
- ::= { upsIta2comEntry 328 }
- upsIta2com_328_Addr16lithiumBatSOC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_327_Addr16lithiumBatSOC stored as 0.01%."
- ::= { upsIta2comEntry 329 }
- upsIta2com_329_Addr16lithiumBatSOH OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_328_Addr16lithiumBatSOH stored as 0.01%."
- ::= { upsIta2comEntry 330 }
- upsIta2com_330_Addr16lithiumBatcellmaxvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_329_Addr16lithiumBatcellmaxvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 331 }
- upsIta2com_331_Addr16lithiumBatcellminvoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_330_Addr16lithiumBatcellminvoltage stored as 0.01mV."
- ::= { upsIta2comEntry 332 }
- upsIta2com_332_Addr16lithiumBatcellmaxtemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_331_Addr16lithiumBatcellmaxtemp stored as 0.01℃."
- ::= { upsIta2comEntry 333 }
- upsIta2com_333_Addr16lithiumBatcellmintemp OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_332_Addr16lithiumBatcellmintemp stored as 0.01℃."
- ::= { upsIta2comEntry 334 }
- upsIta2com_334_Addr1Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_333_Addr1Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 335 }
- upsIta2com_335_Addr1Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_334_Addr1Bathighvolt status."
- ::= { upsIta2comEntry 336 }
- upsIta2com_336_Addr1Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_335_Addr1Batlowvolt status."
- ::= { upsIta2comEntry 337 }
- upsIta2com_337_Addr1Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_336_Addr1Bathighcellvolt status."
- ::= { upsIta2comEntry 338 }
- upsIta2com_338_Addr1Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_337_Addr1Batlowcellvolt status."
- ::= { upsIta2comEntry 339 }
- upsIta2com_339_Addr1Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_338_Addr1Batchargehighcelltemp status."
- ::= { upsIta2comEntry 340 }
- upsIta2com_340_Addr1Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_339_Addr1Batchargelowcelltemp status."
- ::= { upsIta2comEntry 341 }
- upsIta2com_341_Addr1Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_340_Addr1Batchargeovercurrent status."
- ::= { upsIta2comEntry 342 }
- upsIta2com_342_Addr1Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_341_Addr1Batdischargeovercurrent status."
- ::= { upsIta2comEntry 343 }
- upsIta2com_343_Addr1BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_342_Addr1BatAddrconflict status."
- ::= { upsIta2comEntry 344 }
- upsIta2com_344_Addr1Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_343_Addr1Batportreverse status."
- ::= { upsIta2comEntry 345 }
- upsIta2com_345_Addr1BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_344_Addr1BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 346 }
- upsIta2com_346_Addr1Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_345_Addr1Batsafetyundervoltage status."
- ::= { upsIta2comEntry 347 }
- upsIta2com_347_Addr1Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_346_Addr1Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 348 }
- upsIta2com_348_Addr1Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_347_Addr1Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 349 }
- upsIta2com_349_Addr1Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_348_Addr1Batparallelchargehightemp status."
- ::= { upsIta2comEntry 350 }
- upsIta2com_350_Addr1BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_349_Addr1BatinternalCommabnormal status."
- ::= { upsIta2comEntry 351 }
- upsIta2com_351_Addr1Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_350_Addr1Batconditionfail status."
- ::= { upsIta2comEntry 352 }
- upsIta2com_352_Addr1BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_351_Addr1BatLowinsulationresistance status."
- ::= { upsIta2comEntry 353 }
- upsIta2com_353_Addr1BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_352_Addr1BatLargepressurediff status."
- ::= { upsIta2comEntry 354 }
- upsIta2com_354_Addr1BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_353_Addr1BatBatfailure status."
- ::= { upsIta2comEntry 355 }
- upsIta2com_355_Addr1BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_354_Addr1BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 356 }
- upsIta2com_356_Addr1BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_355_Addr1BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 357 }
- upsIta2com_357_Addr1BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_356_Addr1BatTempcolllectfailure status."
- ::= { upsIta2comEntry 358 }
- upsIta2com_358_Addr1BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_357_Addr1BatAddrSeterror status."
- ::= { upsIta2comEntry 359 }
- upsIta2com_359_Addr1BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_358_Addr1BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 360 }
- upsIta2com_360_Addr1BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_359_Addr1BatMOSFETfailure status."
- ::= { upsIta2comEntry 361 }
- upsIta2com_361_Addr1Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_360_Addr1Battempabnormal status."
- ::= { upsIta2comEntry 362 }
- upsIta2com_362_Addr1Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_361_Addr1Batcablefault status."
- ::= { upsIta2comEntry 363 }
- upsIta2com_363_Addr1BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_362_Addr1BatShortcircuit status."
- ::= { upsIta2comEntry 364 }
- upsIta2com_364_Addr1BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_363_Addr1BatOtherfailures status."
- ::= { upsIta2comEntry 365 }
- upsIta2com_365_Addr1BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_364_Addr1BatCommcablefailure status."
- ::= { upsIta2comEntry 366 }
- upsIta2com_366_Addr1BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_365_Addr1BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 367 }
- upsIta2com_367_Addr1BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_366_Addr1BatFuseblown status."
- ::= { upsIta2comEntry 368 }
- upsIta2com_368_Addr1BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_367_Addr1BatWaitingforcharging status."
- ::= { upsIta2comEntry 369 }
- upsIta2com_369_Addr1BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_368_Addr1BatBataging status."
- ::= { upsIta2comEntry 370 }
- upsIta2com_370_Addr1Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_369_Addr1Batboxconnectabnormal status."
- ::= { upsIta2comEntry 371 }
- upsIta2com_371_Addr1batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_370_Addr1batBatterySoftincompatible status."
- ::= { upsIta2comEntry 372 }
- upsIta2com_372_Addr1batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_371_Addr1batEOL status."
- ::= { upsIta2comEntry 373 }
- upsIta2com_373_Addr1batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_372_Addr1batSamplingfailure status."
- ::= { upsIta2comEntry 374 }
- upsIta2com_374_Addr1batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_373_Addr1batHardwareprotection status."
- ::= { upsIta2comEntry 375 }
- upsIta2com_375_Addr1batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_374_Addr1batBatterycapacitylow status."
- ::= { upsIta2comEntry 376 }
- upsIta2com_376_Addr2Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_375_Addr2Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 377 }
- upsIta2com_377_Addr2Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_376_Addr2Bathighvolt status."
- ::= { upsIta2comEntry 378 }
- upsIta2com_378_Addr2Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_377_Addr2Batlowvolt status."
- ::= { upsIta2comEntry 379 }
- upsIta2com_379_Addr2Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_378_Addr2Bathighcellvolt status."
- ::= { upsIta2comEntry 380 }
- upsIta2com_380_Addr2Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_379_Addr2Batlowcellvolt status."
- ::= { upsIta2comEntry 381 }
- upsIta2com_381_Addr2Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_380_Addr2Batchargehighcelltemp status."
- ::= { upsIta2comEntry 382 }
- upsIta2com_382_Addr2Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_381_Addr2Batchargelowcelltemp status."
- ::= { upsIta2comEntry 383 }
- upsIta2com_383_Addr2Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_382_Addr2Batchargeovercurrent status."
- ::= { upsIta2comEntry 384 }
- upsIta2com_384_Addr2Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_383_Addr2Batdischargeovercurrent status."
- ::= { upsIta2comEntry 385 }
- upsIta2com_385_Addr2BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_384_Addr2BatAddrconflict status."
- ::= { upsIta2comEntry 386 }
- upsIta2com_386_Addr2Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_385_Addr2Batportreverse status."
- ::= { upsIta2comEntry 387 }
- upsIta2com_387_Addr2BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_386_Addr2BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 388 }
- upsIta2com_388_Addr2Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_387_Addr2Batsafetyundervoltage status."
- ::= { upsIta2comEntry 389 }
- upsIta2com_389_Addr2Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_388_Addr2Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 390 }
- upsIta2com_390_Addr2Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_389_Addr2Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 391 }
- upsIta2com_391_Addr2Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_390_Addr2Batparallelchargehightemp status."
- ::= { upsIta2comEntry 392 }
- upsIta2com_392_Addr2BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_391_Addr2BatinternalCommabnormal status."
- ::= { upsIta2comEntry 393 }
- upsIta2com_393_Addr2Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_392_Addr2Batconditionfail status."
- ::= { upsIta2comEntry 394 }
- upsIta2com_394_Addr2BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_393_Addr2BatLowinsulationresistance status."
- ::= { upsIta2comEntry 395 }
- upsIta2com_395_Addr2BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_394_Addr2BatLargepressurediff status."
- ::= { upsIta2comEntry 396 }
- upsIta2com_396_Addr2BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_395_Addr2BatBatfailure status."
- ::= { upsIta2comEntry 397 }
- upsIta2com_397_Addr2BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_396_Addr2BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 398 }
- upsIta2com_398_Addr2BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_397_Addr2BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 399 }
- upsIta2com_399_Addr2BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_398_Addr2BatTempcolllectfailure status."
- ::= { upsIta2comEntry 400 }
- upsIta2com_400_Addr2BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_399_Addr2BatAddrSeterror status."
- ::= { upsIta2comEntry 401 }
- upsIta2com_401_Addr2BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_400_Addr2BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 402 }
- upsIta2com_402_Addr2BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_401_Addr2BatMOSFETfailure status."
- ::= { upsIta2comEntry 403 }
- upsIta2com_403_Addr2Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_402_Addr2Battempabnormal status."
- ::= { upsIta2comEntry 404 }
- upsIta2com_404_Addr2Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_403_Addr2Batcablefault status."
- ::= { upsIta2comEntry 405 }
- upsIta2com_405_Addr2BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_404_Addr2BatShortcircuit status."
- ::= { upsIta2comEntry 406 }
- upsIta2com_406_Addr2BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_405_Addr2BatOtherfailures status."
- ::= { upsIta2comEntry 407 }
- upsIta2com_407_Addr2BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_406_Addr2BatCommcablefailure status."
- ::= { upsIta2comEntry 408 }
- upsIta2com_408_Addr2BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_407_Addr2BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 409 }
- upsIta2com_409_Addr2BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_408_Addr2BatFuseblown status."
- ::= { upsIta2comEntry 410 }
- upsIta2com_410_Addr2BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_409_Addr2BatWaitingforcharging status."
- ::= { upsIta2comEntry 411 }
- upsIta2com_411_Addr2BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_410_Addr2BatBataging status."
- ::= { upsIta2comEntry 412 }
- upsIta2com_412_Addr2Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_411_Addr2Batboxconnectabnormal status."
- ::= { upsIta2comEntry 413 }
- upsIta2com_413_Addr2batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_412_Addr2batBatterySoftincompatible status."
- ::= { upsIta2comEntry 414 }
- upsIta2com_414_Addr2batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_413_Addr2batEOL status."
- ::= { upsIta2comEntry 415 }
- upsIta2com_415_Addr2batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_414_Addr2batSamplingfailure status."
- ::= { upsIta2comEntry 416 }
- upsIta2com_416_Addr2batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_415_Addr2batHardwareprotection status."
- ::= { upsIta2comEntry 417 }
- upsIta2com_417_Addr2batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_416_Addr2batBatterycapacitylow status."
- ::= { upsIta2comEntry 418 }
- upsIta2com_418_Addr3Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_417_Addr3Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 419 }
- upsIta2com_419_Addr3Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_418_Addr3Bathighvolt status."
- ::= { upsIta2comEntry 420 }
- upsIta2com_420_Addr3Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_419_Addr3Batlowvolt status."
- ::= { upsIta2comEntry 421 }
- upsIta2com_421_Addr3Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_420_Addr3Bathighcellvolt status."
- ::= { upsIta2comEntry 422 }
- upsIta2com_422_Addr3Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_421_Addr3Batlowcellvolt status."
- ::= { upsIta2comEntry 423 }
- upsIta2com_423_Addr3Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_422_Addr3Batchargehighcelltemp status."
- ::= { upsIta2comEntry 424 }
- upsIta2com_424_Addr3Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_423_Addr3Batchargelowcelltemp status."
- ::= { upsIta2comEntry 425 }
- upsIta2com_425_Addr3Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_424_Addr3Batchargeovercurrent status."
- ::= { upsIta2comEntry 426 }
- upsIta2com_426_Addr3Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_425_Addr3Batdischargeovercurrent status."
- ::= { upsIta2comEntry 427 }
- upsIta2com_427_Addr3BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_426_Addr3BatAddrconflict status."
- ::= { upsIta2comEntry 428 }
- upsIta2com_428_Addr3Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_427_Addr3Batportreverse status."
- ::= { upsIta2comEntry 429 }
- upsIta2com_429_Addr3BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_428_Addr3BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 430 }
- upsIta2com_430_Addr3Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_429_Addr3Batsafetyundervoltage status."
- ::= { upsIta2comEntry 431 }
- upsIta2com_431_Addr3Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_430_Addr3Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 432 }
- upsIta2com_432_Addr3Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_431_Addr3Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 433 }
- upsIta2com_433_Addr3Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_432_Addr3Batparallelchargehightemp status."
- ::= { upsIta2comEntry 434 }
- upsIta2com_434_Addr3BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_433_Addr3BatinternalCommabnormal status."
- ::= { upsIta2comEntry 435 }
- upsIta2com_435_Addr3Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_434_Addr3Batconditionfail status."
- ::= { upsIta2comEntry 436 }
- upsIta2com_436_Addr3BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_435_Addr3BatLowinsulationresistance status."
- ::= { upsIta2comEntry 437 }
- upsIta2com_437_Addr3BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_436_Addr3BatLargepressurediff status."
- ::= { upsIta2comEntry 438 }
- upsIta2com_438_Addr3BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_437_Addr3BatBatfailure status."
- ::= { upsIta2comEntry 439 }
- upsIta2com_439_Addr3BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_438_Addr3BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 440 }
- upsIta2com_440_Addr3BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_439_Addr3BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 441 }
- upsIta2com_441_Addr3BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_440_Addr3BatTempcolllectfailure status."
- ::= { upsIta2comEntry 442 }
- upsIta2com_442_Addr3BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_441_Addr3BatAddrSeterror status."
- ::= { upsIta2comEntry 443 }
- upsIta2com_443_Addr3BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_442_Addr3BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 444 }
- upsIta2com_444_Addr3BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_443_Addr3BatMOSFETfailure status."
- ::= { upsIta2comEntry 445 }
- upsIta2com_445_Addr3Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_444_Addr3Battempabnormal status."
- ::= { upsIta2comEntry 446 }
- upsIta2com_446_Addr3Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_445_Addr3Batcablefault status."
- ::= { upsIta2comEntry 447 }
- upsIta2com_447_Addr3BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_446_Addr3BatShortcircuit status."
- ::= { upsIta2comEntry 448 }
- upsIta2com_448_Addr3BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_447_Addr3BatOtherfailures status."
- ::= { upsIta2comEntry 449 }
- upsIta2com_449_Addr3BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_448_Addr3BatCommcablefailure status."
- ::= { upsIta2comEntry 450 }
- upsIta2com_450_Addr3BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_449_Addr3BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 451 }
- upsIta2com_451_Addr3BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_450_Addr3BatFuseblown status."
- ::= { upsIta2comEntry 452 }
- upsIta2com_452_Addr3BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_451_Addr3BatWaitingforcharging status."
- ::= { upsIta2comEntry 453 }
- upsIta2com_453_Addr3BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_452_Addr3BatBataging status."
- ::= { upsIta2comEntry 454 }
- upsIta2com_454_Addr3Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_453_Addr3Batboxconnectabnormal status."
- ::= { upsIta2comEntry 455 }
- upsIta2com_455_Addr3batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_454_Addr3batBatterySoftincompatible status."
- ::= { upsIta2comEntry 456 }
- upsIta2com_456_Addr3batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_455_Addr3batEOL status."
- ::= { upsIta2comEntry 457 }
- upsIta2com_457_Addr3batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_456_Addr3batSamplingfailure status."
- ::= { upsIta2comEntry 458 }
- upsIta2com_458_Addr3batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_457_Addr3batHardwareprotection status."
- ::= { upsIta2comEntry 459 }
- upsIta2com_459_Addr3batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_458_Addr3batBatterycapacitylow status."
- ::= { upsIta2comEntry 460 }
- upsIta2com_460_Addr4Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_459_Addr4Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 461 }
- upsIta2com_461_Addr4Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_460_Addr4Bathighvolt status."
- ::= { upsIta2comEntry 462 }
- upsIta2com_462_Addr4Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_461_Addr4Batlowvolt status."
- ::= { upsIta2comEntry 463 }
- upsIta2com_463_Addr4Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_462_Addr4Bathighcellvolt status."
- ::= { upsIta2comEntry 464 }
- upsIta2com_464_Addr4Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_463_Addr4Batlowcellvolt status."
- ::= { upsIta2comEntry 465 }
- upsIta2com_465_Addr4Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_464_Addr4Batchargehighcelltemp status."
- ::= { upsIta2comEntry 466 }
- upsIta2com_466_Addr4Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_465_Addr4Batchargelowcelltemp status."
- ::= { upsIta2comEntry 467 }
- upsIta2com_467_Addr4Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_466_Addr4Batchargeovercurrent status."
- ::= { upsIta2comEntry 468 }
- upsIta2com_468_Addr4Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_467_Addr4Batdischargeovercurrent status."
- ::= { upsIta2comEntry 469 }
- upsIta2com_469_Addr4BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_468_Addr4BatAddrconflict status."
- ::= { upsIta2comEntry 470 }
- upsIta2com_470_Addr4Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_469_Addr4Batportreverse status."
- ::= { upsIta2comEntry 471 }
- upsIta2com_471_Addr4BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_470_Addr4BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 472 }
- upsIta2com_472_Addr4Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_471_Addr4Batsafetyundervoltage status."
- ::= { upsIta2comEntry 473 }
- upsIta2com_473_Addr4Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_472_Addr4Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 474 }
- upsIta2com_474_Addr4Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_473_Addr4Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 475 }
- upsIta2com_475_Addr4Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_474_Addr4Batparallelchargehightemp status."
- ::= { upsIta2comEntry 476 }
- upsIta2com_476_Addr4BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_475_Addr4BatinternalCommabnormal status."
- ::= { upsIta2comEntry 477 }
- upsIta2com_477_Addr4Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_476_Addr4Batconditionfail status."
- ::= { upsIta2comEntry 478 }
- upsIta2com_478_Addr4BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_477_Addr4BatLowinsulationresistance status."
- ::= { upsIta2comEntry 479 }
- upsIta2com_479_Addr4BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_478_Addr4BatLargepressurediff status."
- ::= { upsIta2comEntry 480 }
- upsIta2com_480_Addr4BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_479_Addr4BatBatfailure status."
- ::= { upsIta2comEntry 481 }
- upsIta2com_481_Addr4BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_480_Addr4BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 482 }
- upsIta2com_482_Addr4BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_481_Addr4BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 483 }
- upsIta2com_483_Addr4BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_482_Addr4BatTempcolllectfailure status."
- ::= { upsIta2comEntry 484 }
- upsIta2com_484_Addr4BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_483_Addr4BatAddrSeterror status."
- ::= { upsIta2comEntry 485 }
- upsIta2com_485_Addr4BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_484_Addr4BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 486 }
- upsIta2com_486_Addr4BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_485_Addr4BatMOSFETfailure status."
- ::= { upsIta2comEntry 487 }
- upsIta2com_487_Addr4Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_486_Addr4Battempabnormal status."
- ::= { upsIta2comEntry 488 }
- upsIta2com_488_Addr4Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_487_Addr4Batcablefault status."
- ::= { upsIta2comEntry 489 }
- upsIta2com_489_Addr4BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_488_Addr4BatShortcircuit status."
- ::= { upsIta2comEntry 490 }
- upsIta2com_490_Addr4BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_489_Addr4BatOtherfailures status."
- ::= { upsIta2comEntry 491 }
- upsIta2com_491_Addr4BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_490_Addr4BatCommcablefailure status."
- ::= { upsIta2comEntry 492 }
- upsIta2com_492_Addr4BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_491_Addr4BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 493 }
- upsIta2com_493_Addr4BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_492_Addr4BatFuseblown status."
- ::= { upsIta2comEntry 494 }
- upsIta2com_494_Addr4BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_493_Addr4BatWaitingforcharging status."
- ::= { upsIta2comEntry 495 }
- upsIta2com_495_Addr4BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_494_Addr4BatBataging status."
- ::= { upsIta2comEntry 496 }
- upsIta2com_496_Addr4Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_495_Addr4Batboxconnectabnormal status."
- ::= { upsIta2comEntry 497 }
- upsIta2com_497_Addr4batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_496_Addr4batBatterySoftincompatible status."
- ::= { upsIta2comEntry 498 }
- upsIta2com_498_Addr4batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_497_Addr4batEOL status."
- ::= { upsIta2comEntry 499 }
- upsIta2com_499_Addr4batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_498_Addr4batSamplingfailure status."
- ::= { upsIta2comEntry 500 }
- upsIta2com_500_Addr4batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_499_Addr4batHardwareprotection status."
- ::= { upsIta2comEntry 501 }
- upsIta2com_501_Addr4batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_500_Addr4batBatterycapacitylow status."
- ::= { upsIta2comEntry 502 }
- upsIta2com_502_Addr5Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_501_Addr5Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 503 }
- upsIta2com_503_Addr5Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_502_Addr5Bathighvolt status."
- ::= { upsIta2comEntry 504 }
- upsIta2com_504_Addr5Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_503_Addr5Batlowvolt status."
- ::= { upsIta2comEntry 505 }
- upsIta2com_505_Addr5Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_504_Addr5Bathighcellvolt status."
- ::= { upsIta2comEntry 506 }
- upsIta2com_506_Addr5Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_505_Addr5Batlowcellvolt status."
- ::= { upsIta2comEntry 507 }
- upsIta2com_507_Addr5Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_506_Addr5Batchargehighcelltemp status."
- ::= { upsIta2comEntry 508 }
- upsIta2com_508_Addr5Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_507_Addr5Batchargelowcelltemp status."
- ::= { upsIta2comEntry 509 }
- upsIta2com_509_Addr5Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_508_Addr5Batchargeovercurrent status."
- ::= { upsIta2comEntry 510 }
- upsIta2com_510_Addr5Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_509_Addr5Batdischargeovercurrent status."
- ::= { upsIta2comEntry 511 }
- upsIta2com_511_Addr5BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_510_Addr5BatAddrconflict status."
- ::= { upsIta2comEntry 512 }
- upsIta2com_512_Addr5Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_511_Addr5Batportreverse status."
- ::= { upsIta2comEntry 513 }
- upsIta2com_513_Addr5BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_512_Addr5BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 514 }
- upsIta2com_514_Addr5Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_513_Addr5Batsafetyundervoltage status."
- ::= { upsIta2comEntry 515 }
- upsIta2com_515_Addr5Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_514_Addr5Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 516 }
- upsIta2com_516_Addr5Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_515_Addr5Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 517 }
- upsIta2com_517_Addr5Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_516_Addr5Batparallelchargehightemp status."
- ::= { upsIta2comEntry 518 }
- upsIta2com_518_Addr5BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_517_Addr5BatinternalCommabnormal status."
- ::= { upsIta2comEntry 519 }
- upsIta2com_519_Addr5Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_518_Addr5Batconditionfail status."
- ::= { upsIta2comEntry 520 }
- upsIta2com_520_Addr5BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_519_Addr5BatLowinsulationresistance status."
- ::= { upsIta2comEntry 521 }
- upsIta2com_521_Addr5BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_520_Addr5BatLargepressurediff status."
- ::= { upsIta2comEntry 522 }
- upsIta2com_522_Addr5BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_521_Addr5BatBatfailure status."
- ::= { upsIta2comEntry 523 }
- upsIta2com_523_Addr5BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_522_Addr5BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 524 }
- upsIta2com_524_Addr5BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_523_Addr5BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 525 }
- upsIta2com_525_Addr5BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_524_Addr5BatTempcolllectfailure status."
- ::= { upsIta2comEntry 526 }
- upsIta2com_526_Addr5BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_525_Addr5BatAddrSeterror status."
- ::= { upsIta2comEntry 527 }
- upsIta2com_527_Addr5BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_526_Addr5BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 528 }
- upsIta2com_528_Addr5BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_527_Addr5BatMOSFETfailure status."
- ::= { upsIta2comEntry 529 }
- upsIta2com_529_Addr5Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_528_Addr5Battempabnormal status."
- ::= { upsIta2comEntry 530 }
- upsIta2com_530_Addr5Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_529_Addr5Batcablefault status."
- ::= { upsIta2comEntry 531 }
- upsIta2com_531_Addr5BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_530_Addr5BatShortcircuit status."
- ::= { upsIta2comEntry 532 }
- upsIta2com_532_Addr5BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_531_Addr5BatOtherfailures status."
- ::= { upsIta2comEntry 533 }
- upsIta2com_533_Addr5BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_532_Addr5BatCommcablefailure status."
- ::= { upsIta2comEntry 534 }
- upsIta2com_534_Addr5BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_533_Addr5BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 535 }
- upsIta2com_535_Addr5BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_534_Addr5BatFuseblown status."
- ::= { upsIta2comEntry 536 }
- upsIta2com_536_Addr5BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_535_Addr5BatWaitingforcharging status."
- ::= { upsIta2comEntry 537 }
- upsIta2com_537_Addr5BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_536_Addr5BatBataging status."
- ::= { upsIta2comEntry 538 }
- upsIta2com_538_Addr5Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_537_Addr5Batboxconnectabnormal status."
- ::= { upsIta2comEntry 539 }
- upsIta2com_539_Addr5batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_538_Addr5batBatterySoftincompatible status."
- ::= { upsIta2comEntry 540 }
- upsIta2com_540_Addr5batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_539_Addr5batEOL status."
- ::= { upsIta2comEntry 541 }
- upsIta2com_541_Addr5batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_540_Addr5batSamplingfailure status."
- ::= { upsIta2comEntry 542 }
- upsIta2com_542_Addr5batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_541_Addr5batHardwareprotection status."
- ::= { upsIta2comEntry 543 }
- upsIta2com_543_Addr5batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_542_Addr5batBatterycapacitylow status."
- ::= { upsIta2comEntry 544 }
- upsIta2com_544_Addr6Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_543_Addr6Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 545 }
- upsIta2com_545_Addr6Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_544_Addr6Bathighvolt status."
- ::= { upsIta2comEntry 546 }
- upsIta2com_546_Addr6Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_545_Addr6Batlowvolt status."
- ::= { upsIta2comEntry 547 }
- upsIta2com_547_Addr6Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_546_Addr6Bathighcellvolt status."
- ::= { upsIta2comEntry 548 }
- upsIta2com_548_Addr6Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_547_Addr6Batlowcellvolt status."
- ::= { upsIta2comEntry 549 }
- upsIta2com_549_Addr6Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_548_Addr6Batchargehighcelltemp status."
- ::= { upsIta2comEntry 550 }
- upsIta2com_550_Addr6Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_549_Addr6Batchargelowcelltemp status."
- ::= { upsIta2comEntry 551 }
- upsIta2com_551_Addr6Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_550_Addr6Batchargeovercurrent status."
- ::= { upsIta2comEntry 552 }
- upsIta2com_552_Addr6Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_551_Addr6Batdischargeovercurrent status."
- ::= { upsIta2comEntry 553 }
- upsIta2com_553_Addr6BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_552_Addr6BatAddrconflict status."
- ::= { upsIta2comEntry 554 }
- upsIta2com_554_Addr6Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_553_Addr6Batportreverse status."
- ::= { upsIta2comEntry 555 }
- upsIta2com_555_Addr6BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_554_Addr6BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 556 }
- upsIta2com_556_Addr6Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_555_Addr6Batsafetyundervoltage status."
- ::= { upsIta2comEntry 557 }
- upsIta2com_557_Addr6Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_556_Addr6Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 558 }
- upsIta2com_558_Addr6Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_557_Addr6Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 559 }
- upsIta2com_559_Addr6Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_558_Addr6Batparallelchargehightemp status."
- ::= { upsIta2comEntry 560 }
- upsIta2com_560_Addr6BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_559_Addr6BatinternalCommabnormal status."
- ::= { upsIta2comEntry 561 }
- upsIta2com_561_Addr6Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_560_Addr6Batconditionfail status."
- ::= { upsIta2comEntry 562 }
- upsIta2com_562_Addr6BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_561_Addr6BatLowinsulationresistance status."
- ::= { upsIta2comEntry 563 }
- upsIta2com_563_Addr6BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_562_Addr6BatLargepressurediff status."
- ::= { upsIta2comEntry 564 }
- upsIta2com_564_Addr6BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_563_Addr6BatBatfailure status."
- ::= { upsIta2comEntry 565 }
- upsIta2com_565_Addr6BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_564_Addr6BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 566 }
- upsIta2com_566_Addr6BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_565_Addr6BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 567 }
- upsIta2com_567_Addr6BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_566_Addr6BatTempcolllectfailure status."
- ::= { upsIta2comEntry 568 }
- upsIta2com_568_Addr6BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_567_Addr6BatAddrSeterror status."
- ::= { upsIta2comEntry 569 }
- upsIta2com_569_Addr6BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_568_Addr6BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 570 }
- upsIta2com_570_Addr6BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_569_Addr6BatMOSFETfailure status."
- ::= { upsIta2comEntry 571 }
- upsIta2com_571_Addr6Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_570_Addr6Battempabnormal status."
- ::= { upsIta2comEntry 572 }
- upsIta2com_572_Addr6Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_571_Addr6Batcablefault status."
- ::= { upsIta2comEntry 573 }
- upsIta2com_573_Addr6BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_572_Addr6BatShortcircuit status."
- ::= { upsIta2comEntry 574 }
- upsIta2com_574_Addr6BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_573_Addr6BatOtherfailures status."
- ::= { upsIta2comEntry 575 }
- upsIta2com_575_Addr6BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_574_Addr6BatCommcablefailure status."
- ::= { upsIta2comEntry 576 }
- upsIta2com_576_Addr6BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_575_Addr6BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 577 }
- upsIta2com_577_Addr6BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_576_Addr6BatFuseblown status."
- ::= { upsIta2comEntry 578 }
- upsIta2com_578_Addr6BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_577_Addr6BatWaitingforcharging status."
- ::= { upsIta2comEntry 579 }
- upsIta2com_579_Addr6BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_578_Addr6BatBataging status."
- ::= { upsIta2comEntry 580 }
- upsIta2com_580_Addr6Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_579_Addr6Batboxconnectabnormal status."
- ::= { upsIta2comEntry 581 }
- upsIta2com_581_Addr6batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_580_Addr6batBatterySoftincompatible status."
- ::= { upsIta2comEntry 582 }
- upsIta2com_582_Addr6batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_581_Addr6batEOL status."
- ::= { upsIta2comEntry 583 }
- upsIta2com_583_Addr6batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_582_Addr6batSamplingfailure status."
- ::= { upsIta2comEntry 584 }
- upsIta2com_584_Addr6batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_583_Addr6batHardwareprotection status."
- ::= { upsIta2comEntry 585 }
- upsIta2com_585_Addr6batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_584_Addr6batBatterycapacitylow status."
- ::= { upsIta2comEntry 586 }
- upsIta2com_586_Addr7Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_585_Addr7Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 587 }
- upsIta2com_587_Addr7Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_586_Addr7Bathighvolt status."
- ::= { upsIta2comEntry 588 }
- upsIta2com_588_Addr7Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_587_Addr7Batlowvolt status."
- ::= { upsIta2comEntry 589 }
- upsIta2com_589_Addr7Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_588_Addr7Bathighcellvolt status."
- ::= { upsIta2comEntry 590 }
- upsIta2com_590_Addr7Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_589_Addr7Batlowcellvolt status."
- ::= { upsIta2comEntry 591 }
- upsIta2com_591_Addr7Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_590_Addr7Batchargehighcelltemp status."
- ::= { upsIta2comEntry 592 }
- upsIta2com_592_Addr7Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_591_Addr7Batchargelowcelltemp status."
- ::= { upsIta2comEntry 593 }
- upsIta2com_593_Addr7Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_592_Addr7Batchargeovercurrent status."
- ::= { upsIta2comEntry 594 }
- upsIta2com_594_Addr7Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_593_Addr7Batdischargeovercurrent status."
- ::= { upsIta2comEntry 595 }
- upsIta2com_595_Addr7BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_594_Addr7BatAddrconflict status."
- ::= { upsIta2comEntry 596 }
- upsIta2com_596_Addr7Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_595_Addr7Batportreverse status."
- ::= { upsIta2comEntry 597 }
- upsIta2com_597_Addr7BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_596_Addr7BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 598 }
- upsIta2com_598_Addr7Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_597_Addr7Batsafetyundervoltage status."
- ::= { upsIta2comEntry 599 }
- upsIta2com_599_Addr7Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_598_Addr7Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 600 }
- upsIta2com_600_Addr7Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_599_Addr7Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 601 }
- upsIta2com_601_Addr7Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_600_Addr7Batparallelchargehightemp status."
- ::= { upsIta2comEntry 602 }
- upsIta2com_602_Addr7BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_601_Addr7BatinternalCommabnormal status."
- ::= { upsIta2comEntry 603 }
- upsIta2com_603_Addr7Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_602_Addr7Batconditionfail status."
- ::= { upsIta2comEntry 604 }
- upsIta2com_604_Addr7BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_603_Addr7BatLowinsulationresistance status."
- ::= { upsIta2comEntry 605 }
- upsIta2com_605_Addr7BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_604_Addr7BatLargepressurediff status."
- ::= { upsIta2comEntry 606 }
- upsIta2com_606_Addr7BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_605_Addr7BatBatfailure status."
- ::= { upsIta2comEntry 607 }
- upsIta2com_607_Addr7BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_606_Addr7BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 608 }
- upsIta2com_608_Addr7BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_607_Addr7BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 609 }
- upsIta2com_609_Addr7BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_608_Addr7BatTempcolllectfailure status."
- ::= { upsIta2comEntry 610 }
- upsIta2com_610_Addr7BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_609_Addr7BatAddrSeterror status."
- ::= { upsIta2comEntry 611 }
- upsIta2com_611_Addr7BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_610_Addr7BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 612 }
- upsIta2com_612_Addr7BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_611_Addr7BatMOSFETfailure status."
- ::= { upsIta2comEntry 613 }
- upsIta2com_613_Addr7Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_612_Addr7Battempabnormal status."
- ::= { upsIta2comEntry 614 }
- upsIta2com_614_Addr7Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_613_Addr7Batcablefault status."
- ::= { upsIta2comEntry 615 }
- upsIta2com_615_Addr7BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_614_Addr7BatShortcircuit status."
- ::= { upsIta2comEntry 616 }
- upsIta2com_616_Addr7BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_615_Addr7BatOtherfailures status."
- ::= { upsIta2comEntry 617 }
- upsIta2com_617_Addr7BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_616_Addr7BatCommcablefailure status."
- ::= { upsIta2comEntry 618 }
- upsIta2com_618_Addr7BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_617_Addr7BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 619 }
- upsIta2com_619_Addr7BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_618_Addr7BatFuseblown status."
- ::= { upsIta2comEntry 620 }
- upsIta2com_620_Addr7BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_619_Addr7BatWaitingforcharging status."
- ::= { upsIta2comEntry 621 }
- upsIta2com_621_Addr7BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_620_Addr7BatBataging status."
- ::= { upsIta2comEntry 622 }
- upsIta2com_622_Addr7Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_621_Addr7Batboxconnectabnormal status."
- ::= { upsIta2comEntry 623 }
- upsIta2com_623_Addr7batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_622_Addr7batBatterySoftincompatible status."
- ::= { upsIta2comEntry 624 }
- upsIta2com_624_Addr7batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_623_Addr7batEOL status."
- ::= { upsIta2comEntry 625 }
- upsIta2com_625_Addr7batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_624_Addr7batSamplingfailure status."
- ::= { upsIta2comEntry 626 }
- upsIta2com_626_Addr7batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_625_Addr7batHardwareprotection status."
- ::= { upsIta2comEntry 627 }
- upsIta2com_627_Addr7batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_626_Addr7batBatterycapacitylow status."
- ::= { upsIta2comEntry 628 }
- upsIta2com_628_Addr8Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_627_Addr8Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 629 }
- upsIta2com_629_Addr8Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_628_Addr8Bathighvolt status."
- ::= { upsIta2comEntry 630 }
- upsIta2com_630_Addr8Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_629_Addr8Batlowvolt status."
- ::= { upsIta2comEntry 631 }
- upsIta2com_631_Addr8Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_630_Addr8Bathighcellvolt status."
- ::= { upsIta2comEntry 632 }
- upsIta2com_632_Addr8Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_631_Addr8Batlowcellvolt status."
- ::= { upsIta2comEntry 633 }
- upsIta2com_633_Addr8Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_632_Addr8Batchargehighcelltemp status."
- ::= { upsIta2comEntry 634 }
- upsIta2com_634_Addr8Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_633_Addr8Batchargelowcelltemp status."
- ::= { upsIta2comEntry 635 }
- upsIta2com_635_Addr8Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_634_Addr8Batchargeovercurrent status."
- ::= { upsIta2comEntry 636 }
- upsIta2com_636_Addr8Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_635_Addr8Batdischargeovercurrent status."
- ::= { upsIta2comEntry 637 }
- upsIta2com_637_Addr8BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_636_Addr8BatAddrconflict status."
- ::= { upsIta2comEntry 638 }
- upsIta2com_638_Addr8Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_637_Addr8Batportreverse status."
- ::= { upsIta2comEntry 639 }
- upsIta2com_639_Addr8BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_638_Addr8BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 640 }
- upsIta2com_640_Addr8Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_639_Addr8Batsafetyundervoltage status."
- ::= { upsIta2comEntry 641 }
- upsIta2com_641_Addr8Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_640_Addr8Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 642 }
- upsIta2com_642_Addr8Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_641_Addr8Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 643 }
- upsIta2com_643_Addr8Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_642_Addr8Batparallelchargehightemp status."
- ::= { upsIta2comEntry 644 }
- upsIta2com_644_Addr8BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_643_Addr8BatinternalCommabnormal status."
- ::= { upsIta2comEntry 645 }
- upsIta2com_645_Addr8Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_644_Addr8Batconditionfail status."
- ::= { upsIta2comEntry 646 }
- upsIta2com_646_Addr8BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_645_Addr8BatLowinsulationresistance status."
- ::= { upsIta2comEntry 647 }
- upsIta2com_647_Addr8BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_646_Addr8BatLargepressurediff status."
- ::= { upsIta2comEntry 648 }
- upsIta2com_648_Addr8BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_647_Addr8BatBatfailure status."
- ::= { upsIta2comEntry 649 }
- upsIta2com_649_Addr8BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_648_Addr8BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 650 }
- upsIta2com_650_Addr8BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_649_Addr8BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 651 }
- upsIta2com_651_Addr8BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_650_Addr8BatTempcolllectfailure status."
- ::= { upsIta2comEntry 652 }
- upsIta2com_652_Addr8BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_651_Addr8BatAddrSeterror status."
- ::= { upsIta2comEntry 653 }
- upsIta2com_653_Addr8BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_652_Addr8BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 654 }
- upsIta2com_654_Addr8BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_653_Addr8BatMOSFETfailure status."
- ::= { upsIta2comEntry 655 }
- upsIta2com_655_Addr8Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_654_Addr8Battempabnormal status."
- ::= { upsIta2comEntry 656 }
- upsIta2com_656_Addr8Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_655_Addr8Batcablefault status."
- ::= { upsIta2comEntry 657 }
- upsIta2com_657_Addr8BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_656_Addr8BatShortcircuit status."
- ::= { upsIta2comEntry 658 }
- upsIta2com_658_Addr8BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_657_Addr8BatOtherfailures status."
- ::= { upsIta2comEntry 659 }
- upsIta2com_659_Addr8BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_658_Addr8BatCommcablefailure status."
- ::= { upsIta2comEntry 660 }
- upsIta2com_660_Addr8BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_659_Addr8BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 661 }
- upsIta2com_661_Addr8BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_660_Addr8BatFuseblown status."
- ::= { upsIta2comEntry 662 }
- upsIta2com_662_Addr8BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_661_Addr8BatWaitingforcharging status."
- ::= { upsIta2comEntry 663 }
- upsIta2com_663_Addr8BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_662_Addr8BatBataging status."
- ::= { upsIta2comEntry 664 }
- upsIta2com_664_Addr8Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_663_Addr8Batboxconnectabnormal status."
- ::= { upsIta2comEntry 665 }
- upsIta2com_665_Addr8batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_664_Addr8batBatterySoftincompatible status."
- ::= { upsIta2comEntry 666 }
- upsIta2com_666_Addr8batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_665_Addr8batEOL status."
- ::= { upsIta2comEntry 667 }
- upsIta2com_667_Addr8batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_666_Addr8batSamplingfailure status."
- ::= { upsIta2comEntry 668 }
- upsIta2com_668_Addr8batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_667_Addr8batHardwareprotection status."
- ::= { upsIta2comEntry 669 }
- upsIta2com_669_Addr8batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_668_Addr8batBatterycapacitylow status."
- ::= { upsIta2comEntry 670 }
- upsIta2com_670_Addr9Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_669_Addr9Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 671 }
- upsIta2com_671_Addr9Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_670_Addr9Bathighvolt status."
- ::= { upsIta2comEntry 672 }
- upsIta2com_672_Addr9Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_671_Addr9Batlowvolt status."
- ::= { upsIta2comEntry 673 }
- upsIta2com_673_Addr9Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_672_Addr9Bathighcellvolt status."
- ::= { upsIta2comEntry 674 }
- upsIta2com_674_Addr9Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_673_Addr9Batlowcellvolt status."
- ::= { upsIta2comEntry 675 }
- upsIta2com_675_Addr9Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_674_Addr9Batchargehighcelltemp status."
- ::= { upsIta2comEntry 676 }
- upsIta2com_676_Addr9Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_675_Addr9Batchargelowcelltemp status."
- ::= { upsIta2comEntry 677 }
- upsIta2com_677_Addr9Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_676_Addr9Batchargeovercurrent status."
- ::= { upsIta2comEntry 678 }
- upsIta2com_678_Addr9Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_677_Addr9Batdischargeovercurrent status."
- ::= { upsIta2comEntry 679 }
- upsIta2com_679_Addr9BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_678_Addr9BatAddrconflict status."
- ::= { upsIta2comEntry 680 }
- upsIta2com_680_Addr9Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_679_Addr9Batportreverse status."
- ::= { upsIta2comEntry 681 }
- upsIta2com_681_Addr9BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_680_Addr9BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 682 }
- upsIta2com_682_Addr9Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_681_Addr9Batsafetyundervoltage status."
- ::= { upsIta2comEntry 683 }
- upsIta2com_683_Addr9Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_682_Addr9Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 684 }
- upsIta2com_684_Addr9Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_683_Addr9Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 685 }
- upsIta2com_685_Addr9Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_684_Addr9Batparallelchargehightemp status."
- ::= { upsIta2comEntry 686 }
- upsIta2com_686_Addr9BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_685_Addr9BatinternalCommabnormal status."
- ::= { upsIta2comEntry 687 }
- upsIta2com_687_Addr9Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_686_Addr9Batconditionfail status."
- ::= { upsIta2comEntry 688 }
- upsIta2com_688_Addr9BatLowinsulationresistance OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_687_Addr9BatLowinsulationresistance status."
- ::= { upsIta2comEntry 689 }
- upsIta2com_689_Addr9BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_688_Addr9BatLargepressurediff status."
- ::= { upsIta2comEntry 690 }
- upsIta2com_690_Addr9BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_689_Addr9BatBatfailure status."
- ::= { upsIta2comEntry 691 }
- upsIta2com_691_Addr9BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_690_Addr9BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 692 }
- upsIta2com_692_Addr9BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_691_Addr9BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 693 }
- upsIta2com_693_Addr9BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_692_Addr9BatTempcolllectfailure status."
- ::= { upsIta2comEntry 694 }
- upsIta2com_694_Addr9BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_693_Addr9BatAddrSeterror status."
- ::= { upsIta2comEntry 695 }
- upsIta2com_695_Addr9BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_694_Addr9BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 696 }
- upsIta2com_696_Addr9BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_695_Addr9BatMOSFETfailure status."
- ::= { upsIta2comEntry 697 }
- upsIta2com_697_Addr9Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_696_Addr9Battempabnormal status."
- ::= { upsIta2comEntry 698 }
- upsIta2com_698_Addr9Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_697_Addr9Batcablefault status."
- ::= { upsIta2comEntry 699 }
- upsIta2com_699_Addr9BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_698_Addr9BatShortcircuit status."
- ::= { upsIta2comEntry 700 }
- upsIta2com_700_Addr9BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_699_Addr9BatOtherfailures status."
- ::= { upsIta2comEntry 701 }
- upsIta2com_701_Addr9BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_700_Addr9BatCommcablefailure status."
- ::= { upsIta2comEntry 702 }
- upsIta2com_702_Addr9BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_701_Addr9BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 703 }
- upsIta2com_703_Addr9BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_702_Addr9BatFuseblown status."
- ::= { upsIta2comEntry 704 }
- upsIta2com_704_Addr9BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_703_Addr9BatWaitingforcharging status."
- ::= { upsIta2comEntry 705 }
- upsIta2com_705_Addr9BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_704_Addr9BatBataging status."
- ::= { upsIta2comEntry 706 }
- upsIta2com_706_Addr9Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_705_Addr9Batboxconnectabnormal status."
- ::= { upsIta2comEntry 707 }
- upsIta2com_707_Addr9batBatterySoftincompatible OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_706_Addr9batBatterySoftincompatible status."
- ::= { upsIta2comEntry 708 }
- upsIta2com_708_Addr9batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_707_Addr9batEOL status."
- ::= { upsIta2comEntry 709 }
- upsIta2com_709_Addr9batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_708_Addr9batSamplingfailure status."
- ::= { upsIta2comEntry 710 }
- upsIta2com_710_Addr9batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_709_Addr9batHardwareprotection status."
- ::= { upsIta2comEntry 711 }
- upsIta2com_711_Addr9batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_710_Addr9batBatterycapacitylow status."
- ::= { upsIta2comEntry 712 }
- upsIta2com_712_Addr10Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_711_Addr10Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 713 }
- upsIta2com_713_Addr10Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_712_Addr10Bathighvolt status."
- ::= { upsIta2comEntry 714 }
- upsIta2com_714_Addr10Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_713_Addr10Batlowvolt status."
- ::= { upsIta2comEntry 715 }
- upsIta2com_715_Addr10Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_714_Addr10Bathighcellvolt status."
- ::= { upsIta2comEntry 716 }
- upsIta2com_716_Addr10Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_715_Addr10Batlowcellvolt status."
- ::= { upsIta2comEntry 717 }
- upsIta2com_717_Addr10Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_716_Addr10Batchargehighcelltemp status."
- ::= { upsIta2comEntry 718 }
- upsIta2com_718_Addr10Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_717_Addr10Batchargelowcelltemp status."
- ::= { upsIta2comEntry 719 }
- upsIta2com_719_Addr10Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_718_Addr10Batchargeovercurrent status."
- ::= { upsIta2comEntry 720 }
- upsIta2com_720_Addr10Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_719_Addr10Batdischargeovercurrent status."
- ::= { upsIta2comEntry 721 }
- upsIta2com_721_Addr10BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_720_Addr10BatAddrconflict status."
- ::= { upsIta2comEntry 722 }
- upsIta2com_722_Addr10Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_721_Addr10Batportreverse status."
- ::= { upsIta2comEntry 723 }
- upsIta2com_723_Addr10BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_722_Addr10BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 724 }
- upsIta2com_724_Addr10Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_723_Addr10Batsafetyundervoltage status."
- ::= { upsIta2comEntry 725 }
- upsIta2com_725_Addr10Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_724_Addr10Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 726 }
- upsIta2com_726_Addr10Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_725_Addr10Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 727 }
- upsIta2com_727_Addr10Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_726_Addr10Batparallelchargehightemp status."
- ::= { upsIta2comEntry 728 }
- upsIta2com_728_Addr10BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_727_Addr10BatinternalCommabnormal status."
- ::= { upsIta2comEntry 729 }
- upsIta2com_729_Addr10Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_728_Addr10Batconditionfail status."
- ::= { upsIta2comEntry 730 }
- upsIta2com_730_Addr10BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_729_Addr10BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 731 }
- upsIta2com_731_Addr10BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_730_Addr10BatLargepressurediff status."
- ::= { upsIta2comEntry 732 }
- upsIta2com_732_Addr10BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_731_Addr10BatBatfailure status."
- ::= { upsIta2comEntry 733 }
- upsIta2com_733_Addr10BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_732_Addr10BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 734 }
- upsIta2com_734_Addr10BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_733_Addr10BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 735 }
- upsIta2com_735_Addr10BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_734_Addr10BatTempcolllectfailure status."
- ::= { upsIta2comEntry 736 }
- upsIta2com_736_Addr10BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_735_Addr10BatAddrSeterror status."
- ::= { upsIta2comEntry 737 }
- upsIta2com_737_Addr10BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_736_Addr10BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 738 }
- upsIta2com_738_Addr10BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_737_Addr10BatMOSFETfailure status."
- ::= { upsIta2comEntry 739 }
- upsIta2com_739_Addr10Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_738_Addr10Battempabnormal status."
- ::= { upsIta2comEntry 740 }
- upsIta2com_740_Addr10Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_739_Addr10Batcablefault status."
- ::= { upsIta2comEntry 741 }
- upsIta2com_741_Addr10BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_740_Addr10BatShortcircuit status."
- ::= { upsIta2comEntry 742 }
- upsIta2com_742_Addr10BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_741_Addr10BatOtherfailures status."
- ::= { upsIta2comEntry 743 }
- upsIta2com_743_Addr10BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_742_Addr10BatCommcablefailure status."
- ::= { upsIta2comEntry 744 }
- upsIta2com_744_Addr10BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_743_Addr10BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 745 }
- upsIta2com_745_Addr10BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_744_Addr10BatFuseblown status."
- ::= { upsIta2comEntry 746 }
- upsIta2com_746_Addr10BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_745_Addr10BatWaitingforcharging status."
- ::= { upsIta2comEntry 747 }
- upsIta2com_747_Addr10BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_746_Addr10BatBataging status."
- ::= { upsIta2comEntry 748 }
- upsIta2com_748_Addr10Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_747_Addr10Batboxconnectabnormal status."
- ::= { upsIta2comEntry 749 }
- upsIta2com_749_Addr10batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_748_Addr10batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 750 }
- upsIta2com_750_Addr10batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_749_Addr10batEOL status."
- ::= { upsIta2comEntry 751 }
- upsIta2com_751_Addr10batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_750_Addr10batSamplingfailure status."
- ::= { upsIta2comEntry 752 }
- upsIta2com_752_Addr10batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_751_Addr10batHardwareprotection status."
- ::= { upsIta2comEntry 753 }
- upsIta2com_753_Addr10batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_752_Addr10batBatterycapacitylow status."
- ::= { upsIta2comEntry 754 }
- upsIta2com_754_Addr11Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_753_Addr11Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 755 }
- upsIta2com_755_Addr11Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_754_Addr11Bathighvolt status."
- ::= { upsIta2comEntry 756 }
- upsIta2com_756_Addr11Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_755_Addr11Batlowvolt status."
- ::= { upsIta2comEntry 757 }
- upsIta2com_757_Addr11Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_756_Addr11Bathighcellvolt status."
- ::= { upsIta2comEntry 758 }
- upsIta2com_758_Addr11Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_757_Addr11Batlowcellvolt status."
- ::= { upsIta2comEntry 759 }
- upsIta2com_759_Addr11Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_758_Addr11Batchargehighcelltemp status."
- ::= { upsIta2comEntry 760 }
- upsIta2com_760_Addr11Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_759_Addr11Batchargelowcelltemp status."
- ::= { upsIta2comEntry 761 }
- upsIta2com_761_Addr11Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_760_Addr11Batchargeovercurrent status."
- ::= { upsIta2comEntry 762 }
- upsIta2com_762_Addr11Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_761_Addr11Batdischargeovercurrent status."
- ::= { upsIta2comEntry 763 }
- upsIta2com_763_Addr11BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_762_Addr11BatAddrconflict status."
- ::= { upsIta2comEntry 764 }
- upsIta2com_764_Addr11Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_763_Addr11Batportreverse status."
- ::= { upsIta2comEntry 765 }
- upsIta2com_765_Addr11BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_764_Addr11BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 766 }
- upsIta2com_766_Addr11Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_765_Addr11Batsafetyundervoltage status."
- ::= { upsIta2comEntry 767 }
- upsIta2com_767_Addr11Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_766_Addr11Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 768 }
- upsIta2com_768_Addr11Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_767_Addr11Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 769 }
- upsIta2com_769_Addr11Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_768_Addr11Batparallelchargehightemp status."
- ::= { upsIta2comEntry 770 }
- upsIta2com_770_Addr11BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_769_Addr11BatinternalCommabnormal status."
- ::= { upsIta2comEntry 771 }
- upsIta2com_771_Addr11Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_770_Addr11Batconditionfail status."
- ::= { upsIta2comEntry 772 }
- upsIta2com_772_Addr11BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_771_Addr11BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 773 }
- upsIta2com_773_Addr11BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_772_Addr11BatLargepressurediff status."
- ::= { upsIta2comEntry 774 }
- upsIta2com_774_Addr11BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_773_Addr11BatBatfailure status."
- ::= { upsIta2comEntry 775 }
- upsIta2com_775_Addr11BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_774_Addr11BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 776 }
- upsIta2com_776_Addr11BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_775_Addr11BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 777 }
- upsIta2com_777_Addr11BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_776_Addr11BatTempcolllectfailure status."
- ::= { upsIta2comEntry 778 }
- upsIta2com_778_Addr11BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_777_Addr11BatAddrSeterror status."
- ::= { upsIta2comEntry 779 }
- upsIta2com_779_Addr11BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_778_Addr11BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 780 }
- upsIta2com_780_Addr11BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_779_Addr11BatMOSFETfailure status."
- ::= { upsIta2comEntry 781 }
- upsIta2com_781_Addr11Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_780_Addr11Battempabnormal status."
- ::= { upsIta2comEntry 782 }
- upsIta2com_782_Addr11Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_781_Addr11Batcablefault status."
- ::= { upsIta2comEntry 783 }
- upsIta2com_783_Addr11BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_782_Addr11BatShortcircuit status."
- ::= { upsIta2comEntry 784 }
- upsIta2com_784_Addr11BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_783_Addr11BatOtherfailures status."
- ::= { upsIta2comEntry 785 }
- upsIta2com_785_Addr11BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_784_Addr11BatCommcablefailure status."
- ::= { upsIta2comEntry 786 }
- upsIta2com_786_Addr11BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_785_Addr11BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 787 }
- upsIta2com_787_Addr11BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_786_Addr11BatFuseblown status."
- ::= { upsIta2comEntry 788 }
- upsIta2com_788_Addr11BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_787_Addr11BatWaitingforcharging status."
- ::= { upsIta2comEntry 789 }
- upsIta2com_789_Addr11BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_788_Addr11BatBataging status."
- ::= { upsIta2comEntry 790 }
- upsIta2com_790_Addr11Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_789_Addr11Batboxconnectabnormal status."
- ::= { upsIta2comEntry 791 }
- upsIta2com_791_Addr11batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_790_Addr11batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 792 }
- upsIta2com_792_Addr11batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_791_Addr11batEOL status."
- ::= { upsIta2comEntry 793 }
- upsIta2com_793_Addr11batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_792_Addr11batSamplingfailure status."
- ::= { upsIta2comEntry 794 }
- upsIta2com_794_Addr11batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_793_Addr11batHardwareprotection status."
- ::= { upsIta2comEntry 795 }
- upsIta2com_795_Addr11batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_794_Addr11batBatterycapacitylow status."
- ::= { upsIta2comEntry 796 }
- upsIta2com_796_Addr12Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_795_Addr12Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 797 }
- upsIta2com_797_Addr12Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_796_Addr12Bathighvolt status."
- ::= { upsIta2comEntry 798 }
- upsIta2com_798_Addr12Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_797_Addr12Batlowvolt status."
- ::= { upsIta2comEntry 799 }
- upsIta2com_799_Addr12Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_798_Addr12Bathighcellvolt status."
- ::= { upsIta2comEntry 800 }
- upsIta2com_800_Addr12Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_799_Addr12Batlowcellvolt status."
- ::= { upsIta2comEntry 801 }
- upsIta2com_801_Addr12Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_800_Addr12Batchargehighcelltemp status."
- ::= { upsIta2comEntry 802 }
- upsIta2com_802_Addr12Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_801_Addr12Batchargelowcelltemp status."
- ::= { upsIta2comEntry 803 }
- upsIta2com_803_Addr12Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_802_Addr12Batchargeovercurrent status."
- ::= { upsIta2comEntry 804 }
- upsIta2com_804_Addr12Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_803_Addr12Batdischargeovercurrent status."
- ::= { upsIta2comEntry 805 }
- upsIta2com_805_Addr12BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_804_Addr12BatAddrconflict status."
- ::= { upsIta2comEntry 806 }
- upsIta2com_806_Addr12Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_805_Addr12Batportreverse status."
- ::= { upsIta2comEntry 807 }
- upsIta2com_807_Addr12BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_806_Addr12BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 808 }
- upsIta2com_808_Addr12Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_807_Addr12Batsafetyundervoltage status."
- ::= { upsIta2comEntry 809 }
- upsIta2com_809_Addr12Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_808_Addr12Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 810 }
- upsIta2com_810_Addr12Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_809_Addr12Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 811 }
- upsIta2com_811_Addr12Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_810_Addr12Batparallelchargehightemp status."
- ::= { upsIta2comEntry 812 }
- upsIta2com_812_Addr12BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_811_Addr12BatinternalCommabnormal status."
- ::= { upsIta2comEntry 813 }
- upsIta2com_813_Addr12Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_812_Addr12Batconditionfail status."
- ::= { upsIta2comEntry 814 }
- upsIta2com_814_Addr12BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_813_Addr12BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 815 }
- upsIta2com_815_Addr12BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_814_Addr12BatLargepressurediff status."
- ::= { upsIta2comEntry 816 }
- upsIta2com_816_Addr12BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_815_Addr12BatBatfailure status."
- ::= { upsIta2comEntry 817 }
- upsIta2com_817_Addr12BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_816_Addr12BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 818 }
- upsIta2com_818_Addr12BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_817_Addr12BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 819 }
- upsIta2com_819_Addr12BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_818_Addr12BatTempcolllectfailure status."
- ::= { upsIta2comEntry 820 }
- upsIta2com_820_Addr12BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_819_Addr12BatAddrSeterror status."
- ::= { upsIta2comEntry 821 }
- upsIta2com_821_Addr12BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_820_Addr12BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 822 }
- upsIta2com_822_Addr12BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_821_Addr12BatMOSFETfailure status."
- ::= { upsIta2comEntry 823 }
- upsIta2com_823_Addr12Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_822_Addr12Battempabnormal status."
- ::= { upsIta2comEntry 824 }
- upsIta2com_824_Addr12Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_823_Addr12Batcablefault status."
- ::= { upsIta2comEntry 825 }
- upsIta2com_825_Addr12BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_824_Addr12BatShortcircuit status."
- ::= { upsIta2comEntry 826 }
- upsIta2com_826_Addr12BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_825_Addr12BatOtherfailures status."
- ::= { upsIta2comEntry 827 }
- upsIta2com_827_Addr12BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_826_Addr12BatCommcablefailure status."
- ::= { upsIta2comEntry 828 }
- upsIta2com_828_Addr12BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_827_Addr12BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 829 }
- upsIta2com_829_Addr12BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_828_Addr12BatFuseblown status."
- ::= { upsIta2comEntry 830 }
- upsIta2com_830_Addr12BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_829_Addr12BatWaitingforcharging status."
- ::= { upsIta2comEntry 831 }
- upsIta2com_831_Addr12BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_830_Addr12BatBataging status."
- ::= { upsIta2comEntry 832 }
- upsIta2com_832_Addr12Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_831_Addr12Batboxconnectabnormal status."
- ::= { upsIta2comEntry 833 }
- upsIta2com_833_Addr12batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_832_Addr12batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 834 }
- upsIta2com_834_Addr12batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_833_Addr12batEOL status."
- ::= { upsIta2comEntry 835 }
- upsIta2com_835_Addr12batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_834_Addr12batSamplingfailure status."
- ::= { upsIta2comEntry 836 }
- upsIta2com_836_Addr12batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_835_Addr12batHardwareprotection status."
- ::= { upsIta2comEntry 837 }
- upsIta2com_837_Addr12batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_836_Addr12batBatterycapacitylow status."
- ::= { upsIta2comEntry 838 }
- upsIta2com_838_Addr13Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_837_Addr13Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 839 }
- upsIta2com_839_Addr13Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_838_Addr13Bathighvolt status."
- ::= { upsIta2comEntry 840 }
- upsIta2com_840_Addr13Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_839_Addr13Batlowvolt status."
- ::= { upsIta2comEntry 841 }
- upsIta2com_841_Addr13Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_840_Addr13Bathighcellvolt status."
- ::= { upsIta2comEntry 842 }
- upsIta2com_842_Addr13Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_841_Addr13Batlowcellvolt status."
- ::= { upsIta2comEntry 843 }
- upsIta2com_843_Addr13Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_842_Addr13Batchargehighcelltemp status."
- ::= { upsIta2comEntry 844 }
- upsIta2com_844_Addr13Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_843_Addr13Batchargelowcelltemp status."
- ::= { upsIta2comEntry 845 }
- upsIta2com_845_Addr13Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_844_Addr13Batchargeovercurrent status."
- ::= { upsIta2comEntry 846 }
- upsIta2com_846_Addr13Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_845_Addr13Batdischargeovercurrent status."
- ::= { upsIta2comEntry 847 }
- upsIta2com_847_Addr13BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_846_Addr13BatAddrconflict status."
- ::= { upsIta2comEntry 848 }
- upsIta2com_848_Addr13Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_847_Addr13Batportreverse status."
- ::= { upsIta2comEntry 849 }
- upsIta2com_849_Addr13BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_848_Addr13BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 850 }
- upsIta2com_850_Addr13Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_849_Addr13Batsafetyundervoltage status."
- ::= { upsIta2comEntry 851 }
- upsIta2com_851_Addr13Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_850_Addr13Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 852 }
- upsIta2com_852_Addr13Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_851_Addr13Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 853 }
- upsIta2com_853_Addr13Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_852_Addr13Batparallelchargehightemp status."
- ::= { upsIta2comEntry 854 }
- upsIta2com_854_Addr13BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_853_Addr13BatinternalCommabnormal status."
- ::= { upsIta2comEntry 855 }
- upsIta2com_855_Addr13Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_854_Addr13Batconditionfail status."
- ::= { upsIta2comEntry 856 }
- upsIta2com_856_Addr13BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_855_Addr13BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 857 }
- upsIta2com_857_Addr13BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_856_Addr13BatLargepressurediff status."
- ::= { upsIta2comEntry 858 }
- upsIta2com_858_Addr13BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_857_Addr13BatBatfailure status."
- ::= { upsIta2comEntry 859 }
- upsIta2com_859_Addr13BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_858_Addr13BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 860 }
- upsIta2com_860_Addr13BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_859_Addr13BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 861 }
- upsIta2com_861_Addr13BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_860_Addr13BatTempcolllectfailure status."
- ::= { upsIta2comEntry 862 }
- upsIta2com_862_Addr13BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_861_Addr13BatAddrSeterror status."
- ::= { upsIta2comEntry 863 }
- upsIta2com_863_Addr13BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_862_Addr13BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 864 }
- upsIta2com_864_Addr13BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_863_Addr13BatMOSFETfailure status."
- ::= { upsIta2comEntry 865 }
- upsIta2com_865_Addr13Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_864_Addr13Battempabnormal status."
- ::= { upsIta2comEntry 866 }
- upsIta2com_866_Addr13Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_865_Addr13Batcablefault status."
- ::= { upsIta2comEntry 867 }
- upsIta2com_867_Addr13BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_866_Addr13BatShortcircuit status."
- ::= { upsIta2comEntry 868 }
- upsIta2com_868_Addr13BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_867_Addr13BatOtherfailures status."
- ::= { upsIta2comEntry 869 }
- upsIta2com_869_Addr13BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_868_Addr13BatCommcablefailure status."
- ::= { upsIta2comEntry 870 }
- upsIta2com_870_Addr13BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_869_Addr13BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 871 }
- upsIta2com_871_Addr13BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_870_Addr13BatFuseblown status."
- ::= { upsIta2comEntry 872 }
- upsIta2com_872_Addr13BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_871_Addr13BatWaitingforcharging status."
- ::= { upsIta2comEntry 873 }
- upsIta2com_873_Addr13BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_872_Addr13BatBataging status."
- ::= { upsIta2comEntry 874 }
- upsIta2com_874_Addr13Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_873_Addr13Batboxconnectabnormal status."
- ::= { upsIta2comEntry 875 }
- upsIta2com_875_Addr13batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_874_Addr13batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 876 }
- upsIta2com_876_Addr13batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_875_Addr13batEOL status."
- ::= { upsIta2comEntry 877 }
- upsIta2com_877_Addr13batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_876_Addr13batSamplingfailure status."
- ::= { upsIta2comEntry 878 }
- upsIta2com_878_Addr13batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_877_Addr13batHardwareprotection status."
- ::= { upsIta2comEntry 879 }
- upsIta2com_879_Addr13batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_878_Addr13batBatterycapacitylow status."
- ::= { upsIta2comEntry 880 }
- upsIta2com_880_Addr14Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_879_Addr14Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 881 }
- upsIta2com_881_Addr14Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_880_Addr14Bathighvolt status."
- ::= { upsIta2comEntry 882 }
- upsIta2com_882_Addr14Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_881_Addr14Batlowvolt status."
- ::= { upsIta2comEntry 883 }
- upsIta2com_883_Addr14Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_882_Addr14Bathighcellvolt status."
- ::= { upsIta2comEntry 884 }
- upsIta2com_884_Addr14Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_883_Addr14Batlowcellvolt status."
- ::= { upsIta2comEntry 885 }
- upsIta2com_885_Addr14Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_884_Addr14Batchargehighcelltemp status."
- ::= { upsIta2comEntry 886 }
- upsIta2com_886_Addr14Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_885_Addr14Batchargelowcelltemp status."
- ::= { upsIta2comEntry 887 }
- upsIta2com_887_Addr14Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_886_Addr14Batchargeovercurrent status."
- ::= { upsIta2comEntry 888 }
- upsIta2com_888_Addr14Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_887_Addr14Batdischargeovercurrent status."
- ::= { upsIta2comEntry 889 }
- upsIta2com_889_Addr14BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_888_Addr14BatAddrconflict status."
- ::= { upsIta2comEntry 890 }
- upsIta2com_890_Addr14Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_889_Addr14Batportreverse status."
- ::= { upsIta2comEntry 891 }
- upsIta2com_891_Addr14BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_890_Addr14BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 892 }
- upsIta2com_892_Addr14Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_891_Addr14Batsafetyundervoltage status."
- ::= { upsIta2comEntry 893 }
- upsIta2com_893_Addr14Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_892_Addr14Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 894 }
- upsIta2com_894_Addr14Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_893_Addr14Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 895 }
- upsIta2com_895_Addr14Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_894_Addr14Batparallelchargehightemp status."
- ::= { upsIta2comEntry 896 }
- upsIta2com_896_Addr14BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_895_Addr14BatinternalCommabnormal status."
- ::= { upsIta2comEntry 897 }
- upsIta2com_897_Addr14Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_896_Addr14Batconditionfail status."
- ::= { upsIta2comEntry 898 }
- upsIta2com_898_Addr14BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_897_Addr14BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 899 }
- upsIta2com_899_Addr14BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_898_Addr14BatLargepressurediff status."
- ::= { upsIta2comEntry 900 }
- upsIta2com_900_Addr14BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_899_Addr14BatBatfailure status."
- ::= { upsIta2comEntry 901 }
- upsIta2com_901_Addr14BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_900_Addr14BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 902 }
- upsIta2com_902_Addr14BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_901_Addr14BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 903 }
- upsIta2com_903_Addr14BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_902_Addr14BatTempcolllectfailure status."
- ::= { upsIta2comEntry 904 }
- upsIta2com_904_Addr14BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_903_Addr14BatAddrSeterror status."
- ::= { upsIta2comEntry 905 }
- upsIta2com_905_Addr14BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_904_Addr14BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 906 }
- upsIta2com_906_Addr14BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_905_Addr14BatMOSFETfailure status."
- ::= { upsIta2comEntry 907 }
- upsIta2com_907_Addr14Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_906_Addr14Battempabnormal status."
- ::= { upsIta2comEntry 908 }
- upsIta2com_908_Addr14Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_907_Addr14Batcablefault status."
- ::= { upsIta2comEntry 909 }
- upsIta2com_909_Addr14BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_908_Addr14BatShortcircuit status."
- ::= { upsIta2comEntry 910 }
- upsIta2com_910_Addr14BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_909_Addr14BatOtherfailures status."
- ::= { upsIta2comEntry 911 }
- upsIta2com_911_Addr14BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_910_Addr14BatCommcablefailure status."
- ::= { upsIta2comEntry 912 }
- upsIta2com_912_Addr14BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_911_Addr14BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 913 }
- upsIta2com_913_Addr14BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_912_Addr14BatFuseblown status."
- ::= { upsIta2comEntry 914 }
- upsIta2com_914_Addr14BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_913_Addr14BatWaitingforcharging status."
- ::= { upsIta2comEntry 915 }
- upsIta2com_915_Addr14BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_914_Addr14BatBataging status."
- ::= { upsIta2comEntry 916 }
- upsIta2com_916_Addr14Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_915_Addr14Batboxconnectabnormal status."
- ::= { upsIta2comEntry 917 }
- upsIta2com_917_Addr14batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_916_Addr14batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 918 }
- upsIta2com_918_Addr14batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_917_Addr14batEOL status."
- ::= { upsIta2comEntry 919 }
- upsIta2com_919_Addr14batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_918_Addr14batSamplingfailure status."
- ::= { upsIta2comEntry 920 }
- upsIta2com_920_Addr14batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_919_Addr14batHardwareprotection status."
- ::= { upsIta2comEntry 921 }
- upsIta2com_921_Addr14batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_920_Addr14batBatterycapacitylow status."
- ::= { upsIta2comEntry 922 }
- upsIta2com_922_Addr15Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_921_Addr15Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 923 }
- upsIta2com_923_Addr15Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_922_Addr15Bathighvolt status."
- ::= { upsIta2comEntry 924 }
- upsIta2com_924_Addr15Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_923_Addr15Batlowvolt status."
- ::= { upsIta2comEntry 925 }
- upsIta2com_925_Addr15Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_924_Addr15Bathighcellvolt status."
- ::= { upsIta2comEntry 926 }
- upsIta2com_926_Addr15Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_925_Addr15Batlowcellvolt status."
- ::= { upsIta2comEntry 927 }
- upsIta2com_927_Addr15Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_926_Addr15Batchargehighcelltemp status."
- ::= { upsIta2comEntry 928 }
- upsIta2com_928_Addr15Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_927_Addr15Batchargelowcelltemp status."
- ::= { upsIta2comEntry 929 }
- upsIta2com_929_Addr15Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_928_Addr15Batchargeovercurrent status."
- ::= { upsIta2comEntry 930 }
- upsIta2com_930_Addr15Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_929_Addr15Batdischargeovercurrent status."
- ::= { upsIta2comEntry 931 }
- upsIta2com_931_Addr15BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_930_Addr15BatAddrconflict status."
- ::= { upsIta2comEntry 932 }
- upsIta2com_932_Addr15Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_931_Addr15Batportreverse status."
- ::= { upsIta2comEntry 933 }
- upsIta2com_933_Addr15BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_932_Addr15BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 934 }
- upsIta2com_934_Addr15Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_933_Addr15Batsafetyundervoltage status."
- ::= { upsIta2comEntry 935 }
- upsIta2com_935_Addr15Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_934_Addr15Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 936 }
- upsIta2com_936_Addr15Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_935_Addr15Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 937 }
- upsIta2com_937_Addr15Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_936_Addr15Batparallelchargehightemp status."
- ::= { upsIta2comEntry 938 }
- upsIta2com_938_Addr15BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_937_Addr15BatinternalCommabnormal status."
- ::= { upsIta2comEntry 939 }
- upsIta2com_939_Addr15Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_938_Addr15Batconditionfail status."
- ::= { upsIta2comEntry 940 }
- upsIta2com_940_Addr15BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_939_Addr15BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 941 }
- upsIta2com_941_Addr15BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_940_Addr15BatLargepressurediff status."
- ::= { upsIta2comEntry 942 }
- upsIta2com_942_Addr15BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_941_Addr15BatBatfailure status."
- ::= { upsIta2comEntry 943 }
- upsIta2com_943_Addr15BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_942_Addr15BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 944 }
- upsIta2com_944_Addr15BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_943_Addr15BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 945 }
- upsIta2com_945_Addr15BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_944_Addr15BatTempcolllectfailure status."
- ::= { upsIta2comEntry 946 }
- upsIta2com_946_Addr15BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_945_Addr15BatAddrSeterror status."
- ::= { upsIta2comEntry 947 }
- upsIta2com_947_Addr15BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_946_Addr15BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 948 }
- upsIta2com_948_Addr15BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_947_Addr15BatMOSFETfailure status."
- ::= { upsIta2comEntry 949 }
- upsIta2com_949_Addr15Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_948_Addr15Battempabnormal status."
- ::= { upsIta2comEntry 950 }
- upsIta2com_950_Addr15Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_949_Addr15Batcablefault status."
- ::= { upsIta2comEntry 951 }
- upsIta2com_951_Addr15BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_950_Addr15BatShortcircuit status."
- ::= { upsIta2comEntry 952 }
- upsIta2com_952_Addr15BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_951_Addr15BatOtherfailures status."
- ::= { upsIta2comEntry 953 }
- upsIta2com_953_Addr15BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_952_Addr15BatCommcablefailure status."
- ::= { upsIta2comEntry 954 }
- upsIta2com_954_Addr15BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_953_Addr15BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 955 }
- upsIta2com_955_Addr15BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_954_Addr15BatFuseblown status."
- ::= { upsIta2comEntry 956 }
- upsIta2com_956_Addr15BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_955_Addr15BatWaitingforcharging status."
- ::= { upsIta2comEntry 957 }
- upsIta2com_957_Addr15BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_956_Addr15BatBataging status."
- ::= { upsIta2comEntry 958 }
- upsIta2com_958_Addr15Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_957_Addr15Batboxconnectabnormal status."
- ::= { upsIta2comEntry 959 }
- upsIta2com_959_Addr15batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_958_Addr15batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 960 }
- upsIta2com_960_Addr15batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_959_Addr15batEOL status."
- ::= { upsIta2comEntry 961 }
- upsIta2com_961_Addr15batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_960_Addr15batSamplingfailure status."
- ::= { upsIta2comEntry 962 }
- upsIta2com_962_Addr15batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_961_Addr15batHardwareprotection status."
- ::= { upsIta2comEntry 963 }
- upsIta2com_963_Addr15batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_962_Addr15batBatterycapacitylow status."
- ::= { upsIta2comEntry 964 }
- upsIta2com_964_Addr16Batalarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_963_Addr16Batalarmnumber stored as 1."
- ::= { upsIta2comEntry 965 }
- upsIta2com_965_Addr16Bathighvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_964_Addr16Bathighvolt status."
- ::= { upsIta2comEntry 966 }
- upsIta2com_966_Addr16Batlowvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_965_Addr16Batlowvolt status."
- ::= { upsIta2comEntry 967 }
- upsIta2com_967_Addr16Bathighcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_966_Addr16Bathighcellvolt status."
- ::= { upsIta2comEntry 968 }
- upsIta2com_968_Addr16Batlowcellvolt OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_967_Addr16Batlowcellvolt status."
- ::= { upsIta2comEntry 969 }
- upsIta2com_969_Addr16Batchargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_968_Addr16Batchargehighcelltemp status."
- ::= { upsIta2comEntry 970 }
- upsIta2com_970_Addr16Batchargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_969_Addr16Batchargelowcelltemp status."
- ::= { upsIta2comEntry 971 }
- upsIta2com_971_Addr16Batchargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_970_Addr16Batchargeovercurrent status."
- ::= { upsIta2comEntry 972 }
- upsIta2com_972_Addr16Batdischargeovercurrent OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_971_Addr16Batdischargeovercurrent status."
- ::= { upsIta2comEntry 973 }
- upsIta2com_973_Addr16BatAddrconflict OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_972_Addr16BatAddrconflict status."
- ::= { upsIta2comEntry 974 }
- upsIta2com_974_Addr16Batportreverse OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_973_Addr16Batportreverse status."
- ::= { upsIta2comEntry 975 }
- upsIta2com_975_Addr16BatBMSrelayinvalid OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_974_Addr16BatBMSrelayinvalid status."
- ::= { upsIta2comEntry 976 }
- upsIta2com_976_Addr16Batsafetyundervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_975_Addr16Batsafetyundervoltage status."
- ::= { upsIta2comEntry 977 }
- upsIta2com_977_Addr16Batdischargehighcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_976_Addr16Batdischargehighcelltemp status."
- ::= { upsIta2comEntry 978 }
- upsIta2com_978_Addr16Batdischargelowcelltemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_977_Addr16Batdischargelowcelltemp status."
- ::= { upsIta2comEntry 979 }
- upsIta2com_979_Addr16Batparallelchargehightemp OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_978_Addr16Batparallelchargehightemp status."
- ::= { upsIta2comEntry 980 }
- upsIta2com_980_Addr16BatinternalCommabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_979_Addr16BatinternalCommabnormal status."
- ::= { upsIta2comEntry 981 }
- upsIta2com_981_Addr16Batconditionfail OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_980_Addr16Batconditionfail status."
- ::= { upsIta2comEntry 982 }
- upsIta2com_982_Addr16BatLowinsulationresistanc OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_981_Addr16BatLowinsulationresistanc status."
- ::= { upsIta2comEntry 983 }
- upsIta2com_983_Addr16BatLargepressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_982_Addr16BatLargepressurediff status."
- ::= { upsIta2comEntry 984 }
- upsIta2com_984_Addr16BatBatfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_983_Addr16BatBatfailure status."
- ::= { upsIta2comEntry 985 }
- upsIta2com_985_Addr16BatVoltageacquisitfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_984_Addr16BatVoltageacquisitfailure status."
- ::= { upsIta2comEntry 986 }
- upsIta2com_986_Addr16BatCurrentcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_985_Addr16BatCurrentcolllectfailure status."
- ::= { upsIta2comEntry 987 }
- upsIta2com_987_Addr16BatTempcolllectfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_986_Addr16BatTempcolllectfailure status."
- ::= { upsIta2comEntry 988 }
- upsIta2com_988_Addr16BatAddrSeterror OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_987_Addr16BatAddrSeterror status."
- ::= { upsIta2comEntry 989 }
- upsIta2com_989_Addr16BatLargegrouppressurediff OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_988_Addr16BatLargegrouppressurediff status."
- ::= { upsIta2comEntry 990 }
- upsIta2com_990_Addr16BatMOSFETfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_989_Addr16BatMOSFETfailure status."
- ::= { upsIta2comEntry 991 }
- upsIta2com_991_Addr16Battempabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_990_Addr16Battempabnormal status."
- ::= { upsIta2comEntry 992 }
- upsIta2com_992_Addr16Batcablefault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_991_Addr16Batcablefault status."
- ::= { upsIta2comEntry 993 }
- upsIta2com_993_Addr16BatShortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_992_Addr16BatShortcircuit status."
- ::= { upsIta2comEntry 994 }
- upsIta2com_994_Addr16BatOtherfailures OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_993_Addr16BatOtherfailures status."
- ::= { upsIta2comEntry 995 }
- upsIta2com_995_Addr16BatCommcablefailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_994_Addr16BatCommcablefailure status."
- ::= { upsIta2comEntry 996 }
- upsIta2com_996_Addr16BatMOSFETtempishigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_995_Addr16BatMOSFETtempishigh status."
- ::= { upsIta2comEntry 997 }
- upsIta2com_997_Addr16BatFuseblown OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_996_Addr16BatFuseblown status."
- ::= { upsIta2comEntry 998 }
- upsIta2com_998_Addr16BatWaitingforcharging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_997_Addr16BatWaitingforcharging status."
- ::= { upsIta2comEntry 999 }
- upsIta2com_999_Addr16BatBataging OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_998_Addr16BatBataging status."
- ::= { upsIta2comEntry 1000 }
- upsIta2com_1000_Addr16Batboxconnectabnormal OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_999_Addr16Batboxconnectabnormal status."
- ::= { upsIta2comEntry 1001 }
- upsIta2com_1001_Addr16batBatterySoftincompatibl OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1000_Addr16batBatterySoftincompatibl status."
- ::= { upsIta2comEntry 1002 }
- upsIta2com_1002_Addr16batEOL OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1001_Addr16batEOL status."
- ::= { upsIta2comEntry 1003 }
- upsIta2com_1003_Addr16batSamplingfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1002_Addr16batSamplingfailure status."
- ::= { upsIta2comEntry 1004 }
- upsIta2com_1004_Addr16batHardwareprotection OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1003_Addr16batHardwareprotection status."
- ::= { upsIta2comEntry 1005 }
- upsIta2com_1005_Addr16batBatterycapacitylow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1004_Addr16batBatterycapacitylow status."
- ::= { upsIta2comEntry 1006 }
- upsIta2com_1006_Addr1Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1005_Addr1Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1007 }
- upsIta2com_1007_Addr2Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1006_Addr2Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1008 }
- upsIta2com_1008_Addr3Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1007_Addr3Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1009 }
- upsIta2com_1009_Addr4Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1008_Addr4Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1010 }
- upsIta2com_1010_Addr5Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1009_Addr5Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1011 }
- upsIta2com_1011_Addr6Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1010_Addr6Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1012 }
- upsIta2com_1012_Addr7Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1011_Addr7Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1013 }
- upsIta2com_1013_Addr8Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1012_Addr8Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1014 }
- upsIta2com_1014_Addr9Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1013_Addr9Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1015 }
- upsIta2com_1015_Addr10Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1014_Addr10Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1016 }
- upsIta2com_1016_Addr11Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1015_Addr11Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1017 }
- upsIta2com_1017_Addr12Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1016_Addr12Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1018 }
- upsIta2com_1018_Addr13Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1017_Addr13Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1019 }
- upsIta2com_1019_Addr14Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1018_Addr14Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1020 }
- upsIta2com_1020_Addr15Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1019_Addr15Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1021 }
- upsIta2com_1021_Addr16Batcuralarmnumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1020_Addr16Batcuralarmnumber stored as 1."
- ::= { upsIta2comEntry 1022 }
- upsIta2com_1022_StanderBatteryStatus OBJECT-TYPE
- SYNTAX INTEGER {
- nondischargeandrecharge(0),
- floatcharging(1),
- equalizationcharging(2),
- discharging(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1021_StanderBatteryStatus status."
- ::= { upsIta2comEntry 1023 }
- upsIta2com_1023_Commtatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "upsIta2com_1022_Commtatus status."
- ::= { upsIta2comEntry 1024 }
- upsIta2com_1024_RemoteBatSelftest OBJECT-TYPE
- SYNTAX INTEGER {
- start(0),
- end(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1023_RemoteBatSelftest status."
- ::= { upsIta2comEntry 1025 }
- upsIta2com_1025_BatSelfTestCommand OBJECT-TYPE
- SYNTAX INTEGER {
- start(0),
- end(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1024_BatSelfTestCommand status."
- ::= { upsIta2comEntry 1026 }
- upsIta2com_1026_TurnOffUpsOutput OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1025_TurnOffUpsOutput status."
- ::= { upsIta2comEntry 1027 }
- upsIta2com_1027_TurnOnUpsInstantly OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1026_TurnOnUpsInstantly status."
- ::= { upsIta2comEntry 1028 }
- upsIta2com_1028_TurnOffUpsInstantly OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1027_TurnOffUpsInstantly status."
- ::= { upsIta2comEntry 1029 }
- upsIta2com_1029_SetTime OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1028_SetTime status."
- ::= { upsIta2comEntry 1030 }
- upsIta2com_1030_OpenInverterWithDelay OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1029_OpenInverterWithDelay status."
- ::= { upsIta2comEntry 1031 }
- upsIta2com_1031_CloseOutputWithDelay OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1030_CloseOutputWithDelay status."
- ::= { upsIta2comEntry 1032 }
- upsIta2com_1032_DelayedShutdownCancellation OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1031_DelayedShutdownCancellation status."
- ::= { upsIta2comEntry 1033 }
- upsIta2com_1033_ForcedtowakeuplithiumBat OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1032_ForcedtowakeuplithiumBat status."
- ::= { upsIta2comEntry 1034 }
- upsIta2com_1034_DelayTimeOfSelfStart OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1033_DelayTimeOfSelfStart stored as 1s."
- ::= { upsIta2comEntry 1035 }
- upsIta2com_1035_DelayTimeOfRemoteShutDown OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1034_DelayTimeOfRemoteShutDown stored as 1s."
- ::= { upsIta2comEntry 1036 }
- upsIta2com_1036_IntervalOfBatSelfTest OBJECT-TYPE
- SYNTAX INTEGER {
- forbidden(0),
- 8weeks(1),
- 12weeks(2),
- 16weeks(3),
- 20weeks(4),
- 26weeks(5) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1035_IntervalOfBatSelfTest status."
- ::= { upsIta2comEntry 1037 }
- upsIta2com_1037_UpsWorkingMode OBJECT-TYPE
- SYNTAX INTEGER {
- normalmode(0),
- ecomode(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1036_UpsWorkingMode status."
- ::= { upsIta2comEntry 1038 }
- upsIta2com_1038_SelfStartSet OBJECT-TYPE
- SYNTAX INTEGER {
- forbidden(0),
- allow(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1037_SelfStartSet status."
- ::= { upsIta2comEntry 1039 }
- upsIta2com_1039_SetsRedundance OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1038_SetsRedundance status."
- ::= { upsIta2comEntry 1040 }
- upsIta2com_1040_RemoteOpenDelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1039_RemoteOpenDelayTime stored as 1s."
- ::= { upsIta2comEntry 1041 }
- upsIta2com_1041_LogNumberSet OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "upsIta2com_1040_LogNumberSet stored as 1."
- ::= { upsIta2comEntry 1042 }
- ------------------------------------------------------------
- -- Mpdu { 13400.3.2 }
- ------------------------------------------------------------
- pdu OBJECT IDENTIFIER ::= { dcs 2 }
- ------------------------------------------------------------
- -- Mpscom { 13400.3.2.225 }
- ------------------------------------------------------------
- mpdu-Mpscom OBJECT IDENTIFIER ::= { pdu 225 }
- mpduMpscomTable OBJECT-TYPE
- SYNTAX SEQUENCE OF MpduMpscomEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "mpduMpscomTable"
- ::= { mpdu-Mpscom 1 }
- mpduMpscomEntry OBJECT-TYPE
- SYNTAX MpduMpscomEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "mpduMpscomEntry"
- INDEX { mpduMpscomIndex }
- ::= { mpduMpscomTable 1 }
- MpduMpscomEntry ::= SEQUENCE {
- mpduMpscomIndex Integer32,
- mpduMpscom_2_ProductType INTEGER,
- mpduMpscom_3_Voltage Integer32,
- mpduMpscom_4_TotalCurrent Integer32,
- mpduMpscom_5_Branch1Current Integer32,
- mpduMpscom_6_Branch2Current Integer32,
- mpduMpscom_7_Branch3Current Integer32,
- mpduMpscom_8_ActivePower Integer32,
- mpduMpscom_9_ApparentPower Integer32,
- mpduMpscom_10_PowerFactor Integer32,
- mpduMpscom_11_Frequency Integer32,
- mpduMpscom_12_LoadCurrent Integer32,
- mpduMpscom_13_PowerConsumption Integer32,
- mpduMpscom_14_OutletState116 Integer32,
- mpduMpscom_15_OutletState1732 Integer32,
- mpduMpscom_16_TimeS Integer32,
- mpduMpscom_17_TimeMin Integer32,
- mpduMpscom_18_TimeHour Integer32,
- mpduMpscom_19_TimeDay Integer32,
- mpduMpscom_20_TimeWeek Integer32,
- mpduMpscom_21_TimeMonth Integer32,
- mpduMpscom_22_TimeYear Integer32,
- mpduMpscom_23_Barcode12 Integer32,
- mpduMpscom_24_Barcode34 Integer32,
- mpduMpscom_25_Barcode56 Integer32,
- mpduMpscom_26_Barcode78 Integer32,
- mpduMpscom_27_Barcode910 Integer32,
- mpduMpscom_28_Barcode1112 Integer32,
- mpduMpscom_29_Barcode1314 Integer32,
- mpduMpscom_30_Barcode1516 Integer32,
- mpduMpscom_31_Barcode1718 Integer32,
- mpduMpscom_32_Barcode1920 Integer32,
- mpduMpscom_33_C13OutputNumbers Integer32,
- mpduMpscom_34_C19OutputNumbers Integer32,
- mpduMpscom_35_10AStandard Integer32,
- mpduMpscom_36_16AStandard Integer32,
- mpduMpscom_37_RatedCurrent Integer32,
- mpduMpscom_38_ProductAddress Integer32,
- mpduMpscom_39_Voltagedifference Integer32,
- mpduMpscom_40_Currentdifference Integer32,
- mpduMpscom_41_LoadVoltageLowLimit INTEGER,
- mpduMpscom_42_LoadVoltageHighLimit INTEGER,
- mpduMpscom_43_LoadCurrentLowLimit INTEGER,
- mpduMpscom_44_LoadCurrentHighLimit INTEGER,
- mpduMpscom_45_Branch1LoadTotalCurrentLow INTEGER,
- mpduMpscom_46_Branch1LoadTotalCurrentHigh INTEGER,
- mpduMpscom_47_Branch2LoadTotalCurrentLow INTEGER,
- mpduMpscom_48_Branch2LoadTotalCurrentHigh INTEGER,
- mpduMpscom_49_Branch3LoadTotalCurrentLow INTEGER,
- mpduMpscom_50_Branch3LoadTotalCurrentHigh INTEGER,
- mpduMpscom_51_CommunicateStatus INTEGER,
- mpduMpscom_52_Outlet1Status INTEGER,
- mpduMpscom_53_Outlet2Status INTEGER,
- mpduMpscom_54_Outlet3Status INTEGER,
- mpduMpscom_55_Outlet4Status INTEGER,
- mpduMpscom_56_Outlet5Status INTEGER,
- mpduMpscom_57_Outlet6Status INTEGER,
- mpduMpscom_58_Outlet7Status INTEGER,
- mpduMpscom_59_Outlet8Status INTEGER,
- mpduMpscom_60_Outlet9Status INTEGER,
- mpduMpscom_61_Outlet10Status INTEGER,
- mpduMpscom_62_Outlet11Status INTEGER,
- mpduMpscom_63_Outlet12Status INTEGER,
- mpduMpscom_64_Outlet13Status INTEGER,
- mpduMpscom_65_Outlet14Status INTEGER,
- mpduMpscom_66_Outlet15Status INTEGER,
- mpduMpscom_67_Outlet16Status INTEGER,
- mpduMpscom_68_Outlet17Status INTEGER,
- mpduMpscom_69_Outlet18Status INTEGER,
- mpduMpscom_70_Outlet19Status INTEGER,
- mpduMpscom_71_Outlet20Status INTEGER,
- mpduMpscom_72_Outlet21Status INTEGER,
- mpduMpscom_73_Outlet22Status INTEGER,
- mpduMpscom_74_Outlet23Status INTEGER,
- mpduMpscom_75_Outlet24Status INTEGER,
- mpduMpscom_76_LoadVoltageLowLimit Integer32,
- mpduMpscom_77_LoadVoltageHighLimit Integer32,
- mpduMpscom_78_LoadCurrentLowLimit Integer32,
- mpduMpscom_79_LoadCurrentHighLimit Integer32,
- mpduMpscom_80_Branch1LoadTotalCurrentLow Integer32,
- mpduMpscom_81_Branch1LoadTotalCurrentHigh Integer32,
- mpduMpscom_82_Branch2LoadTotalCurrentLow Integer32,
- mpduMpscom_83_Branch2LoadTotalCurrentHigh Integer32,
- mpduMpscom_84_Branch3LoadTotalCurrentLow Integer32,
- mpduMpscom_85_Branch3LoadTotalCurrentHigh Integer32,
- mpduMpscom_86_Outlet1DelayTime INTEGER,
- mpduMpscom_87_Outlet2DelayTime INTEGER,
- mpduMpscom_88_Outlet3DelayTime INTEGER,
- mpduMpscom_89_Outlet4DelayTime INTEGER,
- mpduMpscom_90_Outlet5DelayTime INTEGER,
- mpduMpscom_91_Outlet6DelayTime INTEGER,
- mpduMpscom_92_Outlet7DelayTime INTEGER,
- mpduMpscom_93_Outlet8DelayTime INTEGER,
- mpduMpscom_94_Outlet9DelayTime INTEGER,
- mpduMpscom_95_Outlet10DelayTime INTEGER,
- mpduMpscom_96_Outlet11DelayTime INTEGER,
- mpduMpscom_97_Outlet12DelayTime INTEGER,
- mpduMpscom_98_Outlet13DelayTime INTEGER,
- mpduMpscom_99_Outlet14DelayTime INTEGER,
- mpduMpscom_100_Outlet15DelayTime INTEGER,
- mpduMpscom_101_Outlet16DelayTime INTEGER,
- mpduMpscom_102_Outlet17DelayTime INTEGER,
- mpduMpscom_103_Outlet18DelayTime INTEGER,
- mpduMpscom_104_Outlet19DelayTime INTEGER,
- mpduMpscom_105_Outlet20DelayTime INTEGER,
- mpduMpscom_106_Outlet21DelayTime INTEGER,
- mpduMpscom_107_Outlet22DelayTime INTEGER,
- mpduMpscom_108_Outlet23DelayTime INTEGER,
- mpduMpscom_109_Outlet24DelayTime INTEGER,
- mpduMpscom_110_PDUPORTNUM INTEGER }
- mpduMpscomIndex OBJECT-TYPE
- SYNTAX Integer32(1..110)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom System Entry Index."
- ::= { mpduMpscomEntry 1 }
- mpduMpscom_2_ProductType OBJECT-TYPE
- SYNTAX INTEGER {
- undefined(0),
- totalcurrentcommeter(1),
- totalcurrentcomswitch(2),
- totalcurrentipmeter(3),
- totalcurrentipswitch(4),
- bitcurrentcommeter(5),
- bitcurrentcomswitch(6),
- bitcurrentipmeter(7),
- bitcurrentipswitch(8) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_1_ProductType status."
- ::= { mpduMpscomEntry 2 }
- mpduMpscom_3_Voltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_2_Voltage stored as 1V."
- ::= { mpduMpscomEntry 3 }
- mpduMpscom_4_TotalCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_3_TotalCurrent stored as 0.1A."
- ::= { mpduMpscomEntry 4 }
- mpduMpscom_5_Branch1Current OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_4_Branch1Current stored as 0.1A."
- ::= { mpduMpscomEntry 5 }
- mpduMpscom_6_Branch2Current OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_5_Branch2Current stored as 0.1A."
- ::= { mpduMpscomEntry 6 }
- mpduMpscom_7_Branch3Current OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_6_Branch3Current stored as 0.1A."
- ::= { mpduMpscomEntry 7 }
- mpduMpscom_8_ActivePower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_7_ActivePower stored as 0.01kW."
- ::= { mpduMpscomEntry 8 }
- mpduMpscom_9_ApparentPower OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_8_ApparentPower stored as 0.01kVA."
- ::= { mpduMpscomEntry 9 }
- mpduMpscom_10_PowerFactor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_9_PowerFactor stored as 0.01."
- ::= { mpduMpscomEntry 10 }
- mpduMpscom_11_Frequency OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_10_Frequency stored as 0.1Hz."
- ::= { mpduMpscomEntry 11 }
- mpduMpscom_12_LoadCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_11_LoadCurrent stored as 0.1%."
- ::= { mpduMpscomEntry 12 }
- mpduMpscom_13_PowerConsumption OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_12_PowerConsumption stored as 0.01kWh."
- ::= { mpduMpscomEntry 13 }
- mpduMpscom_14_OutletState116 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_13_OutletState116 stored as 1."
- ::= { mpduMpscomEntry 14 }
- mpduMpscom_15_OutletState1732 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_14_OutletState1732 stored as 1."
- ::= { mpduMpscomEntry 15 }
- mpduMpscom_16_TimeS OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_15_TimeS stored as 1S."
- ::= { mpduMpscomEntry 16 }
- mpduMpscom_17_TimeMin OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_16_TimeMin stored as 1Min."
- ::= { mpduMpscomEntry 17 }
- mpduMpscom_18_TimeHour OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_17_TimeHour stored as 1Hour."
- ::= { mpduMpscomEntry 18 }
- mpduMpscom_19_TimeDay OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_18_TimeDay stored as 1Day."
- ::= { mpduMpscomEntry 19 }
- mpduMpscom_20_TimeWeek OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_19_TimeWeek stored as 1Week."
- ::= { mpduMpscomEntry 20 }
- mpduMpscom_21_TimeMonth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_20_TimeMonth stored as 1Month."
- ::= { mpduMpscomEntry 21 }
- mpduMpscom_22_TimeYear OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_21_TimeYear stored as 1Year."
- ::= { mpduMpscomEntry 22 }
- mpduMpscom_23_Barcode12 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_22_Barcode12 stored as 1."
- ::= { mpduMpscomEntry 23 }
- mpduMpscom_24_Barcode34 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_23_Barcode34 stored as 1."
- ::= { mpduMpscomEntry 24 }
- mpduMpscom_25_Barcode56 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_24_Barcode56 stored as 1."
- ::= { mpduMpscomEntry 25 }
- mpduMpscom_26_Barcode78 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_25_Barcode78 stored as 1."
- ::= { mpduMpscomEntry 26 }
- mpduMpscom_27_Barcode910 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_26_Barcode910 stored as 1."
- ::= { mpduMpscomEntry 27 }
- mpduMpscom_28_Barcode1112 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_27_Barcode1112 stored as 1."
- ::= { mpduMpscomEntry 28 }
- mpduMpscom_29_Barcode1314 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_28_Barcode1314 stored as 1."
- ::= { mpduMpscomEntry 29 }
- mpduMpscom_30_Barcode1516 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_29_Barcode1516 stored as 1."
- ::= { mpduMpscomEntry 30 }
- mpduMpscom_31_Barcode1718 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_30_Barcode1718 stored as 1."
- ::= { mpduMpscomEntry 31 }
- mpduMpscom_32_Barcode1920 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_31_Barcode1920 stored as 1."
- ::= { mpduMpscomEntry 32 }
- mpduMpscom_33_C13OutputNumbers OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_32_C13OutputNumbers stored as 1."
- ::= { mpduMpscomEntry 33 }
- mpduMpscom_34_C19OutputNumbers OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_33_C19OutputNumbers stored as 1."
- ::= { mpduMpscomEntry 34 }
- mpduMpscom_35_10AStandard OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_34_10AStandard stored as 1."
- ::= { mpduMpscomEntry 35 }
- mpduMpscom_36_16AStandard OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_35_16AStandard stored as 1."
- ::= { mpduMpscomEntry 36 }
- mpduMpscom_37_RatedCurrent OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_36_RatedCurrent stored as 0.1A."
- ::= { mpduMpscomEntry 37 }
- mpduMpscom_38_ProductAddress OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_37_ProductAddress stored as 1."
- ::= { mpduMpscomEntry 38 }
- mpduMpscom_39_Voltagedifference OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_38_Voltagedifference stored as 0.1V."
- ::= { mpduMpscomEntry 39 }
- mpduMpscom_40_Currentdifference OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_39_Currentdifference stored as 0.1A."
- ::= { mpduMpscomEntry 40 }
- mpduMpscom_41_LoadVoltageLowLimit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_40_LoadVoltageLowLimit status."
- ::= { mpduMpscomEntry 41 }
- mpduMpscom_42_LoadVoltageHighLimit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_41_LoadVoltageHighLimit status."
- ::= { mpduMpscomEntry 42 }
- mpduMpscom_43_LoadCurrentLowLimit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_42_LoadCurrentLowLimit status."
- ::= { mpduMpscomEntry 43 }
- mpduMpscom_44_LoadCurrentHighLimit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_43_LoadCurrentHighLimit status."
- ::= { mpduMpscomEntry 44 }
- mpduMpscom_45_Branch1LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_44_Branch1LoadTotalCurrentLow status."
- ::= { mpduMpscomEntry 45 }
- mpduMpscom_46_Branch1LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_45_Branch1LoadTotalCurrentHigh status."
- ::= { mpduMpscomEntry 46 }
- mpduMpscom_47_Branch2LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_46_Branch2LoadTotalCurrentLow status."
- ::= { mpduMpscomEntry 47 }
- mpduMpscom_48_Branch2LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_47_Branch2LoadTotalCurrentHigh status."
- ::= { mpduMpscomEntry 48 }
- mpduMpscom_49_Branch3LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_48_Branch3LoadTotalCurrentLow status."
- ::= { mpduMpscomEntry 49 }
- mpduMpscom_50_Branch3LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_49_Branch3LoadTotalCurrentHigh status."
- ::= { mpduMpscomEntry 50 }
- mpduMpscom_51_CommunicateStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_50_CommunicateStatus status."
- ::= { mpduMpscomEntry 51 }
- mpduMpscom_52_Outlet1Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_51_Outlet1Status status."
- ::= { mpduMpscomEntry 52 }
- mpduMpscom_53_Outlet2Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_52_Outlet2Status status."
- ::= { mpduMpscomEntry 53 }
- mpduMpscom_54_Outlet3Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_53_Outlet3Status status."
- ::= { mpduMpscomEntry 54 }
- mpduMpscom_55_Outlet4Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_54_Outlet4Status status."
- ::= { mpduMpscomEntry 55 }
- mpduMpscom_56_Outlet5Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_55_Outlet5Status status."
- ::= { mpduMpscomEntry 56 }
- mpduMpscom_57_Outlet6Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_56_Outlet6Status status."
- ::= { mpduMpscomEntry 57 }
- mpduMpscom_58_Outlet7Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_57_Outlet7Status status."
- ::= { mpduMpscomEntry 58 }
- mpduMpscom_59_Outlet8Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_58_Outlet8Status status."
- ::= { mpduMpscomEntry 59 }
- mpduMpscom_60_Outlet9Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_59_Outlet9Status status."
- ::= { mpduMpscomEntry 60 }
- mpduMpscom_61_Outlet10Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_60_Outlet10Status status."
- ::= { mpduMpscomEntry 61 }
- mpduMpscom_62_Outlet11Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_61_Outlet11Status status."
- ::= { mpduMpscomEntry 62 }
- mpduMpscom_63_Outlet12Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_62_Outlet12Status status."
- ::= { mpduMpscomEntry 63 }
- mpduMpscom_64_Outlet13Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_63_Outlet13Status status."
- ::= { mpduMpscomEntry 64 }
- mpduMpscom_65_Outlet14Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_64_Outlet14Status status."
- ::= { mpduMpscomEntry 65 }
- mpduMpscom_66_Outlet15Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_65_Outlet15Status status."
- ::= { mpduMpscomEntry 66 }
- mpduMpscom_67_Outlet16Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_66_Outlet16Status status."
- ::= { mpduMpscomEntry 67 }
- mpduMpscom_68_Outlet17Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_67_Outlet17Status status."
- ::= { mpduMpscomEntry 68 }
- mpduMpscom_69_Outlet18Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_68_Outlet18Status status."
- ::= { mpduMpscomEntry 69 }
- mpduMpscom_70_Outlet19Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_69_Outlet19Status status."
- ::= { mpduMpscomEntry 70 }
- mpduMpscom_71_Outlet20Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_70_Outlet20Status status."
- ::= { mpduMpscomEntry 71 }
- mpduMpscom_72_Outlet21Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_71_Outlet21Status status."
- ::= { mpduMpscomEntry 72 }
- mpduMpscom_73_Outlet22Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_72_Outlet22Status status."
- ::= { mpduMpscomEntry 73 }
- mpduMpscom_74_Outlet23Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_73_Outlet23Status status."
- ::= { mpduMpscomEntry 74 }
- mpduMpscom_75_Outlet24Status OBJECT-TYPE
- SYNTAX INTEGER {
- poweroff(0),
- poweron(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_74_Outlet24Status status."
- ::= { mpduMpscomEntry 75 }
- mpduMpscom_76_LoadVoltageLowLimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_75_LoadVoltageLowLimit stored as 1V."
- ::= { mpduMpscomEntry 76 }
- mpduMpscom_77_LoadVoltageHighLimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_76_LoadVoltageHighLimit stored as 1V."
- ::= { mpduMpscomEntry 77 }
- mpduMpscom_78_LoadCurrentLowLimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_77_LoadCurrentLowLimit stored as 1A."
- ::= { mpduMpscomEntry 78 }
- mpduMpscom_79_LoadCurrentHighLimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_78_LoadCurrentHighLimit stored as 1A."
- ::= { mpduMpscomEntry 79 }
- mpduMpscom_80_Branch1LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_79_Branch1LoadTotalCurrentLow stored as 1A."
- ::= { mpduMpscomEntry 80 }
- mpduMpscom_81_Branch1LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_80_Branch1LoadTotalCurrentHigh stored as 1A."
- ::= { mpduMpscomEntry 81 }
- mpduMpscom_82_Branch2LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_81_Branch2LoadTotalCurrentLow stored as 1A."
- ::= { mpduMpscomEntry 82 }
- mpduMpscom_83_Branch2LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_82_Branch2LoadTotalCurrentHigh stored as 1A."
- ::= { mpduMpscomEntry 83 }
- mpduMpscom_84_Branch3LoadTotalCurrentLow OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_83_Branch3LoadTotalCurrentLow stored as 1A."
- ::= { mpduMpscomEntry 84 }
- mpduMpscom_85_Branch3LoadTotalCurrentHigh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_84_Branch3LoadTotalCurrentHigh stored as 1A."
- ::= { mpduMpscomEntry 85 }
- mpduMpscom_86_Outlet1DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_85_Outlet1DelayTime stored as 1s."
- ::= { mpduMpscomEntry 86 }
- mpduMpscom_87_Outlet2DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_86_Outlet2DelayTime stored as 1s."
- ::= { mpduMpscomEntry 87 }
- mpduMpscom_88_Outlet3DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_87_Outlet3DelayTime stored as 1s."
- ::= { mpduMpscomEntry 88 }
- mpduMpscom_89_Outlet4DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_88_Outlet4DelayTime stored as 1s."
- ::= { mpduMpscomEntry 89 }
- mpduMpscom_90_Outlet5DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_89_Outlet5DelayTime stored as 1s."
- ::= { mpduMpscomEntry 90 }
- mpduMpscom_91_Outlet6DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_90_Outlet6DelayTime stored as 1s."
- ::= { mpduMpscomEntry 91 }
- mpduMpscom_92_Outlet7DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_91_Outlet7DelayTime stored as 1s."
- ::= { mpduMpscomEntry 92 }
- mpduMpscom_93_Outlet8DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_92_Outlet8DelayTime stored as 1s."
- ::= { mpduMpscomEntry 93 }
- mpduMpscom_94_Outlet9DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_93_Outlet9DelayTime stored as 1s."
- ::= { mpduMpscomEntry 94 }
- mpduMpscom_95_Outlet10DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_94_Outlet10DelayTime stored as 1s."
- ::= { mpduMpscomEntry 95 }
- mpduMpscom_96_Outlet11DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_95_Outlet11DelayTime stored as 1s."
- ::= { mpduMpscomEntry 96 }
- mpduMpscom_97_Outlet12DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_96_Outlet12DelayTime stored as 1s."
- ::= { mpduMpscomEntry 97 }
- mpduMpscom_98_Outlet13DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_97_Outlet13DelayTime stored as 1s."
- ::= { mpduMpscomEntry 98 }
- mpduMpscom_99_Outlet14DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_98_Outlet14DelayTime stored as 1s."
- ::= { mpduMpscomEntry 99 }
- mpduMpscom_100_Outlet15DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_99_Outlet15DelayTime stored as 1s."
- ::= { mpduMpscomEntry 100 }
- mpduMpscom_101_Outlet16DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_100_Outlet16DelayTime stored as 1s."
- ::= { mpduMpscomEntry 101 }
- mpduMpscom_102_Outlet17DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_101_Outlet17DelayTime stored as 1s."
- ::= { mpduMpscomEntry 102 }
- mpduMpscom_103_Outlet18DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_102_Outlet18DelayTime stored as 1s."
- ::= { mpduMpscomEntry 103 }
- mpduMpscom_104_Outlet19DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_103_Outlet19DelayTime stored as 1s."
- ::= { mpduMpscomEntry 104 }
- mpduMpscom_105_Outlet20DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_104_Outlet20DelayTime stored as 1s."
- ::= { mpduMpscomEntry 105 }
- mpduMpscom_106_Outlet21DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_105_Outlet21DelayTime stored as 1s."
- ::= { mpduMpscomEntry 106 }
- mpduMpscom_107_Outlet22DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_106_Outlet22DelayTime stored as 1s."
- ::= { mpduMpscomEntry 107 }
- mpduMpscom_108_Outlet23DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_107_Outlet23DelayTime stored as 1s."
- ::= { mpduMpscomEntry 108 }
- mpduMpscom_109_Outlet24DelayTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "mpduMpscom_108_Outlet24DelayTime stored as 1s."
- ::= { mpduMpscomEntry 109 }
- mpduMpscom_110_PDUPORTNUM OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "mpduMpscom_109_PDUPORTNUM stored as 1."
- ::= { mpduMpscomEntry 110 }
- ------------------------------------------------------------
- -- Acdu { 13400.3.3 }
- ------------------------------------------------------------
- ac OBJECT IDENTIFIER ::= { dcs 3 }
- ------------------------------------------------------------
- -- Ou { 13400.3.3.3031 }
- ------------------------------------------------------------
- ac-Ou OBJECT IDENTIFIER ::= { ac 3031 }
- acOuTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AcOuEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "acOuTable"
- ::= { ac-Ou 1 }
- acOuEntry OBJECT-TYPE
- SYNTAX AcOuEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "acOuEntry"
- INDEX { acOuIndex }
- ::= { acOuTable 1 }
- AcOuEntry ::= SEQUENCE {
- acOuIndex Integer32,
- acOu_2_Highwaterlevelswitch INTEGER,
- acOu_3_Lowvoltageswitch INTEGER,
- acOu_4_Remoteswitch INTEGER,
- acOu_5_Compressoroutput INTEGER,
- acOu_6_Fanoutput INTEGER,
- acOu_7_Commonalarmoutput INTEGER,
- acOu_8_Bypasssolenoidvalveoutput INTEGER,
- acOu_9_HighPressure INTEGER,
- acOu_10_LowPressure INTEGER,
- acOu_11_Exhausttemperaturealarm INTEGER,
- acOu_12_Returnairhightempalarm INTEGER,
- acOu_13_supplyairLowtempalarm INTEGER,
- acOu_14_supplyairhightempalarm INTEGER,
- acOu_15_Frequenthighpressurealarm INTEGER,
- acOu_16_Lowpressurefrequentalarm INTEGER,
- acOu_17_Frequenthightempexhaustalar INTEGER,
- acOu_18_Powerlossalarm INTEGER,
- acOu_19_Powerovervoltagealarm INTEGER,
- acOu_20_Powerundervoltagealarm INTEGER,
- acOu_21_Highwaterlevelalarm INTEGER,
- acOu_22_FilterServiceRequired INTEGER,
- acOu_23_RemoteShutdownAlarm INTEGER,
- acOu_24_Returnairtempsensorfault INTEGER,
- acOu_25_Supplyairtempsensorfault INTEGER,
- acOu_26_Highpressuresensorfault INTEGER,
- acOu_27_Newalarmflag INTEGER,
- acOu_28_PanelOff INTEGER,
- acOu_29_Monitorshutdown INTEGER,
- acOu_30_Remoteshutdownflag INTEGER,
- acOu_31_Remoteswitchinputpolarity INTEGER,
- acOu_32_Publicalarmoutputpolarity INTEGER,
- acOu_33_Refrigeration INTEGER,
- acOu_34_Exhaustgastempsensorfault INTEGER,
- acOu_35_EEVcommunicationfailure INTEGER,
- acOu_36_Intakeairtemperaturesensorf INTEGER,
- acOu_37_Lowpressuresensorfault INTEGER,
- acOu_38_Compressordrivecommunication INTEGER,
- acOu_39_Module2overtemperature INTEGER,
- acOu_40_Busovervoltage INTEGER,
- acOu_41_Tempsensor1isfaulty INTEGER,
- acOu_42_Tempsensor2isfaulty INTEGER,
- acOu_43_Shortcircuit INTEGER,
- acOu_44_FrequencyShift INTEGER,
- acOu_45_Module1overtemperature INTEGER,
- acOu_46_CompressordriveprotectionU04 INTEGER,
- acOu_47_CompressordriveprotectionU13 INTEGER,
- acOu_48_CompressordriveprotectionU14 INTEGER,
- acOu_49_CompressordriveprotectionU11 INTEGER,
- acOu_50_CompressordriveprotectionU08 INTEGER,
- acOu_51_CompressordriveprotectionU09 INTEGER,
- acOu_52_CompressordriveprotectionU10 INTEGER,
- acOu_53_CompressordriveprotectionU12 INTEGER,
- acOu_54_CompressordriveprotectionU15 INTEGER,
- acOu_55_CompressordriveprotectionU06 INTEGER,
- acOu_56_Supplyairtemperature Integer32,
- acOu_57_Returnairtemperature Integer32,
- acOu_58_Outsidetemperature Integer32,
- acOu_59_Exhausttemperature Integer32,
- acOu_60_Inspiratorytemperature Integer32,
- acOu_61_Exhaustpressure Integer32,
- acOu_62_Inspiratorypressure Integer32,
- acOu_63_Monitoraddress Integer32,
- acOu_64_Powervoltage Integer32,
- acOu_65_Powerfrequency Integer32,
- acOu_66_Inspiratorysuperheat Integer32,
- acOu_67_Thenumberofalarmstates Integer32,
- acOu_68_Numberofalarmhistory Integer32,
- acOu_69_Compressorstartandstoprecor Integer32,
- acOu_70_Fanstartandstoprecordnumbe Integer32,
- acOu_71_Compressorhoursofoperationr Integer32,
- acOu_72_CommunicateStatus INTEGER,
- acOu_73_Highsoftwareversion Integer32,
- acOu_74_Softwareversionlow Integer32,
- acOu_75_Airconditioningrunningstatus INTEGER,
- acOu_76_Compressorcapacityactualvalu Integer32,
- acOu_77_Fanspeed Integer32,
- acOu_78_Expansionvalveopening Integer32,
- acOu_79_Highpressureabnormalrecordn Integer32,
- acOu_80_Controlmode Integer32,
- acOu_81_Compressortemperatureintegrat Integer32,
- acOu_82_Compressortemperaturedifferen Integer32,
- acOu_83_Fantemperatureintegrationtim Integer32,
- acOu_84_Fantemperaturedifferentialti Integer32,
- acOu_85_Modelselection Integer32,
- acOu_86_Returntoruntime Integer32,
- acOu_87_Returnoilcapacity Integer32,
- acOu_88_Compressorhoppingpoint1 Integer32,
- acOu_89_Compressorhoppingpoint1band Integer32,
- acOu_90_Compressorhoppingpoint2 Integer32,
- acOu_91_Compressorhoppingpoint2band Integer32,
- acOu_92_Compressorhoppingpoint3 Integer32,
- acOu_93_Compressorhoppingpoint3band Integer32,
- acOu_94_Compressorhoppingpoint4 Integer32,
- acOu_95_Compressorhoppingpoint4band Integer32,
- acOu_96_Compressorhoppingpoint5 Integer32,
- acOu_97_Compressorhoppingpoint5band Integer32,
- acOu_98_Indoorfanfrequencyhoppingpo Integer32,
- acOu_99_Indoorfanfrequencyhoppingpo Integer32,
- acOu_100_Indoorfanfrequencyhoppingpo Integer32,
- acOu_101_Indoorfanfrequencyhoppingpo Integer32,
- acOu_102_Indoorfanfrequencyhoppingpo Integer32,
- acOu_103_Indoorfanfrequencyhoppingpo Integer32,
- acOu_104_Indoorfanfrequencyhoppingpo Integer32,
- acOu_105_Indoorfanfrequencyhoppingpo Integer32,
- acOu_106_Indoorfanfrequencyhoppingpo Integer32,
- acOu_107_Indoorfanfrequencyhoppingpo Integer32,
- acOu_108_Indoorfanfrequencyhoppingpo Integer32,
- acOu_109_Indoorfanfrequencyhoppingpo Integer32,
- acOu_110_reset INTEGER,
- acOu_111_Filtermaintenance INTEGER,
- acOu_112_RemoteOn INTEGER,
- acOu_113_RemoteOff INTEGER,
- acOu_114_RemoteOff INTEGER,
- acOu_115_Supplyairtempcorrectionvalu Integer32,
- acOu_116_Returnairtempecorrectionval Integer32,
- acOu_117_Exhausttempcorrectionvalue Integer32,
- acOu_118_Exhaustpressurecorrectionval Integer32,
- acOu_119_Suctionpressurecorrectionval Integer32,
- acOu_120_Monitoraddress Integer32,
- acOu_121_Compressorshortestrunningtim Integer32,
- acOu_122_Minimumcompressordowntime Integer32,
- acOu_123_Fanstartdelay Integer32,
- acOu_124_Fanstopdelay Integer32,
- acOu_125_Deadzonetemperature Integer32,
- acOu_126_Returnairtempsetting Integer32,
- acOu_127_Compressorcapacityoutputvalu Integer32,
- acOu_128_Lowpressurealarmdelay Integer32,
- acOu_129_Filtermaintenanceremindertim Integer32,
- acOu_130_Highpressurealarmvalue Integer32,
- acOu_131_Supplyairtemperaturealarmva Integer32,
- acOu_132_Supplyairtemperaturealarmva Integer32,
- acOu_133_Returnairtemperaturealarmva Integer32,
- acOu_134_Powerovervoltagealarmpoint Integer32,
- acOu_135_Powerundervoltagealarmpoint Integer32,
- acOu_136_Compressortemperatureproporti Integer32,
- acOu_137_Fantemperatureproportionalba Integer32,
- acOu_138_Compressorstartuprequirements Integer32,
- acOu_139_Compressorstopdemand Integer32,
- acOu_140_Compressorminimumcapacity Integer32,
- acOu_141_Compressorstandardcapacity Integer32,
- acOu_142_Compressorstartupcapacity Integer32,
- acOu_143_Compressoroutputdeadzone Integer32,
- acOu_144_Returncycle Integer32,
- acOu_145_Minimumfanspeed Integer32,
- acOu_146_Fanstandardspeed Integer32,
- acOu_147_MinimumfanspeedCFC Integer32,
- acOu_148_FanstandardspeedCFC Integer32,
- acOu_149_Lowspeedfanstep Integer32,
- acOu_150_Highspeedfanstep Integer32,
- acOu_151_Fandecelerationdelay Integer32,
- acOu_152_EEVsuperheatsettingMAX Integer32,
- acOu_153_EEVsuperheatsettingMIN Integer32,
- acOu_154_EEVMOPpressurelimit Integer32,
- acOu_155_EEVvalvebodyshutoffsuperhe Integer32,
- acOu_156_Outdoorfanminimumsupplyvolt Integer32,
- acOu_157_Outdoorfanmaximumsupplyvolt Integer32,
- acOu_158_Outdoorfanpressurecontrolra Integer32,
- acOu_159_Outdoorfanstartpressure Integer32,
- acOu_160_Outdoorfanstartpressure Integer32 }
- acOuIndex OBJECT-TYPE
- SYNTAX Integer32(1..160)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu System Entry Index."
- ::= { acOuEntry 1 }
- acOu_2_Highwaterlevelswitch OBJECT-TYPE
- SYNTAX INTEGER {
- shutdown(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_1_Highwaterlevelswitch status."
- ::= { acOuEntry 2 }
- acOu_3_Lowvoltageswitch OBJECT-TYPE
- SYNTAX INTEGER {
- shutdown(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_2_Lowvoltageswitch status."
- ::= { acOuEntry 3 }
- acOu_4_Remoteswitch OBJECT-TYPE
- SYNTAX INTEGER {
- shutdown(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_3_Remoteswitch status."
- ::= { acOuEntry 4 }
- acOu_5_Compressoroutput OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_4_Compressoroutput status."
- ::= { acOuEntry 5 }
- acOu_6_Fanoutput OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0),
- no(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_5_Fanoutput status."
- ::= { acOuEntry 6 }
- acOu_7_Commonalarmoutput OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_6_Commonalarmoutput status."
- ::= { acOuEntry 7 }
- acOu_8_Bypasssolenoidvalveoutput OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_7_Bypasssolenoidvalveoutput status."
- ::= { acOuEntry 8 }
- acOu_9_HighPressure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_8_HighPressure status."
- ::= { acOuEntry 9 }
- acOu_10_LowPressure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_9_LowPressure status."
- ::= { acOuEntry 10 }
- acOu_11_Exhausttemperaturealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_10_Exhausttemperaturealarm status."
- ::= { acOuEntry 11 }
- acOu_12_Returnairhightempalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_11_Returnairhightempalarm status."
- ::= { acOuEntry 12 }
- acOu_13_supplyairLowtempalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_12_supplyairLowtempalarm status."
- ::= { acOuEntry 13 }
- acOu_14_supplyairhightempalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_13_supplyairhightempalarm status."
- ::= { acOuEntry 14 }
- acOu_15_Frequenthighpressurealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_14_Frequenthighpressurealarm status."
- ::= { acOuEntry 15 }
- acOu_16_Lowpressurefrequentalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_15_Lowpressurefrequentalarm status."
- ::= { acOuEntry 16 }
- acOu_17_Frequenthightempexhaustalar OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_16_Frequenthightempexhaustalar status."
- ::= { acOuEntry 17 }
- acOu_18_Powerlossalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_17_Powerlossalarm status."
- ::= { acOuEntry 18 }
- acOu_19_Powerovervoltagealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_18_Powerovervoltagealarm status."
- ::= { acOuEntry 19 }
- acOu_20_Powerundervoltagealarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_19_Powerundervoltagealarm status."
- ::= { acOuEntry 20 }
- acOu_21_Highwaterlevelalarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_20_Highwaterlevelalarm status."
- ::= { acOuEntry 21 }
- acOu_22_FilterServiceRequired OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_21_FilterServiceRequired status."
- ::= { acOuEntry 22 }
- acOu_23_RemoteShutdownAlarm OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_22_RemoteShutdownAlarm status."
- ::= { acOuEntry 23 }
- acOu_24_Returnairtempsensorfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_23_Returnairtempsensorfault status."
- ::= { acOuEntry 24 }
- acOu_25_Supplyairtempsensorfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_24_Supplyairtempsensorfault status."
- ::= { acOuEntry 25 }
- acOu_26_Highpressuresensorfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_25_Highpressuresensorfault status."
- ::= { acOuEntry 26 }
- acOu_27_Newalarmflag OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_26_Newalarmflag status."
- ::= { acOuEntry 27 }
- acOu_28_PanelOff OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_27_PanelOff status."
- ::= { acOuEntry 28 }
- acOu_29_Monitorshutdown OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_28_Monitorshutdown status."
- ::= { acOuEntry 29 }
- acOu_30_Remoteshutdownflag OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_29_Remoteshutdownflag status."
- ::= { acOuEntry 30 }
- acOu_31_Remoteswitchinputpolarity OBJECT-TYPE
- SYNTAX INTEGER {
- normallyclosed(0),
- normallyopen(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_30_Remoteswitchinputpolarity status."
- ::= { acOuEntry 31 }
- acOu_32_Publicalarmoutputpolarity OBJECT-TYPE
- SYNTAX INTEGER {
- normallyclosed(0),
- normallyopen(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_31_Publicalarmoutputpolarity status."
- ::= { acOuEntry 32 }
- acOu_33_Refrigeration OBJECT-TYPE
- SYNTAX INTEGER {
- yes(0),
- no(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_32_Refrigeration status."
- ::= { acOuEntry 33 }
- acOu_34_Exhaustgastempsensorfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_33_Exhaustgastempsensorfault status."
- ::= { acOuEntry 34 }
- acOu_35_EEVcommunicationfailure OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_34_EEVcommunicationfailure status."
- ::= { acOuEntry 35 }
- acOu_36_Intakeairtemperaturesensorf OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_35_Intakeairtemperaturesensorf status."
- ::= { acOuEntry 36 }
- acOu_37_Lowpressuresensorfault OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_36_Lowpressuresensorfault status."
- ::= { acOuEntry 37 }
- acOu_38_Compressordrivecommunication OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_37_Compressordrivecommunication status."
- ::= { acOuEntry 38 }
- acOu_39_Module2overtemperature OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_38_Module2overtemperature status."
- ::= { acOuEntry 39 }
- acOu_40_Busovervoltage OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_39_Busovervoltage status."
- ::= { acOuEntry 40 }
- acOu_41_Tempsensor1isfaulty OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_40_Tempsensor1isfaulty status."
- ::= { acOuEntry 41 }
- acOu_42_Tempsensor2isfaulty OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_41_Tempsensor2isfaulty status."
- ::= { acOuEntry 42 }
- acOu_43_Shortcircuit OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_42_Shortcircuit status."
- ::= { acOuEntry 43 }
- acOu_44_FrequencyShift OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_43_FrequencyShift status."
- ::= { acOuEntry 44 }
- acOu_45_Module1overtemperature OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_44_Module1overtemperature status."
- ::= { acOuEntry 45 }
- acOu_46_CompressordriveprotectionU04 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_45_CompressordriveprotectionU04 status."
- ::= { acOuEntry 46 }
- acOu_47_CompressordriveprotectionU13 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_46_CompressordriveprotectionU13 status."
- ::= { acOuEntry 47 }
- acOu_48_CompressordriveprotectionU14 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_47_CompressordriveprotectionU14 status."
- ::= { acOuEntry 48 }
- acOu_49_CompressordriveprotectionU11 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_48_CompressordriveprotectionU11 status."
- ::= { acOuEntry 49 }
- acOu_50_CompressordriveprotectionU08 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_49_CompressordriveprotectionU08 status."
- ::= { acOuEntry 50 }
- acOu_51_CompressordriveprotectionU09 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_50_CompressordriveprotectionU09 status."
- ::= { acOuEntry 51 }
- acOu_52_CompressordriveprotectionU10 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_51_CompressordriveprotectionU10 status."
- ::= { acOuEntry 52 }
- acOu_53_CompressordriveprotectionU12 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_52_CompressordriveprotectionU12 status."
- ::= { acOuEntry 53 }
- acOu_54_CompressordriveprotectionU15 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_53_CompressordriveprotectionU15 status."
- ::= { acOuEntry 54 }
- acOu_55_CompressordriveprotectionU06 OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_54_CompressordriveprotectionU06 status."
- ::= { acOuEntry 55 }
- acOu_56_Supplyairtemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_55_Supplyairtemperature stored as 0.01℃."
- ::= { acOuEntry 56 }
- acOu_57_Returnairtemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_56_Returnairtemperature stored as 0.01℃."
- ::= { acOuEntry 57 }
- acOu_58_Outsidetemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_57_Outsidetemperature stored as 0.01℃."
- ::= { acOuEntry 58 }
- acOu_59_Exhausttemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_58_Exhausttemperature stored as 0.01℃."
- ::= { acOuEntry 59 }
- acOu_60_Inspiratorytemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_59_Inspiratorytemperature stored as 0.01℃."
- ::= { acOuEntry 60 }
- acOu_61_Exhaustpressure OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_60_Exhaustpressure stored as 0.01Bar."
- ::= { acOuEntry 61 }
- acOu_62_Inspiratorypressure OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_61_Inspiratorypressure stored as 0.01Bar."
- ::= { acOuEntry 62 }
- acOu_63_Monitoraddress OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_62_Monitoraddress stored as 0.01."
- ::= { acOuEntry 63 }
- acOu_64_Powervoltage OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_63_Powervoltage stored as 0.01V."
- ::= { acOuEntry 64 }
- acOu_65_Powerfrequency OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_64_Powerfrequency stored as 0.01Hz."
- ::= { acOuEntry 65 }
- acOu_66_Inspiratorysuperheat OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_65_Inspiratorysuperheat stored as 0.01℃."
- ::= { acOuEntry 66 }
- acOu_67_Thenumberofalarmstates OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_66_Thenumberofalarmstates stored as 0.01."
- ::= { acOuEntry 67 }
- acOu_68_Numberofalarmhistory OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_67_Numberofalarmhistory stored as 0.01."
- ::= { acOuEntry 68 }
- acOu_69_Compressorstartandstoprecor OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_68_Compressorstartandstoprecor stored as 0.01."
- ::= { acOuEntry 69 }
- acOu_70_Fanstartandstoprecordnumbe OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_69_Fanstartandstoprecordnumbe stored as 0.01."
- ::= { acOuEntry 70 }
- acOu_71_Compressorhoursofoperationr OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_70_Compressorhoursofoperationr stored as 0.01Hour."
- ::= { acOuEntry 71 }
- acOu_72_CommunicateStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_71_CommunicateStatus status."
- ::= { acOuEntry 72 }
- acOu_73_Highsoftwareversion OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_72_Highsoftwareversion stored as 0.01."
- ::= { acOuEntry 73 }
- acOu_74_Softwareversionlow OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_73_Softwareversionlow stored as 0.01."
- ::= { acOuEntry 74 }
- acOu_75_Airconditioningrunningstatus OBJECT-TYPE
- SYNTAX INTEGER {
- on(0),
- off(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_74_Airconditioningrunningstatus status."
- ::= { acOuEntry 75 }
- acOu_76_Compressorcapacityactualvalu OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_75_Compressorcapacityactualvalu stored as 0.01%."
- ::= { acOuEntry 76 }
- acOu_77_Fanspeed OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_76_Fanspeed stored as 0.01%."
- ::= { acOuEntry 77 }
- acOu_78_Expansionvalveopening OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_77_Expansionvalveopening stored as 0.01%."
- ::= { acOuEntry 78 }
- acOu_79_Highpressureabnormalrecordn OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_78_Highpressureabnormalrecordn stored as 0.01."
- ::= { acOuEntry 79 }
- acOu_80_Controlmode OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_79_Controlmode stored as 0.01."
- ::= { acOuEntry 80 }
- acOu_81_Compressortemperatureintegrat OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_80_Compressortemperatureintegrat stored as 0.01Sec."
- ::= { acOuEntry 81 }
- acOu_82_Compressortemperaturedifferen OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_81_Compressortemperaturedifferen stored as 0.01Sec."
- ::= { acOuEntry 82 }
- acOu_83_Fantemperatureintegrationtim OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_82_Fantemperatureintegrationtim stored as 0.01Sec."
- ::= { acOuEntry 83 }
- acOu_84_Fantemperaturedifferentialti OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_83_Fantemperaturedifferentialti stored as 0.01Sec."
- ::= { acOuEntry 84 }
- acOu_85_Modelselection OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_84_Modelselection stored as 0.01."
- ::= { acOuEntry 85 }
- acOu_86_Returntoruntime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_85_Returntoruntime stored as 0.01Min."
- ::= { acOuEntry 86 }
- acOu_87_Returnoilcapacity OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_86_Returnoilcapacity stored as 0.01%."
- ::= { acOuEntry 87 }
- acOu_88_Compressorhoppingpoint1 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_87_Compressorhoppingpoint1 stored as 0.01%."
- ::= { acOuEntry 88 }
- acOu_89_Compressorhoppingpoint1band OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_88_Compressorhoppingpoint1band stored as 0.01%."
- ::= { acOuEntry 89 }
- acOu_90_Compressorhoppingpoint2 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_89_Compressorhoppingpoint2 stored as 0.01%."
- ::= { acOuEntry 90 }
- acOu_91_Compressorhoppingpoint2band OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_90_Compressorhoppingpoint2band stored as 0.01%."
- ::= { acOuEntry 91 }
- acOu_92_Compressorhoppingpoint3 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_91_Compressorhoppingpoint3 stored as 0.01%."
- ::= { acOuEntry 92 }
- acOu_93_Compressorhoppingpoint3band OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_92_Compressorhoppingpoint3band stored as 0.01%."
- ::= { acOuEntry 93 }
- acOu_94_Compressorhoppingpoint4 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_93_Compressorhoppingpoint4 stored as 0.01%."
- ::= { acOuEntry 94 }
- acOu_95_Compressorhoppingpoint4band OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_94_Compressorhoppingpoint4band stored as 0.01%."
- ::= { acOuEntry 95 }
- acOu_96_Compressorhoppingpoint5 OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_95_Compressorhoppingpoint5 stored as 0.01%."
- ::= { acOuEntry 96 }
- acOu_97_Compressorhoppingpoint5band OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_96_Compressorhoppingpoint5band stored as 0.01%."
- ::= { acOuEntry 97 }
- acOu_98_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_97_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 98 }
- acOu_99_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_98_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 99 }
- acOu_100_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_99_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 100 }
- acOu_101_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_100_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 101 }
- acOu_102_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_101_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 102 }
- acOu_103_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_102_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 103 }
- acOu_104_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_103_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 104 }
- acOu_105_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_104_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 105 }
- acOu_106_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_105_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 106 }
- acOu_107_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_106_Indoorfanfrequencyhoppingpo stored as 0.01%."
- ::= { acOuEntry 107 }
- acOu_108_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_107_Indoorfanfrequencyhoppingpo stored as 1%."
- ::= { acOuEntry 108 }
- acOu_109_Indoorfanfrequencyhoppingpo OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "acOu_108_Indoorfanfrequencyhoppingpo stored as 1%."
- ::= { acOuEntry 109 }
- acOu_110_reset OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_109_reset status."
- ::= { acOuEntry 110 }
- acOu_111_Filtermaintenance OBJECT-TYPE
- SYNTAX INTEGER {
- no(0),
- yes(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_110_Filtermaintenance status."
- ::= { acOuEntry 111 }
- acOu_112_RemoteOn OBJECT-TYPE
- SYNTAX INTEGER {
- remoteon(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_111_RemoteOn status."
- ::= { acOuEntry 112 }
- acOu_113_RemoteOff OBJECT-TYPE
- SYNTAX INTEGER {
- remoteoff(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_112_RemoteOff status."
- ::= { acOuEntry 113 }
- acOu_114_RemoteOff OBJECT-TYPE
- SYNTAX INTEGER {
- remoteoff(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_113_RemoteOff status."
- ::= { acOuEntry 114 }
- acOu_115_Supplyairtempcorrectionvalu OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_114_Supplyairtempcorrectionvalu stored as 1℃."
- ::= { acOuEntry 115 }
- acOu_116_Returnairtempecorrectionval OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_115_Returnairtempecorrectionval stored as 1℃."
- ::= { acOuEntry 116 }
- acOu_117_Exhausttempcorrectionvalue OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_116_Exhausttempcorrectionvalue stored as 1℃."
- ::= { acOuEntry 117 }
- acOu_118_Exhaustpressurecorrectionval OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_117_Exhaustpressurecorrectionval stored as 1Bar."
- ::= { acOuEntry 118 }
- acOu_119_Suctionpressurecorrectionval OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_118_Suctionpressurecorrectionval stored as 1Bar."
- ::= { acOuEntry 119 }
- acOu_120_Monitoraddress OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_119_Monitoraddress stored as 1."
- ::= { acOuEntry 120 }
- acOu_121_Compressorshortestrunningtim OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_120_Compressorshortestrunningtim stored as 1Min."
- ::= { acOuEntry 121 }
- acOu_122_Minimumcompressordowntime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_121_Minimumcompressordowntime stored as 1Min."
- ::= { acOuEntry 122 }
- acOu_123_Fanstartdelay OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_122_Fanstartdelay stored as 1Sec."
- ::= { acOuEntry 123 }
- acOu_124_Fanstopdelay OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_123_Fanstopdelay stored as 1Sec."
- ::= { acOuEntry 124 }
- acOu_125_Deadzonetemperature OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_124_Deadzonetemperature stored as 0.1℃."
- ::= { acOuEntry 125 }
- acOu_126_Returnairtempsetting OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_125_Returnairtempsetting stored as 1℃."
- ::= { acOuEntry 126 }
- acOu_127_Compressorcapacityoutputvalu OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_126_Compressorcapacityoutputvalu stored as 1%."
- ::= { acOuEntry 127 }
- acOu_128_Lowpressurealarmdelay OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_127_Lowpressurealarmdelay stored as 1Sec."
- ::= { acOuEntry 128 }
- acOu_129_Filtermaintenanceremindertim OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_128_Filtermaintenanceremindertim stored as 1Day."
- ::= { acOuEntry 129 }
- acOu_130_Highpressurealarmvalue OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_129_Highpressurealarmvalue stored as 1Bar."
- ::= { acOuEntry 130 }
- acOu_131_Supplyairtemperaturealarmva OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_130_Supplyairtemperaturealarmva stored as 1℃."
- ::= { acOuEntry 131 }
- acOu_132_Supplyairtemperaturealarmva OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_131_Supplyairtemperaturealarmva stored as 1℃."
- ::= { acOuEntry 132 }
- acOu_133_Returnairtemperaturealarmva OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_132_Returnairtemperaturealarmva stored as 1℃."
- ::= { acOuEntry 133 }
- acOu_134_Powerovervoltagealarmpoint OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_133_Powerovervoltagealarmpoint stored as 1V."
- ::= { acOuEntry 134 }
- acOu_135_Powerundervoltagealarmpoint OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_134_Powerundervoltagealarmpoint stored as 1V."
- ::= { acOuEntry 135 }
- acOu_136_Compressortemperatureproporti OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_135_Compressortemperatureproporti stored as 1℃."
- ::= { acOuEntry 136 }
- acOu_137_Fantemperatureproportionalba OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_136_Fantemperatureproportionalba stored as 1℃."
- ::= { acOuEntry 137 }
- acOu_138_Compressorstartuprequirements OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_137_Compressorstartuprequirements stored as 1%."
- ::= { acOuEntry 138 }
- acOu_139_Compressorstopdemand OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_138_Compressorstopdemand stored as 1%."
- ::= { acOuEntry 139 }
- acOu_140_Compressorminimumcapacity OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_139_Compressorminimumcapacity stored as 1%."
- ::= { acOuEntry 140 }
- acOu_141_Compressorstandardcapacity OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_140_Compressorstandardcapacity stored as 1%."
- ::= { acOuEntry 141 }
- acOu_142_Compressorstartupcapacity OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_141_Compressorstartupcapacity stored as 1%."
- ::= { acOuEntry 142 }
- acOu_143_Compressoroutputdeadzone OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_142_Compressoroutputdeadzone stored as 0.1%."
- ::= { acOuEntry 143 }
- acOu_144_Returncycle OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_143_Returncycle stored as 1h."
- ::= { acOuEntry 144 }
- acOu_145_Minimumfanspeed OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_144_Minimumfanspeed stored as 1%."
- ::= { acOuEntry 145 }
- acOu_146_Fanstandardspeed OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_145_Fanstandardspeed stored as 1%."
- ::= { acOuEntry 146 }
- acOu_147_MinimumfanspeedCFC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_146_MinimumfanspeedCFC stored as 1%."
- ::= { acOuEntry 147 }
- acOu_148_FanstandardspeedCFC OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_147_FanstandardspeedCFC stored as 1%."
- ::= { acOuEntry 148 }
- acOu_149_Lowspeedfanstep OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_148_Lowspeedfanstep stored as 0.1%s."
- ::= { acOuEntry 149 }
- acOu_150_Highspeedfanstep OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_149_Highspeedfanstep stored as 0.1%s."
- ::= { acOuEntry 150 }
- acOu_151_Fandecelerationdelay OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_150_Fandecelerationdelay stored as 1Sec."
- ::= { acOuEntry 151 }
- acOu_152_EEVsuperheatsettingMAX OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_151_EEVsuperheatsettingMAX stored as 1℃."
- ::= { acOuEntry 152 }
- acOu_153_EEVsuperheatsettingMIN OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_152_EEVsuperheatsettingMIN stored as 1℃."
- ::= { acOuEntry 153 }
- acOu_154_EEVMOPpressurelimit OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_153_EEVMOPpressurelimit stored as 1Bar."
- ::= { acOuEntry 154 }
- acOu_155_EEVvalvebodyshutoffsuperhe OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_154_EEVvalvebodyshutoffsuperhe stored as 1℃."
- ::= { acOuEntry 155 }
- acOu_156_Outdoorfanminimumsupplyvolt OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_155_Outdoorfanminimumsupplyvolt stored as 1%."
- ::= { acOuEntry 156 }
- acOu_157_Outdoorfanmaximumsupplyvolt OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_156_Outdoorfanmaximumsupplyvolt stored as 1%."
- ::= { acOuEntry 157 }
- acOu_158_Outdoorfanpressurecontrolra OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_157_Outdoorfanpressurecontrolra stored as 1Bar."
- ::= { acOuEntry 158 }
- acOu_159_Outdoorfanstartpressure OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_158_Outdoorfanstartpressure stored as 1Bar."
- ::= { acOuEntry 159 }
- acOu_160_Outdoorfanstartpressure OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "acOu_159_Outdoorfanstartpressure stored as 1Bar."
- ::= { acOuEntry 160 }
- ------------------------------------------------------------
- -- Accu { 13400.3.7 }
- ------------------------------------------------------------
- acc OBJECT IDENTIFIER ::= { dcs 7 }
- ------------------------------------------------------------
- -- Chd2100j5com { 13400.3.7.7008 }
- ------------------------------------------------------------
- acc-Chd2100j5com OBJECT IDENTIFIER ::= { acc 7008 }
- accChd2100j5comTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AccChd2100j5comEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "accChd2100j5comTable"
- ::= { acc-Chd2100j5com 1 }
- accChd2100j5comEntry OBJECT-TYPE
- SYNTAX AccChd2100j5comEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "accChd2100j5comEntry"
- INDEX { accChd2100j5comIndex }
- ::= { accChd2100j5comTable 1 }
- AccChd2100j5comEntry ::= SEQUENCE {
- accChd2100j5comIndex Integer32,
- accChd2100j5com_2_LogCount Integer32,
- accChd2100j5com_3_RealClock INTEGER,
- accChd2100j5com_4_Eerom INTEGER,
- accChd2100j5com_5_Power INTEGER,
- accChd2100j5com_6_DoorMonitor INTEGER,
- accChd2100j5com_7_OpenDoorRelayDrive INTEGER,
- accChd2100j5com_8_AccessAlarmStatus INTEGER,
- accChd2100j5com_9_DoorLockStatus INTEGER,
- accChd2100j5com_10_OutButtonStatus INTEGER,
- accChd2100j5com_11_GatingRelayDrive INTEGER,
- accChd2100j5com_12_DoorStatusMonitor INTEGER,
- accChd2100j5com_13_ManuallyLockTheDoor INTEGER,
- accChd2100j5com_14_DeviceType INTEGER,
- accChd2100j5com_15_DoorStatus INTEGER,
- accChd2100j5com_16_InfraredStatus INTEGER,
- accChd2100j5com_17_InfraredMonitoringStatus INTEGER,
- accChd2100j5com_18_DoorLable Integer32,
- accChd2100j5com_19_MaxNumberofDoorLockinCont Integer32,
- accChd2100j5com_20_PresentDoorLockNumber Integer32,
- accChd2100j5com_21_PresentDoorLockNumber Integer32,
- accChd2100j5com_22_RemoteOpenDoor INTEGER,
- accChd2100j5com_23_AddUser INTEGER,
- accChd2100j5com_24_DeleteUser INTEGER,
- accChd2100j5com_25_DeleteAllUser INTEGER,
- accChd2100j5com_26_SetTimeSection INTEGER,
- accChd2100j5com_27_SetTime INTEGER,
- accChd2100j5com_28_ReadLogCount INTEGER,
- accChd2100j5com_29_GetLog INTEGER,
- accChd2100j5com_30_UpdateUserInfo INTEGER,
- accChd2100j5com_31_QueryUserIDExist INTEGER,
- accChd2100j5com_32_QueryCardIDExist INTEGER,
- accChd2100j5com_33_SetAlwaysOpenTime INTEGER,
- accChd2100j5com_34_SetCardAndPasswordTime INTEGER,
- accChd2100j5com_35_SetInfraredMonitorTime INTEGER,
- accChd2100j5com_36_GetUserCount INTEGER,
- accChd2100j5com_37_GetAuthorizationList INTEGER,
- accChd2100j5com_38_CardAuthorization INTEGER,
- accChd2100j5com_39_DeleteUserCard INTEGER,
- accChd2100j5com_40_DeleteUserID INTEGER,
- accChd2100j5com_41_DeleteAllUser INTEGER,
- accChd2100j5com_42_Readversion INTEGER,
- accChd2100j5com_43_Addfingerprintusers INTEGER,
- accChd2100j5com_44_Readfingerprintusers INTEGER,
- accChd2100j5com_45_Deletefingerprintuser INTEGER,
- accChd2100j5com_46_Deletefingerprint INTEGER,
- accChd2100j5com_47_Startupsettingsfingerprint INTEGER,
- accChd2100j5com_48_Setfingerprint INTEGER,
- accChd2100j5com_49_Endsetfingerprint INTEGER,
- accChd2100j5com_50_Refreshfingerprintdata INTEGER,
- accChd2100j5com_51_Restorethefingerprintreader INTEGER,
- accChd2100j5com_52_Restorethefingerprintreader INTEGER,
- accChd2100j5com_53_SetRelayOpenTime INTEGER,
- accChd2100j5com_54_MonitorDoorStatus INTEGER,
- accChd2100j5com_55_NeedInputPassword INTEGER,
- accChd2100j5com_56_EnableManualButton INTEGER,
- accChd2100j5com_57_EnableKeyboardOpen INTEGER,
- accChd2100j5com_58_Setsingleordoublecarddoor INTEGER,
- accChd2100j5com_59_Infraredalarmconfirmationtim INTEGER,
- accChd2100j5com_60_Infraredmonitoringstatus INTEGER,
- accChd2100j5com_61_Magneticlevelsensor INTEGER,
- accChd2100j5com_62_Infraredsensorlevel INTEGER,
- accChd2100j5com_63_Entertheemergencyaction INTEGER,
- accChd2100j5com_64_ALARMoutputwhenthealarmact INTEGER,
- accChd2100j5com_65_Passwordtimecontrol INTEGER,
- accChd2100j5com_66_Doorcardpasswordtest INTEGER,
- accChd2100j5com_67_Checkoutcreditcardpassword INTEGER,
- accChd2100j5com_68_Tosetfingerprint1readeraddr Integer32,
- accChd2100j5com_69_Fingerprintreader1address INTEGER,
- accChd2100j5com_70_Addressfingerprintreader INTEGER,
- accChd2100j5com_71_Fingerprintreaderwork Integer32,
- accChd2100j5com_72_Fingerprintreaderwork Integer32 }
- accChd2100j5comIndex OBJECT-TYPE
- SYNTAX Integer32(1..72)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com System Entry Index."
- ::= { accChd2100j5comEntry 1 }
- accChd2100j5com_2_LogCount OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_1_LogCount stored as 1."
- ::= { accChd2100j5comEntry 2 }
- accChd2100j5com_3_RealClock OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- abnormal(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_2_RealClock status."
- ::= { accChd2100j5comEntry 3 }
- accChd2100j5com_4_Eerom OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- abnormal(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_3_Eerom status."
- ::= { accChd2100j5comEntry 4 }
- accChd2100j5com_5_Power OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- abnormal(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_4_Power status."
- ::= { accChd2100j5comEntry 5 }
- accChd2100j5com_6_DoorMonitor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_5_DoorMonitor status."
- ::= { accChd2100j5comEntry 6 }
- accChd2100j5com_7_OpenDoorRelayDrive OBJECT-TYPE
- SYNTAX INTEGER {
- release(0),
- drivers(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_6_OpenDoorRelayDrive status."
- ::= { accChd2100j5comEntry 7 }
- accChd2100j5com_8_AccessAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_7_AccessAlarmStatus status."
- ::= { accChd2100j5comEntry 8 }
- accChd2100j5com_9_DoorLockStatus OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_8_DoorLockStatus status."
- ::= { accChd2100j5comEntry 9 }
- accChd2100j5com_10_OutButtonStatus OBJECT-TYPE
- SYNTAX INTEGER {
- release(0),
- press(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_9_OutButtonStatus status."
- ::= { accChd2100j5comEntry 10 }
- accChd2100j5com_11_GatingRelayDrive OBJECT-TYPE
- SYNTAX INTEGER {
- release(0),
- drivers(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_10_GatingRelayDrive status."
- ::= { accChd2100j5comEntry 11 }
- accChd2100j5com_12_DoorStatusMonitor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_11_DoorStatusMonitor status."
- ::= { accChd2100j5comEntry 12 }
- accChd2100j5com_13_ManuallyLockTheDoor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_12_ManuallyLockTheDoor status."
- ::= { accChd2100j5comEntry 13 }
- accChd2100j5com_14_DeviceType OBJECT-TYPE
- SYNTAX INTEGER {
- unknowndevice(0),
- es2000(1),
- es5000(2),
- es5010(3),
- chd2100j3(4) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_13_DeviceType status."
- ::= { accChd2100j5comEntry 14 }
- accChd2100j5com_15_DoorStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- overtimeisnotclosed(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_14_DoorStatus status."
- ::= { accChd2100j5comEntry 15 }
- accChd2100j5com_16_InfraredStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_15_InfraredStatus status."
- ::= { accChd2100j5comEntry 16 }
- accChd2100j5com_17_InfraredMonitoringStatus OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_16_InfraredMonitoringStatus status."
- ::= { accChd2100j5comEntry 17 }
- accChd2100j5com_18_DoorLable OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_17_DoorLable stored as 1."
- ::= { accChd2100j5comEntry 18 }
- accChd2100j5com_19_MaxNumberofDoorLockinCont OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_18_MaxNumberofDoorLockinCont stored as 1."
- ::= { accChd2100j5comEntry 19 }
- accChd2100j5com_20_PresentDoorLockNumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_19_PresentDoorLockNumber stored as 1."
- ::= { accChd2100j5comEntry 20 }
- accChd2100j5com_21_PresentDoorLockNumber OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "accChd2100j5com_20_PresentDoorLockNumber stored as 1."
- ::= { accChd2100j5comEntry 21 }
- accChd2100j5com_22_RemoteOpenDoor OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_21_RemoteOpenDoor status."
- ::= { accChd2100j5comEntry 22 }
- accChd2100j5com_23_AddUser OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_22_AddUser status."
- ::= { accChd2100j5comEntry 23 }
- accChd2100j5com_24_DeleteUser OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_23_DeleteUser status."
- ::= { accChd2100j5comEntry 24 }
- accChd2100j5com_25_DeleteAllUser OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_24_DeleteAllUser status."
- ::= { accChd2100j5comEntry 25 }
- accChd2100j5com_26_SetTimeSection OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_25_SetTimeSection status."
- ::= { accChd2100j5comEntry 26 }
- accChd2100j5com_27_SetTime OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_26_SetTime status."
- ::= { accChd2100j5comEntry 27 }
- accChd2100j5com_28_ReadLogCount OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_27_ReadLogCount status."
- ::= { accChd2100j5comEntry 28 }
- accChd2100j5com_29_GetLog OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_28_GetLog status."
- ::= { accChd2100j5comEntry 29 }
- accChd2100j5com_30_UpdateUserInfo OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_29_UpdateUserInfo status."
- ::= { accChd2100j5comEntry 30 }
- accChd2100j5com_31_QueryUserIDExist OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_30_QueryUserIDExist status."
- ::= { accChd2100j5comEntry 31 }
- accChd2100j5com_32_QueryCardIDExist OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_31_QueryCardIDExist status."
- ::= { accChd2100j5comEntry 32 }
- accChd2100j5com_33_SetAlwaysOpenTime OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_32_SetAlwaysOpenTime status."
- ::= { accChd2100j5comEntry 33 }
- accChd2100j5com_34_SetCardAndPasswordTime OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_33_SetCardAndPasswordTime status."
- ::= { accChd2100j5comEntry 34 }
- accChd2100j5com_35_SetInfraredMonitorTime OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_34_SetInfraredMonitorTime status."
- ::= { accChd2100j5comEntry 35 }
- accChd2100j5com_36_GetUserCount OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_35_GetUserCount status."
- ::= { accChd2100j5comEntry 36 }
- accChd2100j5com_37_GetAuthorizationList OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_36_GetAuthorizationList status."
- ::= { accChd2100j5comEntry 37 }
- accChd2100j5com_38_CardAuthorization OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_37_CardAuthorization status."
- ::= { accChd2100j5comEntry 38 }
- accChd2100j5com_39_DeleteUserCard OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_38_DeleteUserCard status."
- ::= { accChd2100j5comEntry 39 }
- accChd2100j5com_40_DeleteUserID OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_39_DeleteUserID status."
- ::= { accChd2100j5comEntry 40 }
- accChd2100j5com_41_DeleteAllUser OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_40_DeleteAllUser status."
- ::= { accChd2100j5comEntry 41 }
- accChd2100j5com_42_Readversion OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_41_Readversion status."
- ::= { accChd2100j5comEntry 42 }
- accChd2100j5com_43_Addfingerprintusers OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_42_Addfingerprintusers status."
- ::= { accChd2100j5comEntry 43 }
- accChd2100j5com_44_Readfingerprintusers OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_43_Readfingerprintusers status."
- ::= { accChd2100j5comEntry 44 }
- accChd2100j5com_45_Deletefingerprintuser OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_44_Deletefingerprintuser status."
- ::= { accChd2100j5comEntry 45 }
- accChd2100j5com_46_Deletefingerprint OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_45_Deletefingerprint status."
- ::= { accChd2100j5comEntry 46 }
- accChd2100j5com_47_Startupsettingsfingerprint OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_46_Startupsettingsfingerprint status."
- ::= { accChd2100j5comEntry 47 }
- accChd2100j5com_48_Setfingerprint OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_47_Setfingerprint status."
- ::= { accChd2100j5comEntry 48 }
- accChd2100j5com_49_Endsetfingerprint OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_48_Endsetfingerprint status."
- ::= { accChd2100j5comEntry 49 }
- accChd2100j5com_50_Refreshfingerprintdata OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_49_Refreshfingerprintdata status."
- ::= { accChd2100j5comEntry 50 }
- accChd2100j5com_51_Restorethefingerprintreader OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_50_Restorethefingerprintreader status."
- ::= { accChd2100j5comEntry 51 }
- accChd2100j5com_52_Restorethefingerprintreader OBJECT-TYPE
- SYNTAX INTEGER {
- true(0) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_51_Restorethefingerprintreader status."
- ::= { accChd2100j5comEntry 52 }
- accChd2100j5com_53_SetRelayOpenTime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_52_SetRelayOpenTime stored as 1s."
- ::= { accChd2100j5comEntry 53 }
- accChd2100j5com_54_MonitorDoorStatus OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_53_MonitorDoorStatus status."
- ::= { accChd2100j5comEntry 54 }
- accChd2100j5com_55_NeedInputPassword OBJECT-TYPE
- SYNTAX INTEGER {
- notneed(0),
- need(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_54_NeedInputPassword status."
- ::= { accChd2100j5comEntry 55 }
- accChd2100j5com_56_EnableManualButton OBJECT-TYPE
- SYNTAX INTEGER {
- open(0),
- close(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_55_EnableManualButton status."
- ::= { accChd2100j5comEntry 56 }
- accChd2100j5com_57_EnableKeyboardOpen OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_56_EnableKeyboardOpen status."
- ::= { accChd2100j5comEntry 57 }
- accChd2100j5com_58_Setsingleordoublecarddoor OBJECT-TYPE
- SYNTAX INTEGER {
- singlecard(0),
- doublecard(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_57_Setsingleordoublecarddoor status."
- ::= { accChd2100j5comEntry 58 }
- accChd2100j5com_59_Infraredalarmconfirmationtim OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_58_Infraredalarmconfirmationtim stored as 1s."
- ::= { accChd2100j5comEntry 59 }
- accChd2100j5com_60_Infraredmonitoringstatus OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_59_Infraredmonitoringstatus status."
- ::= { accChd2100j5comEntry 60 }
- accChd2100j5com_61_Magneticlevelsensor OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_60_Magneticlevelsensor status."
- ::= { accChd2100j5comEntry 61 }
- accChd2100j5com_62_Infraredsensorlevel OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_61_Infraredsensorlevel status."
- ::= { accChd2100j5comEntry 62 }
- accChd2100j5com_63_Entertheemergencyaction OBJECT-TYPE
- SYNTAX INTEGER {
- open(0),
- close(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_62_Entertheemergencyaction status."
- ::= { accChd2100j5comEntry 63 }
- accChd2100j5com_64_ALARMoutputwhenthealarmact OBJECT-TYPE
- SYNTAX INTEGER {
- close(0),
- open(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_63_ALARMoutputwhenthealarmact status."
- ::= { accChd2100j5comEntry 64 }
- accChd2100j5com_65_Passwordtimecontrol OBJECT-TYPE
- SYNTAX INTEGER {
- alwaysneed(0),
- bytime(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_64_Passwordtimecontrol status."
- ::= { accChd2100j5comEntry 65 }
- accChd2100j5com_66_Doorcardpasswordtest OBJECT-TYPE
- SYNTAX INTEGER {
- notneed(0),
- need(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_65_Doorcardpasswordtest status."
- ::= { accChd2100j5comEntry 66 }
- accChd2100j5com_67_Checkoutcreditcardpassword OBJECT-TYPE
- SYNTAX INTEGER {
- notneed(0),
- need(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_66_Checkoutcreditcardpassword status."
- ::= { accChd2100j5comEntry 67 }
- accChd2100j5com_68_Tosetfingerprint1readeraddr OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_67_Tosetfingerprint1readeraddr stored as 1."
- ::= { accChd2100j5comEntry 68 }
- accChd2100j5com_69_Fingerprintreader1address OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_68_Fingerprintreader1address stored as 1."
- ::= { accChd2100j5comEntry 69 }
- accChd2100j5com_70_Addressfingerprintreader OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_69_Addressfingerprintreader stored as 1."
- ::= { accChd2100j5comEntry 70 }
- accChd2100j5com_71_Fingerprintreaderwork OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_70_Fingerprintreaderwork stored as 1."
- ::= { accChd2100j5comEntry 71 }
- accChd2100j5com_72_Fingerprintreaderwork OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "accChd2100j5com_71_Fingerprintreaderwork stored as 1."
- ::= { accChd2100j5comEntry 72 }
- ------------------------------------------------------------
- -- Firefighting { 13400.3.5.559 }
- ------------------------------------------------------------
- env-Firefighting OBJECT IDENTIFIER ::= { env 559 }
- envFirefightingTable OBJECT-TYPE
- SYNTAX SEQUENCE OF EnvFirefightingEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "envFirefightingTable"
- ::= { env-Firefighting 1 }
- envFirefightingEntry OBJECT-TYPE
- SYNTAX EnvFirefightingEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "envFirefightingEntry"
- INDEX { envFirefightingIndex }
- ::= { envFirefightingTable 1 }
- EnvFirefightingEntry ::= SEQUENCE {
- envFirefightingIndex Integer32,
- envFirefighting_2_FireAlarmStatus INTEGER,
- envFirefighting_3_FireSensor4DICommStatus INTEGER,
- envFirefighting_4_FireAlarmStausAlarmCriterio INTEGER }
- envFirefightingIndex OBJECT-TYPE
- SYNTAX Integer32(1..4)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envFirefighting System Entry Index."
- ::= { envFirefightingEntry 1 }
- envFirefighting_2_FireAlarmStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- alarm(1),
- uninstalled(2),
- leave(3) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envFirefighting_1_FireAlarmStatus status."
- ::= { envFirefightingEntry 2 }
- envFirefighting_3_FireSensor4DICommStatus OBJECT-TYPE
- SYNTAX INTEGER {
- normal(0),
- failure(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "envFirefighting_2_FireSensor4DICommStatus status."
- ::= { envFirefightingEntry 3 }
- envFirefighting_4_FireAlarmStausAlarmCriterio OBJECT-TYPE
- SYNTAX INTEGER {
- open(0),
- close(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "envFirefighting_3_FireAlarmStausAlarmCriterio status."
- ::= { envFirefightingEntry 4 }
- ------------------------------------------------------------
- -- System Alarm Trap Table { 13400.3.254 }
- ------------------------------------------------------------
- systemAlarmTrapTable OBJECT-TYPE
- SYNTAX SEQUENCE OF SystemAlarmTrapEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "System Table holding information about the submitted alarm traps."
- ::= { dcs 254 }
- systemAlarmTrapEntry OBJECT-TYPE
- SYNTAX SystemAlarmTrapEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION "An entry (conceptual row) in the systemAlarmTrapTable."
- INDEX { systemAlarmIndex }
- ::= { systemAlarmTrapTable 1 }
- SystemAlarmTrapEntry ::= SEQUENCE {
- systemAlarmIndex Counter32,
- systemAlarmTime DisplayString,
- systemAlarmStatusChange AlarmStatusChange,
- systemAlarmSeverity AlarmSeverity,
- systemAlarmDescription DisplayString,
- systemAlarmId Integer32,
- systemAlarmEquipId Integer32,
- systemAlarmEquipTypeId Integer32}
- systemAlarmIndex OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "The unique sequence number of this alarm trap."
- ::= { systemAlarmTrapEntry 1 }
- systemAlarmTime OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Local date and time when event occured, format as YYYY-MM-DD hh:mm:ss."
- ::= { systemAlarmTrapEntry 2 }
- systemAlarmStatusChange OBJECT-TYPE
- SYNTAX AlarmStatusChange
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Indicates 'activated' (0) or 'deactivated' (1) alarm events."
- ::= { systemAlarmTrapEntry 3 }
- systemAlarmSeverity OBJECT-TYPE
- SYNTAX AlarmSeverity
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "The severity of the alarm. One of
- (1) informational
- (2) warning
- (3) critical"
- ::= { systemAlarmTrapEntry 4 }
- systemAlarmDescription OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Free-text description of alarm."
- ::= { systemAlarmTrapEntry 5 }
- systemAlarmId OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Alarm id."
- ::= { systemAlarmTrapEntry 6 }
- systemAlarmEquipId OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Alarm equipment id."
- ::= { systemAlarmTrapEntry 7 }
- systemAlarmEquipTypeId OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION "Alarm equipment type id."
- ::= { systemAlarmTrapEntry 8 }
- ------------------------------------------------------------
- -- System Alarm Trap { 13400.3.255 }
- ------------------------------------------------------------
- systemAlarmTrap OBJECT IDENTIFIER ::= { dcs 255 }
- systemAlarmTrapDefine NOTIFICATION-TYPE
- OBJECTS {
- systemAlarmIndex,
- systemAlarmTime,
- systemAlarmStatusChange,
- systemAlarmSeverity,
- systemAlarmDescription,
- systemAlarmId,
- systemAlarmEquipId,
- systemAlarmEquipTypeId }
- STATUS current
- DESCRIPTION "
- An alarm trap is sent when an alarm occurs (activated) or
- returns to normal state (deactivated). Alarm traps are logged
- in alarmTrapTable. Variables in this trap:
- * systemAlarmIndex - The unique sequence number of this alarm trap.
- * systemAlarmTime - Date and time when event occured (local time).
- * systemAlarmStatusChange - (0) activated or (1) deactivated.
- * systemAlarmSeverity - The severity of the alarm..
- * systemAlarmId - Alarm id.
- * systemAlarmEquipId - Alarm equipment id.
- * systemAlarmEquipTypeId - Alarm equipment type id."
- ::= { systemAlarmTrap 1 }
- ------------------------------------------------------------
- -- End of MIB definitions
- ------------------------------------------------------------
- END