- -- GE Management Information Base VERSION 1.04
- --
- -- Date: 11/10/2004
- -- Changes: remove of "_" in snmp identifiers, remove of duplicate comment characters
- -- Author : MHCL
- --
- -- Date 02/14/2005
- -- Changes: remove additional size definition for DisplayString
- -- Changes: remove additional range definition of PositiveInteger32
- -- Changes: change of range definition for Integer32 entries
- -- Changes: changed names of managed UPSs so that tablenames end with 'table'
- -- without changes of other structures
- -- Changes: changed some Capital-/Lowercase issues
- -- Author : MHCL
- --
- -- Date: 15/11/2006
- -- Changes: added BatterRipple
- -- Changes: added OutputPowerFactor; OutputPeakCurrent; OutputShareCurrent
- -- Changes: added alarm HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
- -- Changes: added traps HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
- -- Changes: added traps HighpeedBusrestore; HighpeedBusCRCrestore; ConnectivityBusrestore
- -- Changes: added group Diagnostic
- -- Changes: added BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
- -- GlobalServiceCheck
- -- Changes: added Status ServiceCheck
- -- Deleted: geEnvironmental tree
- -- Deleted: geModem tree
- -- Deleted: geDevices tree
- -- Deleted: geSoftware tree
- -- Author: GE, Stefan Kuhn
- --
- -- Date: 25/11/2006
- -- Changes: upsDiagnosticGlobalServiceChecke Syntax from DisplayString to Integer32
- -- Changes: upsDiagnosticGlobalServiceChecke into upsDiagnosticGlobalServiceCheck
- -- Author: GE, Stefan Kuhn
- --
- -- Date: 27/11/2006
- -- added: upsDiagnosticBusJACommunicationStatus
- -- added: upsDiagnosticBusJBCommunicationStatus
- -- Moved: BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
- -- GlobalServiceCheck
- -- Author: GE, Stefan Kuhn
- --
- -- Date: 10/12/2006
- -- modified: upsSecondsOnBattery from NonNegativeInteger32 back to Integer32
- -- for the backward compatibility
- -- added: upsAlarmHighSpeedBusJACRCFailure,upsAlarmHighSpeedBusJBCRCFailure,upsAlarmShareCurrent,
- -- upsAlarmDCRipple and there relative traps
- -- Author: GE, Stefan Kuhn
- --
- -- Date: 22/Oct/2007
- -- added: geDevices group
- -- Author: GE, L. Giuntini
- --
- -- Date: Feb 13th, 2008
- -- Author: GE, L. Giuntini
- -- Created version 2.00 for SMIv2 compliance
- -- Changes include the following:
- -- * MODULE-IDENTITY clause introduced right after the IMPORT statement
- -- * Compliance to RFC2578, section 7.1.1, second paragraph
- -- in case of enumerations, use INTEGER rather than Integer32
- -- * Replace MAX-ACCESS read-only with MAX-ACCESS read-write
- -- (access `read-write' is no longer allowed in SMIv2)
- -- * Use NOTIFICATION-TYPE instead of TRAP-TYPE for Traps
- -- Remove ENTERPRISE clause
- -- Rename VARIABLES clause as OBJECTS clause
- -- Add STATUS current clause
- -- Incorporate traps in the Object tree
- -- * Finally, corrected some errors (undefined/re-defined identifiers)
- --
- -- Date: Jul 5th, 2010
- -- Author: GE, L. Giuntini
- -- Created version 2.40 for IEMi / eBoost introduction
- -- Modified:
- -- * Description (Properties) for the upsStatus, upsUPSMode OIDs
- -- * Various changes to ensure full SNMP v2 compliance
- --
- -- GE-MIB
- -- { iso org(3) dod(6) internet(1) private(4) enterprises(1) imv(818) }
- --
- -- Title: GE-MIB
- -- By: Theo Versteeg & Fontana Gianluca
- --
- -- 11-5-00 Theo Versteeg
- -- Removed the complete Victron-MIB to create a new IMV-mib to cover Comprot4,
- -- IM and IMV1 protocol.
- -- incl. external devices and object for the agents and protection software.
- --
- -- Entries marked with (*) are part of the RFC1628 definition
- -- Although we integrated the RFC1628 in our own OID range,
- -- all RCF1628 OIDs should also be accessable on their own OID defined in RFC1628.
- GEPARALLELUPS-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
- OBJECT-IDENTITY, Counter32, Gauge32, Integer32, Unsigned32, enterprises
- FROM SNMPv2-SMI
- DisplayString, TimeStamp, TimeInterval, TestAndIncr,
- AutonomousType, TEXTUAL-CONVENTION
- FROM SNMPv2-TC;
- imv MODULE-IDENTITY
- LAST-UPDATED "201007050000Z"
- ORGANIZATION "GE Digital Energy"
- CONTACT-INFO
- "GE Digital Energy
- Via Cantonale, 50
- CH 6595 Riazzino
- Switzerland"
- DESCRIPTION
- "The MIB module to describe GE Digital Energy
- Uninterruptible Power Supplies."
- REVISION "201007050000Z"
- DESCRIPTION
- "Updated following IEMi & eBoost introduction."
- REVISION "200801080000Z"
- DESCRIPTION
- "SNMPv2 compliant MIB released."
- ::= { enterprises 818 }
- PositiveInteger32 ::= TEXTUAL-CONVENTION
- DISPLAY-HINT "d"
- STATUS current
- DESCRIPTION
- "This data type is a non-zero and non-negative value."
- SYNTAX Integer32 (1..2147483647)
- NonNegativeInteger32 ::= TEXTUAL-CONVENTION
- DISPLAY-HINT "d"
- STATUS current
- DESCRIPTION
- "This data type is a non-negative value."
- SYNTAX Integer32 (0..2147483647)
- geHardware OBJECT IDENTIFIER ::= { imv 1 }
- geUPS OBJECT IDENTIFIER ::= { geHardware 1 }
- -- The following list is not really a table, but can be implemented as one in the software.
- -- The complete UPS section is simply too large to fit in a pre-defined table.
- -- The solution:
- -- * All objects are defined for geGenericUPS
- -- * All individual UPSs of parallel systems can be reached by their respective sequence
- -- number as reflected in below list in stead of the geGenericUPS objects.
- geGenericUPS OBJECT IDENTIFIER ::= { geUPS 10 }
- geFirstUPS OBJECT IDENTIFIER ::= { geUPS 11 }
- geSecondUPS OBJECT IDENTIFIER ::= { geUPS 12 }
- geThirdUPS OBJECT IDENTIFIER ::= { geUPS 13 }
- geFourthUPS OBJECT IDENTIFIER ::= { geUPS 14 }
- geFifthUPS OBJECT IDENTIFIER ::= { geUPS 15 }
- geSixthUPS OBJECT IDENTIFIER ::= { geUPS 16 }
- geSeventhUPS OBJECT IDENTIFIER ::= { geUPS 17 }
- geEighthUPS OBJECT IDENTIFIER ::= { geUPS 18 }
- -- Generic UPS
- upsIdent OBJECT IDENTIFIER ::= { geGenericUPS 1 }
- upsBattery OBJECT IDENTIFIER ::= { geGenericUPS 2 }
- upsInput OBJECT IDENTIFIER ::= { geGenericUPS 3 }
- upsOutput OBJECT IDENTIFIER ::= { geGenericUPS 4 }
- upsBypass OBJECT IDENTIFIER ::= { geGenericUPS 5 }
- upsAlarm OBJECT IDENTIFIER ::= { geGenericUPS 6 }
- upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
- upsTest OBJECT IDENTIFIER ::= { geGenericUPS 7 }
- upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 }
- upsControl OBJECT IDENTIFIER ::= { geGenericUPS 8 }
- upsConfig OBJECT IDENTIFIER ::= { geGenericUPS 9 }
- upsGetSet OBJECT IDENTIFIER ::= { geGenericUPS 10 }
- geUPSTraps OBJECT IDENTIFIER ::= { geGenericUPS 11 }
- upsDiagnostic OBJECT IDENTIFIER ::= { geGenericUPS 12 }
- -- First UPS --
- upsIdentfirst OBJECT IDENTIFIER ::= { geFirstUPS 1 }
- upsBatteryfirst OBJECT IDENTIFIER ::= { geFirstUPS 2 }
- upsInputfirst OBJECT IDENTIFIER ::= { geFirstUPS 3 }
- upsOutputfirst OBJECT IDENTIFIER ::= { geFirstUPS 4 }
- upsBypassfirst OBJECT IDENTIFIER ::= { geFirstUPS 5 }
- upsAlarmfirst OBJECT IDENTIFIER ::= { geFirstUPS 6 }
- upsWellKnownAlarmsfirst OBJECT IDENTIFIER ::= { upsAlarmfirst 3 }
- upsTestfirst OBJECT IDENTIFIER ::= { geFirstUPS 7 }
- upsWellKnownTestsfirst OBJECT IDENTIFIER ::= { upsTestfirst 7 }
- upsControlfirst OBJECT IDENTIFIER ::= { geFirstUPS 8 }
- upsConfigfirst OBJECT IDENTIFIER ::= { geFirstUPS 9 }
- upsGetSetfirst OBJECT IDENTIFIER ::= { geFirstUPS 10 }
- geUPSTrapsfirst OBJECT IDENTIFIER ::= { geFirstUPS 11 }
- upsDiagnosticfirst OBJECT IDENTIFIER ::= { geFirstUPS 12 }
- -- Second UPS --
- upsIdentsecond OBJECT IDENTIFIER ::= { geSecondUPS 1 }
- upsBatterysecond OBJECT IDENTIFIER ::= { geSecondUPS 2 }
- upsInputsecond OBJECT IDENTIFIER ::= { geSecondUPS 3 }
- upsOutputsecond OBJECT IDENTIFIER ::= { geSecondUPS 4 }
- upsBypasssecond OBJECT IDENTIFIER ::= { geSecondUPS 5 }
- upsAlarmsecond OBJECT IDENTIFIER ::= { geSecondUPS 6 }
- upsWellKnownAlarmssecond OBJECT IDENTIFIER ::= { upsAlarmsecond 3 }
- upsTestsecond OBJECT IDENTIFIER ::= { geSecondUPS 7 }
- upsWellKnownTestssecond OBJECT IDENTIFIER ::= { upsTestsecond 7 }
- upsControlsecond OBJECT IDENTIFIER ::= { geSecondUPS 8 }
- upsConfigsecond OBJECT IDENTIFIER ::= { geSecondUPS 9 }
- upsGetSetsecond OBJECT IDENTIFIER ::= { geSecondUPS 10 }
- geUPSTrapssecond OBJECT IDENTIFIER ::= { geSecondUPS 11 }
- upsDiagnosticsecond OBJECT IDENTIFIER ::= { geSecondUPS 12 }
- -- Third UPS --
- upsIdentthird OBJECT IDENTIFIER ::= { geThirdUPS 1 }
- upsBatterythird OBJECT IDENTIFIER ::= { geThirdUPS 2 }
- upsInputthird OBJECT IDENTIFIER ::= { geThirdUPS 3 }
- upsOutputthird OBJECT IDENTIFIER ::= { geThirdUPS 4 }
- upsBypassthird OBJECT IDENTIFIER ::= { geThirdUPS 5 }
- upsAlarmthird OBJECT IDENTIFIER ::= { geThirdUPS 6 }
- upsWellKnownAlarmsthird OBJECT IDENTIFIER ::= { upsAlarmthird 3 }
- upsTestthird OBJECT IDENTIFIER ::= { geThirdUPS 7 }
- upsWellKnownTeststhird OBJECT IDENTIFIER ::= { upsTestthird 7 }
- upsControlthird OBJECT IDENTIFIER ::= { geThirdUPS 8 }
- upsConfigthird OBJECT IDENTIFIER ::= { geThirdUPS 9 }
- upsGetSetthird OBJECT IDENTIFIER ::= { geThirdUPS 10 }
- geUPSTrapsthird OBJECT IDENTIFIER ::= { geThirdUPS 11 }
- upsDiagnosticthird OBJECT IDENTIFIER ::= { geThirdUPS 12 }
- -- Fourth UPS --
- upsIdentfourth OBJECT IDENTIFIER ::= { geFourthUPS 1 }
- upsBatteryfourth OBJECT IDENTIFIER ::= { geFourthUPS 2 }
- upsInputfourth OBJECT IDENTIFIER ::= { geFourthUPS 3 }
- upsOutputfourth OBJECT IDENTIFIER ::= { geFourthUPS 4 }
- upsBypassfourth OBJECT IDENTIFIER ::= { geFourthUPS 5 }
- upsAlarmfourth OBJECT IDENTIFIER ::= { geFourthUPS 6 }
- upsWellKnownAlarmsfourth OBJECT IDENTIFIER ::= { upsAlarmfourth 3 }
- upsTestfourth OBJECT IDENTIFIER ::= { geFourthUPS 7 }
- upsWellKnownTestsfourth OBJECT IDENTIFIER ::= { upsTestfourth 7 }
- upsControlfourth OBJECT IDENTIFIER ::= { geFourthUPS 8 }
- upsConfigfourth OBJECT IDENTIFIER ::= { geFourthUPS 9 }
- upsGetSetfourth OBJECT IDENTIFIER ::= { geFourthUPS 10 }
- geUPSTrapsfourth OBJECT IDENTIFIER ::= { geFourthUPS 11 }
- upsDiagnosticfourth OBJECT IDENTIFIER ::= { geFourthUPS 12 }
- -- Fifth UPS --
- upsIdentfifth OBJECT IDENTIFIER ::= { geFifthUPS 1 }
- upsBatteryfifth OBJECT IDENTIFIER ::= { geFifthUPS 2 }
- upsInputfifth OBJECT IDENTIFIER ::= { geFifthUPS 3 }
- upsOutputfifth OBJECT IDENTIFIER ::= { geFifthUPS 4 }
- upsBypassfifth OBJECT IDENTIFIER ::= { geFifthUPS 5 }
- upsAlarmfifth OBJECT IDENTIFIER ::= { geFifthUPS 6 }
- upsWellKnownAlarmsfifth OBJECT IDENTIFIER ::= { upsAlarmfifth 3 }
- upsTestfifth OBJECT IDENTIFIER ::= { geFifthUPS 7 }
- upsWellKnownTestsfifth OBJECT IDENTIFIER ::= { upsTestfifth 7 }
- upsControlfifth OBJECT IDENTIFIER ::= { geFifthUPS 8 }
- upsConfigfifth OBJECT IDENTIFIER ::= { geFifthUPS 9 }
- upsGetSetfifth OBJECT IDENTIFIER ::= { geFifthUPS 10 }
- geUPSTrapsfifth OBJECT IDENTIFIER ::= { geFifthUPS 11 }
- upsDiagnosticfifth OBJECT IDENTIFIER ::= { geFifthUPS 12 }
- -- Sixth UPS --
- upsIdentsixth OBJECT IDENTIFIER ::= { geSixthUPS 1 }
- upsBatterysixth OBJECT IDENTIFIER ::= { geSixthUPS 2 }
- upsInputsixth OBJECT IDENTIFIER ::= { geSixthUPS 3 }
- upsOutputsixth OBJECT IDENTIFIER ::= { geSixthUPS 4 }
- upsBypasssixth OBJECT IDENTIFIER ::= { geSixthUPS 5 }
- upsAlarmsixth OBJECT IDENTIFIER ::= { geSixthUPS 6 }
- upsWellKnownAlarmssixth OBJECT IDENTIFIER ::= { upsAlarmsixth 3 }
- upsTestsixth OBJECT IDENTIFIER ::= { geSixthUPS 7 }
- upsWellKnownTestssixth OBJECT IDENTIFIER ::= { upsTestsixth 7 }
- upsControlsixth OBJECT IDENTIFIER ::= { geSixthUPS 8 }
- upsConfigsixth OBJECT IDENTIFIER ::= { geSixthUPS 9 }
- upsGetSetsixth OBJECT IDENTIFIER ::= { geSixthUPS 10 }
- geUPSTrapssixth OBJECT IDENTIFIER ::= { geSixthUPS 11 }
- upsDiagnosticsixth OBJECT IDENTIFIER ::= { geSixthUPS 12 }
- -- Seventh UPS --
- upsIdentseventh OBJECT IDENTIFIER ::= { geSeventhUPS 1 }
- upsBatteryseventh OBJECT IDENTIFIER ::= { geSeventhUPS 2 }
- upsInputseventh OBJECT IDENTIFIER ::= { geSeventhUPS 3 }
- upsOutputseventh OBJECT IDENTIFIER ::= { geSeventhUPS 4 }
- upsBypassseventh OBJECT IDENTIFIER ::= { geSeventhUPS 5 }
- upsAlarmseventh OBJECT IDENTIFIER ::= { geSeventhUPS 6 }
- upsWellKnownAlarmsseventh OBJECT IDENTIFIER ::= { upsAlarmseventh 3 }
- upsTestseventh OBJECT IDENTIFIER ::= { geSeventhUPS 7 }
- upsWellKnownTestsseventh OBJECT IDENTIFIER ::= { upsTestseventh 7 }
- upsControlseventh OBJECT IDENTIFIER ::= { geSeventhUPS 8 }
- upsConfigseventh OBJECT IDENTIFIER ::= { geSeventhUPS 9 }
- upsGetSetseventh OBJECT IDENTIFIER ::= { geSeventhUPS 10 }
- geUPSTrapsseventh OBJECT IDENTIFIER ::= { geSeventhUPS 11 }
- upsDiagnosticseventh OBJECT IDENTIFIER ::= { geSeventhUPS 12 }
- -- Eighth UPS --
- upsIdenteighth OBJECT IDENTIFIER ::= { geEighthUPS 1 }
- upsBatteryeighth OBJECT IDENTIFIER ::= { geEighthUPS 2 }
- upsInputeighth OBJECT IDENTIFIER ::= { geEighthUPS 3 }
- upsOutputeighth OBJECT IDENTIFIER ::= { geEighthUPS 4 }
- upsBypasseighth OBJECT IDENTIFIER ::= { geEighthUPS 5 }
- upsAlarmeighth OBJECT IDENTIFIER ::= { geEighthUPS 6 }
- upsWellKnownAlarmseighth OBJECT IDENTIFIER ::= { upsAlarmeighth 3 }
- upsTesteighth OBJECT IDENTIFIER ::= { geEighthUPS 7 }
- upsWellKnownTestseighth OBJECT IDENTIFIER ::= { upsTesteighth 7 }
- upsControleighth OBJECT IDENTIFIER ::= { geEighthUPS 8 }
- upsConfigeighth OBJECT IDENTIFIER ::= { geEighthUPS 9 }
- upsGetSeteighth OBJECT IDENTIFIER ::= { geEighthUPS 10 }
- geUPSTrapseighth OBJECT IDENTIFIER ::= { geEighthUPS 11 }
- upsDiagnosticeighth OBJECT IDENTIFIER ::= { geEighthUPS 12 }
- -- Device
- geDevices OBJECT IDENTIFIER ::= { geHardware 100 }
- geDevicesDescriptions OBJECT IDENTIFIER ::= { geDevices 1 }
- advSNMPWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 1 }
- snmpWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 2 }
- snmpWebIntBox OBJECT IDENTIFIER ::= { geDevicesDescriptions 3 }
- --
- -- The GE UPS group
- --
- geDiscoveredUPSsMask OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Reading this variable returns bit mask indicating which
- UPSs in a parallel system are alive. Management
- software should poll only these UPSs on their snmp
- branches 11-18 as follows:
- 1 FirstUPS alive
- 2 SecondUPS alive
- 4 ThirdUPS alive
- 8 FourthUPS alive
- 16 FifthUPS alive
- 32 SixthUPS alive
- 64 SeventhUPS alive
- 128 EigthUPS alive
- Since the management software should always monitor
- the GenericUPS branch (10), this value has no meaning
- for single upses (which provide values on that snmp
- branch), and should be set to zero in that case."
- ::= { geUPS 1 }
- geRequestPacket OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus.
- This OID could be used for accede directly to the internally RS485 bus from a remote place."
- ::= { geUPS 2 }
- geReplyPacket OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket.
- Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased."
- ::= { geUPS 3 }
- --
- -- The Device Identification group. Generic
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturer OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdent 1 }
- upsIdentModel OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdent 2 }
- upsIdentUPSSoftwareVersion OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdent 3 }
- upsIdentAgentSoftwareVersion OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdent 4 }
- upsIdentName OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdent 5 }
- upsIdentAttachedDevices OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdent 6 }
- upsIdentUPSSerialNumber OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdent 7 }
- upsIdentComProtVersion OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdent 8 }
- upsIdentOperatingTime OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdent 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatus OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBattery 1 }
- upsSecondsOnBattery OBJECT-TYPE
- SYNTAX Integer32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBattery 2 }
- upsEstimatedMinutesRemaining OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBattery 3 }
- upsEstimatedChargeRemaining OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBattery 4 }
- upsBatteryVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBattery 5 }
- upsBatteryCurrent OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBattery 6 }
- upsBatteryTemperature OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBattery 7 }
- upsBatteryRipple OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBattery 8 }
- --
- -- Input Group
- --
- upsInputLineBads OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInput 1 }
- upsInputNumLines OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInput 2 }
- upsInputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInput 3 }
- upsInputEntry OBJECT-TYPE
- SYNTAX UpsInputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndex }
- ::= { upsInputTable 1 }
- UpsInputEntry ::= SEQUENCE {
- upsInputLineIndex PositiveInteger32,
- upsInputFrequency NonNegativeInteger32,
- upsInputVoltage NonNegativeInteger32,
- upsInputCurrent NonNegativeInteger32,
- upsInputTruePower NonNegativeInteger32,
- upsInputVoltageMin NonNegativeInteger32,
- upsInputVoltageMax NonNegativeInteger32
- }
- upsInputLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputEntry 1 }
- upsInputFrequency OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputEntry 2 }
- upsInputVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputEntry 3 }
- upsInputCurrent OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputEntry 4 }
- upsInputTruePower OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputEntry 5 }
- upsInputVoltageMin OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputEntry 6 }
- upsInputVoltageMax OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSource OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutput 1 }
- upsOutputFrequency OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutput 2 }
- upsOutputNumLines OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutput 3 }
- upsOutputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutput 4 }
- upsOutputEntry OBJECT-TYPE
- SYNTAX UpsOutputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndex }
- ::= { upsOutputTable 1 }
- UpsOutputEntry ::= SEQUENCE {
- upsOutputLineIndex PositiveInteger32,
- upsOutputVoltage NonNegativeInteger32,
- upsOutputCurrent NonNegativeInteger32,
- upsOutputPower NonNegativeInteger32,
- upsOutputPercentLoad Integer32,
- upsOutputPowerFactor Integer32,
- upsOutputPeakCurrent Integer32,
- upsOutputShareCurrent Integer32
- }
- upsOutputLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputEntry 1 }
- upsOutputVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputEntry 2 }
- upsOutputCurrent OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputEntry 3 }
- upsOutputPower OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputEntry 4 }
- upsOutputPercentLoad OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputEntry 5 }
- upsOutputPowerFactor OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputEntry 6 }
- upsOutputPeakCurrent OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputEntry 7 }
- upsOutputShareCurrent OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequency OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypass 1 }
- upsBypassNumLines OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypass 2 }
- upsBypassTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypass 3 }
- upsBypassEntry OBJECT-TYPE
- SYNTAX UpsBypassEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndex }
- ::= { upsBypassTable 1 }
- UpsBypassEntry ::= SEQUENCE {
- upsBypassLineIndex PositiveInteger32,
- upsBypassVoltage NonNegativeInteger32,
- upsBypassCurrent NonNegativeInteger32,
- upsBypassPower NonNegativeInteger32
- }
- upsBypassLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassEntry 1 }
- upsBypassVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassEntry 2 }
- upsBypassCurrent OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassEntry 3 }
- upsBypassPower OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresent OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarm 1 }
- upsAlarmTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarm 2 }
- upsAlarmEntry OBJECT-TYPE
- SYNTAX UpsAlarmEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmId }
- ::= { upsAlarmTable 1 }
- UpsAlarmEntry ::= SEQUENCE {
- upsAlarmId PositiveInteger32,
- upsAlarmDescr AutonomousType,
- upsAlarmTime TimeStamp
- }
- upsAlarmId OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmEntry 1 }
- upsAlarmDescr OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmEntry 2 }
- upsAlarmTime OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBad OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarms 1 }
- upsAlarmOnBattery OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarms 2 }
- upsAlarmLowBattery OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarms 3 }
- upsAlarmDepletedBattery OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarms 4 }
- upsAlarmTempBad OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarms 5 }
- upsAlarmInputBad OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarms 6 }
- upsAlarmOutputBad OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarms 7 }
- upsAlarmOutputOverload OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarms 8 }
- upsAlarmOnBypass OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarms 9 }
- upsAlarmBypassBad OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarms 10 }
- upsAlarmOutputOffAsRequested OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarms 11 }
- upsAlarmUpsOffAsRequested OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarms 12 }
- upsAlarmChargerFailed OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarms 13 }
- upsAlarmUpsOutputOff OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarms 14 }
- upsAlarmUpsSystemOff OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarms 15 }
- upsAlarmFanFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarms 16 }
- upsAlarmFuseFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarms 17 }
- upsAlarmGeneralFault OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarms 18 }
- upsAlarmDiagnosticTestFailed OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarms 19 }
- upsAlarmCommunicationsLost OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarms 20 }
- upsAlarmAwaitingPower OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarms 21 }
- upsAlarmShutdownPending OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarms 22 }
- upsAlarmShutdownImminent OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarms 23 }
- upsAlarmTestInProgress OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarms 24 }
- upsAlarmReceptacleOff OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarms 25 }
- upsAlarmHighSpeedBusFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarms 26 }
- upsAlarmHighSpeedBusJACRCFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A CRC problem on the Highspeed Bus JA is detected."
- ::= { upsWellKnownAlarms 27 }
- upsAlarmConnectivityBusFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { upsWellKnownAlarms 28 }
- upsAlarmHighSpeedBusJBCRCFailure OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A CRC problem on the Highspeed Bus JB is detected."
- ::= { upsWellKnownAlarms 29 }
- upsAlarmCurrentSharing OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The System detects an high current sharing on the parallel system"
- ::= { upsWellKnownAlarms 30 }
- upsAlarmDCRipple OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The System detects an high ripple voltage on one DC link"
- ::= { upsWellKnownAlarms 31 }
- upsAlarmMaskA OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarm 4 }
- --
- -- The Test Group generic
- --
- upsTestId OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTest 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLock OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTest 2 }
- upsTestResultsSummary OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTest 3 }
- upsTestResultsDetail OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTest 4 }
- upsTestStartTime OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTest 5 }
- upsTestElapsedTime OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTest 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiated OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTests 1 }
- upsTestAbortTestInProgress OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTests 2 }
- upsTestGeneralSystemsTest OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTests 3 }
- upsTestQuickBatteryTest OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTests 4 }
- upsTestDeepBatteryCalibration OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTests 5 }
- --
- -- The Control group generic.
- --
- upsShutdownType OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControl 1 }
- upsShutdownAfterDelay OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of seconds, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- seconds remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControl 2 }
- upsStartupAfterDelay OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of seconds, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of seconds until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControl 3 }
- upsRebootWithDuration OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of seconds, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of seconds required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 seconds. When read, upsRebootWithDuration
- shall return the number of seconds remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControl 4 }
- upsAutoRestart OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControl 5 }
- upsReceptaclesNum OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControl 6 }
- upsReceptacleTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControl 7 }
- upsReceptacleEntry OBJECT-TYPE
- SYNTAX UpsReceptacleEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndex }
- ::= { upsReceptacleTable 1 }
- UpsReceptacleEntry ::= SEQUENCE {
- upsReceptacleLineIndex PositiveInteger32,
- upsReceptacleOnOff INTEGER
- }
- upsReceptacleLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleEntry 1 }
- upsReceptacleOnOff OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleEntry 2 }
- upsUPSMode OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControl 8 }
- upsRectifierOnOff OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControl 9 }
- upsBatteryChargeMethod OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControl 10 }
- upsInverterOnOff OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControl 11 }
- upsBypassOnOff OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControl 12 }
- upsLoadSource OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControl 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfig 1 }
- upsConfigInputFreq OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfig 2 }
- upsConfigOutputVoltage OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfig 3 }
- upsConfigOutputFreq OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfig 4 }
- upsConfigOutputVA OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfig 5 }
- upsConfigOutputPower OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfig 6 }
- upsConfigLowBattTime OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfig 7 }
- upsConfigAudibleStatus OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfig 8 }
- upsConfigLowVoltageTransferPoint OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfig 9 }
- upsConfigHighVoltageTransferPoint OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfig 10 }
- upsConfigBatteryCapacity OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfig 11 }
- upsConfigBatteryChargeCurrent OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfig 12 }
- upsConfigNoLoadShutdown OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfig 13 }
- upsConfigStartDelay OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfig 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNext OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSet 1 }
- upsEventGetPrevious OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSet 2 }
- upsEventSetStartingTimeStamp OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSet 3 }
- upsEventRetreiveCurrentTimeStamp OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSet 4 }
- upsEventTableSize OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSet 5 }
- upsEventTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSet 6 }
- upsEventEntry OBJECT-TYPE
- SYNTAX UpsEventEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndex }
- ::= { upsEventTable 1 }
- UpsEventEntry ::= SEQUENCE {
- upsEventLineIndex PositiveInteger32,
- upsEventCode Integer32,
- upsEventStatus NonNegativeInteger32,
- upsEventTime NonNegativeInteger32
- }
- upsEventLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventEntry 1 }
- upsEventCode OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventEntry 2 }
- upsEventStatus OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventEntry 3 }
- upsEventTime OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventEntry 4 }
- upsParametersRead OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSet 7 }
- upsParametersWrite OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the first value
- of the table with the lowest index number."
- ::= { upsGetSet 8 }
- upsParametersStartAddress OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSet 9 }
- upsParameterTableSize OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSet 10 }
- upsParameterTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSet 11 }
- upsParameterEntry OBJECT-TYPE
- SYNTAX UpsParameterEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndex }
- ::= { upsParameterTable 1 }
- UpsParameterEntry ::= SEQUENCE {
- upsParameterLineIndex PositiveInteger32,
- upsParameterValue Integer32
- }
- upsParameterLineIndex OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterEntry 1 }
- upsParameterValue OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterEntry 2 }
- upsStatus OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSet 12 }
- upsMainsStatisticsMBfail OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSet 13 }
- upsMainsStatisticsMRfail OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSet 14 }
- upsMainsStatisticsB2 OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSet 15 }
- upsMainsStatisticsB5 OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSet 16 }
- upsMainsStatisticsB10 OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSet 17 }
- upsMainsStatisticsB200 OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSet 18 }
- upsMainsStatisticsBypRel OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSet 19 }
- upsTimegen OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPgenERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSet 20 }
- upsRequestPermission OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSet 21 }
- upsEventGetCode OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSet 22 }
- upsEventSpinLock OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSet 23 }
- upsParameterSpinLock OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSet 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBad NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTraps 1 }
- upsTrapAlarmOnBattery NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBattery }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTraps 2 }
- upsTrapAlarmLowBattery NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTraps 3 }
- upsTrapAlarmDepletedBattery NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTraps 4 }
- upsTrapAlarmTempBad NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTraps 5 }
- upsTrapAlarmInputBad NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTraps 6 }
- upsTrapAlarmOutputBad NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTraps 7 }
- upsTrapAlarmOutputOverload NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLines, upsOutputPercentLoad }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTraps 8 }
- upsTrapAlarmOnBypass NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTraps 9 }
- upsTrapAlarmBypassBad NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTraps 10 }
- upsTrapAlarmOutputOffAsRequested NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTraps 11 }
- upsTrapAlarmUpsOffAsRequested NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTraps 12 }
- upsTrapAlarmChargerFailed NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTraps 13 }
- upsTrapAlarmUpsOutputOff NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTraps 14 }
- upsTrapAlarmUpsSystemOff NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTraps 15 }
- upsTrapAlarmFanFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTraps 16 }
- upsTrapAlarmFuseFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTraps 17 }
- upsTrapAlarmGeneralFault NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTraps 18 }
- upsTrapAlarmDiagnosticTestFailed NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTraps 19 }
- upsTrapAlarmCommunicationsLost NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTraps 20 }
- upsTrapAlarmAwaitingPower NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTraps 21 }
- upsTrapAlarmShutdownPending NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelay }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTraps 22 }
- upsTrapAlarmShutdownImminent NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTraps 23 }
- upsTrapAlarmTestInProgress NOTIFICATION-TYPE
- OBJECTS { upsTestId }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTraps 24 }
- upsTrapAlarmReceptacleOff NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTraps 25 }
- upsTrapAlarmHighspeedBusFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTraps 26 }
- upsTrapAlarmHighspeedBusJACRCFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTraps 27 }
- upsTrapAlarmConnectivityBusFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus is detected."
- ::= { geUPSTraps 28 }
- upsTrapAlarmHighspeedBusJBCRCFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTraps 29 }
- upsTrapAlarmCurrentSharingFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTraps 30 }
- upsTrapAlarmDCRippleFailure NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTraps 31 }
- upsTrapAlarmBatteryBadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTraps 33 }
- upsTrapAlarmOnBatteryRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTraps 34 }
- upsTrapAlarmLowBatteryRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTraps 35 }
- upsTrapAlarmDepletedBatteryRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTraps 36 }
- upsTrapAlarmTempBadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTraps 37 }
- upsTrapAlarmInputBadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTraps 38 }
- upsTrapAlarmOutputBadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTraps 39 }
- upsTrapAlarmOutputOverloadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTraps 40 }
- upsTrapAlarmOnBypassRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTraps 41 }
- upsTrapAlarmBypassBadRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTraps 42 }
- upsTrapAlarmOutputOffAsRequestedRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTraps 43 }
- upsTrapAlarmUpsOffAsRequestedRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTraps 44 }
- upsTrapAlarmChargerFailedRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTraps 45 }
- upsTrapAlarmUpsOutputOn NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTraps 46 }
- upsTrapAlarmUpsSystemOn NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTraps 47 }
- upsTrapAlarmFanFailureRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTraps 48 }
- upsTrapAlarmFuseFailureRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTraps 49 }
- upsTrapAlarmGeneralFaultRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTraps 50 }
- upsTrapAlarmDiagnosticTestFailedRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTraps 51 }
- upsTrapAlarmCommunicationsLostRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTraps 52 }
- upsTrapAlarmAwaitingPowerRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTraps 53 }
- upsTrapAlarmShutdownPendingRestored NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelay }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTraps 54 }
- upsTrapAlarmShutdownImminentRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTraps 55 }
- upsTrapAlarmTestInProgressRestored NOTIFICATION-TYPE
- OBJECTS { upsTestId }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTraps 56 }
- upsTrapAlarmReceptacleOn NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTraps 57 }
- upsTrapAlarmHighspeedBusRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTraps 58 }
- upsTrapAlarmHighspeedBusJACRCRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTraps 59 }
- upsTrapAlarmConnectivityBusRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTraps 60 }
- upsTrapAlarmHighspeedBusJBCRCRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTraps 61 }
- upsTrapAlarmCurrentSharingRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTraps 62 }
- upsTrapAlarmDCRippleRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTraps 63 }
- upsTrapAlarmValueLow NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTraps 129 }
- upsTrapAlarmValueHigh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTraps 130 }
- upsTrapAlarmValueLowRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTraps 133 }
- upsTrapAlarmValueHighRestored NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTraps 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatus OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnostic 1 }
- upsDiagnosticBusJBCommunicationStatus OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnostic 2 }
- upsDiagnosticBatteryLifetime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnostic 3 }
- upsDiagnosticFansLifetime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnostic 4 }
- upsDiagnosticDCcapacitorsLifetime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnostic 5 }
- upsDiagnosticACcapacitorsLifetime OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnostic 6 }
- upsDiagnosticGlobalServiceCheck OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnostic 7 }
- --
- -- The Device Identification group. First
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturerfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentfirst 1 }
- upsIdentModelfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentfirst 2 }
- upsIdentUPSSoftwareVersionfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfirst 3 }
- upsIdentAgentSoftwareVersionfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfirst 4 }
- upsIdentNamefirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentfirst 5 }
- upsIdentAttachedDevicesfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentfirst 6 }
- upsIdentUPSSerialNumberfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentfirst 7 }
- upsIdentComProtVersionfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentfirst 8 }
- upsIdentOperatingTimefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentfirst 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatusfirst OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatteryfirst 1 }
- upsSecondsOnBatteryfirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatteryfirst 2 }
- upsEstimatedMinutesRemainingfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatteryfirst 3 }
- upsEstimatedChargeRemainingfirst OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatteryfirst 4 }
- upsBatteryVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatteryfirst 5 }
- upsBatteryCurrentfirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatteryfirst 6 }
- upsBatteryTemperaturefirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatteryfirst 7 }
- upsBatteryRipplefirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatteryfirst 8 }
- --
- -- Input Group
- --
- upsInputLineBadsfirst OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputfirst 1 }
- upsInputNumLinesfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputfirst 2 }
- upsInputFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputfirst 3 }
- upsInputFirstEntry OBJECT-TYPE
- SYNTAX UpsInputFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexfirst }
- ::= { upsInputFirstTable 1 }
- UpsInputFirstEntry ::= SEQUENCE {
- upsInputLineIndexfirst PositiveInteger32,
- upsInputFrequencyfirst NonNegativeInteger32,
- upsInputVoltagefirst NonNegativeInteger32,
- upsInputCurrentfirst NonNegativeInteger32,
- upsInputTruePowerfirst NonNegativeInteger32,
- upsInputVoltageMinfirst NonNegativeInteger32,
- upsInputVoltageMaxfirst NonNegativeInteger32
- }
- upsInputLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputFirstEntry 1 }
- upsInputFrequencyfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputFirstEntry 2 }
- upsInputVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputFirstEntry 3 }
- upsInputCurrentfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputFirstEntry 4 }
- upsInputTruePowerfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputFirstEntry 5 }
- upsInputVoltageMinfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputFirstEntry 6 }
- upsInputVoltageMaxfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputFirstEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcefirst OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputfirst 1 }
- upsOutputFrequencyfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputfirst 2 }
- upsOutputNumLinesfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputfirst 3 }
- upsOutputFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputfirst 4 }
- upsOutputFirstEntry OBJECT-TYPE
- SYNTAX UpsOutputFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexfirst }
- ::= { upsOutputFirstTable 1 }
- UpsOutputFirstEntry ::= SEQUENCE {
- upsOutputLineIndexfirst PositiveInteger32,
- upsOutputVoltagefirst NonNegativeInteger32,
- upsOutputCurrentfirst NonNegativeInteger32,
- upsOutputPowerfirst NonNegativeInteger32,
- upsOutputPercentLoadfirst Integer32,
- upsOutputPowerFactorfirst Integer32,
- upsOutputPeakCurrentfirst Integer32,
- upsOutputShareCurrentfirst Integer32
- }
- upsOutputLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputFirstEntry 1 }
- upsOutputVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputFirstEntry 2 }
- upsOutputCurrentfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputFirstEntry 3 }
- upsOutputPowerfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputFirstEntry 4 }
- upsOutputPercentLoadfirst OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputFirstEntry 5 }
- upsOutputPowerFactorfirst OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputFirstEntry 6 }
- upsOutputPeakCurrentfirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputFirstEntry 7 }
- upsOutputShareCurrentfirst OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputFirstEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencyfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypassfirst 1 }
- upsBypassNumLinesfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypassfirst 2 }
- upsBypassFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypassfirst 3 }
- upsBypassFirstEntry OBJECT-TYPE
- SYNTAX UpsBypassFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexfirst }
- ::= { upsBypassFirstTable 1 }
- UpsBypassFirstEntry ::= SEQUENCE {
- upsBypassLineIndexfirst PositiveInteger32,
- upsBypassVoltagefirst NonNegativeInteger32,
- upsBypassCurrentfirst NonNegativeInteger32,
- upsBypassPowerfirst NonNegativeInteger32
- }
- upsBypassLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassFirstEntry 1 }
- upsBypassVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassFirstEntry 2 }
- upsBypassCurrentfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassFirstEntry 3 }
- upsBypassPowerfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassFirstEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentfirst OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmfirst 1 }
- upsAlarmFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmfirst 2 }
- upsAlarmFirstEntry OBJECT-TYPE
- SYNTAX UpsAlarmFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdfirst }
- ::= { upsAlarmFirstTable 1 }
- UpsAlarmFirstEntry ::= SEQUENCE {
- upsAlarmIdfirst PositiveInteger32,
- upsAlarmDescrfirst AutonomousType,
- upsAlarmTimefirst TimeStamp
- }
- upsAlarmIdfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmFirstEntry 1 }
- upsAlarmDescrfirst OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmFirstEntry 2 }
- upsAlarmTimefirst OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmFirstEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmsfirst 1 }
- upsAlarmOnBatteryfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmsfirst 2 }
- upsAlarmLowBatteryfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmsfirst 3 }
- upsAlarmDepletedBatteryfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmsfirst 4 }
- upsAlarmTempBadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfirst 5 }
- upsAlarmInputBadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfirst 6 }
- upsAlarmOutputBadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfirst 7 }
- upsAlarmOutputOverloadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmsfirst 8 }
- upsAlarmOnBypassfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmsfirst 9 }
- upsAlarmBypassBadfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfirst 10 }
- upsAlarmOutputOffAsRequestedfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmsfirst 11 }
- upsAlarmUpsOffAsRequestedfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmsfirst 12 }
- upsAlarmChargerFailedfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmsfirst 13 }
- upsAlarmUpsOutputOfffirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmsfirst 14 }
- upsAlarmUpsSystemOfffirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmsfirst 15 }
- upsAlarmFanFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmsfirst 16 }
- upsAlarmFuseFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmsfirst 17 }
- upsAlarmGeneralFaultfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmsfirst 18 }
- upsAlarmDiagnosticTestFailedfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmsfirst 19 }
- upsAlarmCommunicationsLostfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmsfirst 20 }
- upsAlarmAwaitingPowerfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmsfirst 21 }
- upsAlarmShutdownPendingfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmsfirst 22 }
- upsAlarmShutdownImminentfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmsfirst 23 }
- upsAlarmTestInProgressfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmsfirst 24 }
- upsAlarmReceptacleOfffirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmsfirst 25 }
- upsAlarmHighSpeedBusFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmsfirst 26 }
- upsAlarmHighSpeedBusJACRCFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A CRC failure on High Speed Bus JA is detected."
- ::= { upsWellKnownAlarmsfirst 27 }
- upsAlarmConnectivityBusFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmsfirst 28 }
- upsAlarmHighSpeedBusJBCRCFailurefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A CRC failure on High Speed Bus JB is detected."
- ::= { upsWellKnownAlarmsfirst 29 }
- upsAlarmCurrentSharingfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmsfirst 30 }
- upsAlarmDCRipplefirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmsfirst 31 }
- upsAlarmMaskAfirst OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmfirst 4 }
- --
- -- The Test Group generic
- --
- upsTestIdfirst OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestfirst 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockfirst OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestfirst 2 }
- upsTestResultsSummaryfirst OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestfirst 3 }
- upsTestResultsDetailfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestfirst 4 }
- upsTestStartTimefirst OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestfirst 5 }
- upsTestElapsedTimefirst OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestfirst 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestsfirst 1 }
- upsTestAbortTestInProgressfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestsfirst 2 }
- upsTestGeneralSystemsTestfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestsfirst 3 }
- upsTestQuickBatteryTestfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestsfirst 4 }
- upsTestDeepBatteryCalibrationfirst OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestsfirst 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypefirst OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlfirst 1 }
- upsShutdownAfterDelayfirst OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of seconds, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- seconds remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlfirst 2 }
- upsStartupAfterDelayfirst OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of seconds, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of seconds until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlfirst 3 }
- upsRebootWithDurationfirst OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of seconds, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of seconds required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 seconds. When read, upsRebootWithDuration
- shall return the number of seconds remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlfirst 4 }
- upsAutoRestartfirst OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlfirst 5 }
- upsReceptaclesNumfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlfirst 6 }
- upsReceptacleFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlfirst 7 }
- upsReceptacleFirstEntry OBJECT-TYPE
- SYNTAX UpsReceptacleFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexfirst }
- ::= { upsReceptacleFirstTable 1 }
- UpsReceptacleFirstEntry ::= SEQUENCE {
- upsReceptacleLineIndexfirst PositiveInteger32,
- upsReceptacleOnOfffirst INTEGER
- }
- upsReceptacleLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleFirstEntry 1 }
- upsReceptacleOnOfffirst OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleFirstEntry 2 }
- upsUPSModefirst OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlfirst 8 }
- upsRectifierOnOfffirst OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlfirst 9 }
- upsBatteryChargeMethodfirst OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlfirst 10 }
- upsInverterOnOfffirst OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlfirst 11 }
- upsBypassOnOfffirst OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlfirst 12 }
- upsLoadSourcefirst OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlfirst 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfirst 1 }
- upsConfigInputFreqfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfirst 2 }
- upsConfigOutputVoltagefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfirst 3 }
- upsConfigOutputFreqfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfirst 4 }
- upsConfigOutputVAfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigfirst 5 }
- upsConfigOutputPowerfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigfirst 6 }
- upsConfigLowBattTimefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigfirst 7 }
- upsConfigAudibleStatusfirst OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigfirst 8 }
- upsConfigLowVoltageTransferPointfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfirst 9 }
- upsConfigHighVoltageTransferPointfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfirst 10 }
- upsConfigBatteryCapacityfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigfirst 11 }
- upsConfigBatteryChargeCurrentfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigfirst 12 }
- upsConfigNoLoadShutdownfirst OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigfirst 13 }
- upsConfigStartDelayfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigfirst 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetfirst 1 }
- upsEventGetPreviousfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetfirst 2 }
- upsEventSetStartingTimeStampfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetfirst 3 }
- upsEventRetreiveCurrentTimeStampfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetfirst 4 }
- upsEventTableSizefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetfirst 5 }
- upsEventFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetfirst 6 }
- upsEventFirstEntry OBJECT-TYPE
- SYNTAX UpsEventFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexfirst }
- ::= { upsEventFirstTable 1 }
- UpsEventFirstEntry ::= SEQUENCE {
- upsEventLineIndexfirst PositiveInteger32,
- upsEventCodefirst Integer32,
- upsEventStatusfirst NonNegativeInteger32,
- upsEventTimefirst NonNegativeInteger32
- }
- upsEventLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventFirstEntry 1 }
- upsEventCodefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventFirstEntry 2 }
- upsEventStatusfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventFirstEntry 3 }
- upsEventTimefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventFirstEntry 4 }
- upsParametersReadfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetfirst 7 }
- upsParametersWritefirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the first value
- of the table with the lowest index number."
- ::= { upsGetSetfirst 8 }
- upsParametersStartAddressfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetfirst 9 }
- upsParameterTableSizefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetfirst 10 }
- upsParameterFirstTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetfirst 11 }
- upsParameterFirstEntry OBJECT-TYPE
- SYNTAX UpsParameterFirstEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexfirst }
- ::= { upsParameterFirstTable 1 }
- UpsParameterFirstEntry ::= SEQUENCE {
- upsParameterLineIndexfirst PositiveInteger32,
- upsParameterValuefirst Integer32
- }
- upsParameterLineIndexfirst OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterFirstEntry 1 }
- upsParameterValuefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterFirstEntry 2 }
- upsStatusfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetfirst 12 }
- upsMainsStatisticsMBfailfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetfirst 13 }
- upsMainsStatisticsMRfailfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetfirst 14 }
- upsMainsStatisticsB2first OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetfirst 15 }
- upsMainsStatisticsB5first OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetfirst 16 }
- upsMainsStatisticsB10first OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetfirst 17 }
- upsMainsStatisticsB200first OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetfirst 18 }
- upsMainsStatisticsBypRelfirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetfirst 19 }
- upsTimefirst OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPfirstERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetfirst 20 }
- upsRequestPermissionfirst OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetfirst 21 }
- upsEventGetCodefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetfirst 22 }
- upsEventSpinLockfirst OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetfirst 23 }
- upsParameterSpinLockfirst OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetfirst 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapsfirst 1 }
- upsTrapAlarmOnBatteryfirst NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatteryfirst }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapsfirst 2 }
- upsTrapAlarmLowBatteryfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapsfirst 3 }
- upsTrapAlarmDepletedBatteryfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapsfirst 4 }
- upsTrapAlarmTempBadfirst NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapsfirst 5 }
- upsTrapAlarmInputBadfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapsfirst 6 }
- upsTrapAlarmOutputBadfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapsfirst 7 }
- upsTrapAlarmOutputOverloadfirst NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinesfirst, upsOutputPercentLoadfirst }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapsfirst 8 }
- upsTrapAlarmOnBypassfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapsfirst 9 }
- upsTrapAlarmBypassBadfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapsfirst 10 }
- upsTrapAlarmOutputOffAsRequestedfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapsfirst 11 }
- upsTrapAlarmUpsOffAsRequestedfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapsfirst 12 }
- upsTrapAlarmChargerFailedfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapsfirst 13 }
- upsTrapAlarmUpsOutputOfffirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapsfirst 14 }
- upsTrapAlarmUpsSystemOfffirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapsfirst 15 }
- upsTrapAlarmFanFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapsfirst 16 }
- upsTrapAlarmFuseFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapsfirst 17 }
- upsTrapAlarmGeneralFaultfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapsfirst 18 }
- upsTrapAlarmDiagnosticTestFailedfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapsfirst 19 }
- upsTrapAlarmCommunicationsLostfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapsfirst 20 }
- upsTrapAlarmAwaitingPowerfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapsfirst 21 }
- upsTrapAlarmShutdownPendingfirst NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfirst }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapsfirst 22 }
- upsTrapAlarmShutdownImminentfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapsfirst 23 }
- upsTrapAlarmTestInProgressfirst NOTIFICATION-TYPE
- OBJECTS { upsTestIdfirst }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapsfirst 24 }
- upsTrapAlarmReceptacleOfffirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapsfirst 25 }
- upsTrapAlarmHighspeedBusFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapsfirst 26 }
- upsTrapAlarmHighspeedBusJACRCFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsfirst 27 }
- upsTrapAlarmConnectivityBusFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { geUPSTrapsfirst 28 }
- upsTrapAlarmHighspeedBusJBCRCFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsfirst 29 }
- upsTrapAlarmCurrentSharingFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapsfirst 30 }
- upsTrapAlarmDCRippleFailurefirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapsfirst 31 }
- upsTrapAlarmBatteryBadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapsfirst 33 }
- upsTrapAlarmOnBatteryRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapsfirst 34 }
- upsTrapAlarmLowBatteryRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapsfirst 35 }
- upsTrapAlarmDepletedBatteryRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapsfirst 36 }
- upsTrapAlarmTempBadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapsfirst 37 }
- upsTrapAlarmInputBadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapsfirst 38 }
- upsTrapAlarmOutputBadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapsfirst 39 }
- upsTrapAlarmOutputOverloadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapsfirst 40 }
- upsTrapAlarmOnBypassRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapsfirst 41 }
- upsTrapAlarmBypassBadRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapsfirst 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapsfirst 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapsfirst 44 }
- upsTrapAlarmChargerFailedRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapsfirst 45 }
- upsTrapAlarmUpsOutputOnfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapsfirst 46 }
- upsTrapAlarmUpsSystemOnfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapsfirst 47 }
- upsTrapAlarmFanFailureRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapsfirst 48 }
- upsTrapAlarmFuseFailureRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapsfirst 49 }
- upsTrapAlarmGeneralFaultRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapsfirst 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapsfirst 51 }
- upsTrapAlarmCommunicationsLostRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapsfirst 52 }
- upsTrapAlarmAwaitingPowerRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapsfirst 53 }
- upsTrapAlarmShutdownPendingRestoredfirst NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfirst }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapsfirst 54 }
- upsTrapAlarmShutdownImminentRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapsfirst 55 }
- upsTrapAlarmTestInProgressRestoredfirst NOTIFICATION-TYPE
- OBJECTS { upsTestIdfirst }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapsfirst 56 }
- upsTrapAlarmReceptacleOnfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapsfirst 57 }
- upsTrapAlarmHighspeedBusRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapsfirst 58 }
- upsTrapAlarmHighspeedBusJACRCRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapsfirst 59 }
- upsTrapAlarmConnectivityBusRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapsfirst 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapsfirst 61 }
- upsTrapAlarmCurrentSharingRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapsfirst 62 }
- upsTrapAlarmDCRippleRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapsfirst 63 }
- upsTrapAlarmValueLowfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapsfirst 129 }
- upsTrapAlarmValueHighfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapsfirst 130 }
- upsTrapAlarmValueLowRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapsfirst 133 }
- upsTrapAlarmValueHighRestoredfirst NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapsfirst 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatusfirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfirst 1 }
- upsDiagnosticBusJBCommunicationStatusfirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfirst 2 }
- upsDiagnosticBatteryLifetimefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfirst 3 }
- upsDiagnosticFansLifetimefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfirst 4 }
- upsDiagnosticDCcapacitorsLifetimefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfirst 5 }
- upsDiagnosticACcapacitorsLifetimefirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfirst 6 }
- upsDiagnosticGlobalServiceCheckfirst OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfirst 7 }
- --
- -- The Device Identification group. Second
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturersecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentsecond 1 }
- upsIdentModelsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentsecond 2 }
- upsIdentUPSSoftwareVersionsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentsecond 3 }
- upsIdentAgentSoftwareVersionsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentsecond 4 }
- upsIdentNamesecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentsecond 5 }
- upsIdentAttachedDevicessecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentsecond 6 }
- upsIdentUPSSerialNumbersecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentsecond 7 }
- upsIdentComProtVersionsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentsecond 8 }
- upsIdentOperatingTimesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentsecond 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatussecond OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatterysecond 1 }
- upsSecondsOnBatterysecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatterysecond 2 }
- upsEstimatedMinutesRemainingsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatterysecond 3 }
- upsEstimatedChargeRemainingsecond OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatterysecond 4 }
- upsBatteryVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatterysecond 5 }
- upsBatteryCurrentsecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatterysecond 6 }
- upsBatteryTemperaturesecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatterysecond 7 }
- upsBatteryRipplesecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatterysecond 8 }
- --
- -- Input Group
- --
- upsInputLineBadssecond OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputsecond 1 }
- upsInputNumLinessecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputsecond 2 }
- upsInputSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputsecond 3 }
- upsInputSecondEntry OBJECT-TYPE
- SYNTAX UpsInputSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexsecond }
- ::= { upsInputSecondTable 1 }
- UpsInputSecondEntry ::= SEQUENCE {
- upsInputLineIndexsecond PositiveInteger32,
- upsInputFrequencysecond NonNegativeInteger32,
- upsInputVoltagesecond NonNegativeInteger32,
- upsInputCurrentsecond NonNegativeInteger32,
- upsInputTruePowersecond NonNegativeInteger32,
- upsInputVoltageMinsecond NonNegativeInteger32,
- upsInputVoltageMaxsecond NonNegativeInteger32
- }
- upsInputLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputSecondEntry 1 }
- upsInputFrequencysecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputSecondEntry 2 }
- upsInputVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputSecondEntry 3 }
- upsInputCurrentsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputSecondEntry 4 }
- upsInputTruePowersecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputSecondEntry 5 }
- upsInputVoltageMinsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputSecondEntry 6 }
- upsInputVoltageMaxsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputSecondEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcesecond OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputsecond 1 }
- upsOutputFrequencysecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputsecond 2 }
- upsOutputNumLinessecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputsecond 3 }
- upsOutputSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputsecond 4 }
- upsOutputSecondEntry OBJECT-TYPE
- SYNTAX UpsOutputSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexsecond }
- ::= { upsOutputSecondTable 1 }
- UpsOutputSecondEntry ::= SEQUENCE {
- upsOutputLineIndexsecond PositiveInteger32,
- upsOutputVoltagesecond NonNegativeInteger32,
- upsOutputCurrentsecond NonNegativeInteger32,
- upsOutputPowersecond NonNegativeInteger32,
- upsOutputPercentLoadsecond Integer32,
- upsOutputPowerFactorsecond Integer32,
- upsOutputPeakCurrentsecond Integer32,
- upsOutputShareCurrentsecond Integer32
- }
- upsOutputLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputSecondEntry 1 }
- upsOutputVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputSecondEntry 2 }
- upsOutputCurrentsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputSecondEntry 3 }
- upsOutputPowersecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputSecondEntry 4 }
- upsOutputPercentLoadsecond OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputSecondEntry 5 }
- upsOutputPowerFactorsecond OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputSecondEntry 6 }
- upsOutputPeakCurrentsecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputSecondEntry 7 }
- upsOutputShareCurrentsecond OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputSecondEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencysecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypasssecond 1 }
- upsBypassNumLinessecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypasssecond 2 }
- upsBypassSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypasssecond 3 }
- upsBypassSecondEntry OBJECT-TYPE
- SYNTAX UpsBypassSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexsecond }
- ::= { upsBypassSecondTable 1 }
- UpsBypassSecondEntry ::= SEQUENCE {
- upsBypassLineIndexsecond PositiveInteger32,
- upsBypassVoltagesecond NonNegativeInteger32,
- upsBypassCurrentsecond NonNegativeInteger32,
- upsBypassPowersecond NonNegativeInteger32
- }
- upsBypassLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassSecondEntry 1 }
- upsBypassVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassSecondEntry 2 }
- upsBypassCurrentsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassSecondEntry 3 }
- upsBypassPowersecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassSecondEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentsecond OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmsecond 1 }
- upsAlarmSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmsecond 2 }
- upsAlarmSecondEntry OBJECT-TYPE
- SYNTAX UpsAlarmSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdsecond }
- ::= { upsAlarmSecondTable 1 }
- UpsAlarmSecondEntry ::= SEQUENCE {
- upsAlarmIdsecond PositiveInteger32,
- upsAlarmDescrsecond AutonomousType,
- upsAlarmTimesecond TimeStamp
- }
- upsAlarmIdsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmSecondEntry 1 }
- upsAlarmDescrsecond OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmSecondEntry 2 }
- upsAlarmTimesecond OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmSecondEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmssecond 1 }
- upsAlarmOnBatterysecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmssecond 2 }
- upsAlarmLowBatterysecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmssecond 3 }
- upsAlarmDepletedBatterysecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmssecond 4 }
- upsAlarmTempBadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssecond 5 }
- upsAlarmInputBadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssecond 6 }
- upsAlarmOutputBadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmssecond 7 }
- upsAlarmOutputOverloadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmssecond 8 }
- upsAlarmOnBypasssecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmssecond 9 }
- upsAlarmBypassBadsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssecond 10 }
- upsAlarmOutputOffAsRequestedsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmssecond 11 }
- upsAlarmUpsOffAsRequestedsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmssecond 12 }
- upsAlarmChargerFailedsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmssecond 13 }
- upsAlarmUpsOutputOffsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmssecond 14 }
- upsAlarmUpsSystemOffsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmssecond 15 }
- upsAlarmFanFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmssecond 16 }
- upsAlarmFuseFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmssecond 17 }
- upsAlarmGeneralFaultsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmssecond 18 }
- upsAlarmDiagnosticTestFailedsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmssecond 19 }
- upsAlarmCommunicationsLostsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmssecond 20 }
- upsAlarmAwaitingPowersecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmssecond 21 }
- upsAlarmShutdownPendingsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmssecond 22 }
- upsAlarmShutdownImminentsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmssecond 23 }
- upsAlarmTestInProgresssecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmssecond 24 }
- upsAlarmReceptacleOffsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmssecond 25 }
- upsAlarmHighSpeedBusFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmssecond 26 }
- upsAlarmHighSpeedBusJACRCFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmssecond 27 }
- upsAlarmConnectivityBusFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmssecond 28 }
- upsAlarmHighSpeedBusJBCRCFailuresecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmssecond 29 }
- upsAlarmCurrentSharingsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmssecond 30 }
- upsAlarmDCRipplesecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmssecond 31 }
- upsAlarmMaskAsecond OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmsecond 4 }
- --
- -- The Test Group generic
- --
- upsTestIdsecond OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestsecond 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLocksecond OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestsecond 2 }
- upsTestResultsSummarysecond OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestsecond 3 }
- upsTestResultsDetailsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestsecond 4 }
- upsTestStartTimesecond OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestsecond 5 }
- upsTestElapsedTimesecond OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestsecond 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestssecond 1 }
- upsTestAbortTestInProgresssecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestssecond 2 }
- upsTestGeneralSystemsTestsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestssecond 3 }
- upsTestQuickBatteryTestsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestssecond 4 }
- upsTestDeepBatteryCalibrationsecond OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestssecond 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypesecond OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlsecond 1 }
- upsShutdownAfterDelaysecond OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of seconds, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- seconds remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlsecond 2 }
- upsStartupAfterDelaysecond OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of seconds, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of seconds until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlsecond 3 }
- upsRebootWithDurationsecond OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of seconds, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of seconds required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 seconds. When read, upsRebootWithDuration
- shall return the number of seconds remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlsecond 4 }
- upsAutoRestartsecond OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlsecond 5 }
- upsReceptaclesNumsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlsecond 6 }
- upsReceptacleSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlsecond 7 }
- upsReceptacleSecondEntry OBJECT-TYPE
- SYNTAX UpsReceptacleSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexsecond }
- ::= { upsReceptacleSecondTable 1 }
- UpsReceptacleSecondEntry ::= SEQUENCE {
- upsReceptacleLineIndexsecond PositiveInteger32,
- upsReceptacleOnOffsecond INTEGER
- }
- upsReceptacleLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleSecondEntry 1 }
- upsReceptacleOnOffsecond OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleSecondEntry 2 }
- upsUPSModesecond OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlsecond 8 }
- upsRectifierOnOffsecond OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlsecond 9 }
- upsBatteryChargeMethodsecond OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlsecond 10 }
- upsInverterOnOffsecond OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlsecond 11 }
- upsBypassOnOffsecond OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlsecond 12 }
- upsLoadSourcesecond OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlsecond 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsecond 1 }
- upsConfigInputFreqsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsecond 2 }
- upsConfigOutputVoltagesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsecond 3 }
- upsConfigOutputFreqsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsecond 4 }
- upsConfigOutputVAsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigsecond 5 }
- upsConfigOutputPowersecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigsecond 6 }
- upsConfigLowBattTimesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigsecond 7 }
- upsConfigAudibleStatussecond OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigsecond 8 }
- upsConfigLowVoltageTransferPointsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigsecond 9 }
- upsConfigHighVoltageTransferPointsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigsecond 10 }
- upsConfigBatteryCapacitysecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigsecond 11 }
- upsConfigBatteryChargeCurrentsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigsecond 12 }
- upsConfigNoLoadShutdownsecond OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigsecond 13 }
- upsConfigStartDelaysecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigsecond 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetsecond 1 }
- upsEventGetPrevioussecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetsecond 2 }
- upsEventSetStartingTimeStampsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetsecond 3 }
- upsEventRetreiveCurrentTimeStampsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetsecond 4 }
- upsEventTableSizesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetsecond 5 }
- upsEventSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetsecond 6 }
- upsEventSecondEntry OBJECT-TYPE
- SYNTAX UpsEventSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexsecond }
- ::= { upsEventSecondTable 1 }
- UpsEventSecondEntry ::= SEQUENCE {
- upsEventLineIndexsecond PositiveInteger32,
- upsEventCodesecond Integer32,
- upsEventStatussecond NonNegativeInteger32,
- upsEventTimesecond NonNegativeInteger32
- }
- upsEventLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventSecondEntry 1 }
- upsEventCodesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventSecondEntry 2 }
- upsEventStatussecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventSecondEntry 3 }
- upsEventTimesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventSecondEntry 4 }
- upsParametersReadsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetsecond 7 }
- upsParametersWritesecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the second value
- of the table with the lowest index number."
- ::= { upsGetSetsecond 8 }
- upsParametersStartAddresssecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetsecond 9 }
- upsParameterTableSizesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetsecond 10 }
- upsParameterSecondTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetsecond 11 }
- upsParameterSecondEntry OBJECT-TYPE
- SYNTAX UpsParameterSecondEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexsecond }
- ::= { upsParameterSecondTable 1 }
- UpsParameterSecondEntry ::= SEQUENCE {
- upsParameterLineIndexsecond PositiveInteger32,
- upsParameterValuesecond Integer32
- }
- upsParameterLineIndexsecond OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterSecondEntry 1 }
- upsParameterValuesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterSecondEntry 2 }
- upsStatussecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetsecond 12 }
- upsMainsStatisticsMBfailsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetsecond 13 }
- upsMainsStatisticsMRfailsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetsecond 14 }
- upsMainsStatisticsB2second OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetsecond 15 }
- upsMainsStatisticsB5second OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetsecond 16 }
- upsMainsStatisticsB10second OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetsecond 17 }
- upsMainsStatisticsB200second OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetsecond 18 }
- upsMainsStatisticsBypRelsecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetsecond 19 }
- upsTimesecond OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPsecondERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetsecond 20 }
- upsRequestPermissionsecond OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetsecond 21 }
- upsEventGetCodesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetsecond 22 }
- upsEventSpinLocksecond OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetsecond 23 }
- upsParameterSpinLocksecond OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetsecond 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapssecond 1 }
- upsTrapAlarmOnBatterysecond NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatterysecond }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapssecond 2 }
- upsTrapAlarmLowBatterysecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapssecond 3 }
- upsTrapAlarmDepletedBatterysecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapssecond 4 }
- upsTrapAlarmTempBadsecond NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapssecond 5 }
- upsTrapAlarmInputBadsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapssecond 6 }
- upsTrapAlarmOutputBadsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapssecond 7 }
- upsTrapAlarmOutputOverloadsecond NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinessecond, upsOutputPercentLoadsecond }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapssecond 8 }
- upsTrapAlarmOnBypasssecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapssecond 9 }
- upsTrapAlarmBypassBadsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapssecond 10 }
- upsTrapAlarmOutputOffAsRequestedsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapssecond 11 }
- upsTrapAlarmUpsOffAsRequestedsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapssecond 12 }
- upsTrapAlarmChargerFailedsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapssecond 13 }
- upsTrapAlarmUpsOutputOffsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapssecond 14 }
- upsTrapAlarmUpsSystemOffsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapssecond 15 }
- upsTrapAlarmFanFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapssecond 16 }
- upsTrapAlarmFuseFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapssecond 17 }
- upsTrapAlarmGeneralFaultsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapssecond 18 }
- upsTrapAlarmDiagnosticTestFailedsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapssecond 19 }
- upsTrapAlarmCommunicationsLostsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapssecond 20 }
- upsTrapAlarmAwaitingPowersecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapssecond 21 }
- upsTrapAlarmShutdownPendingsecond NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaysecond }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapssecond 22 }
- upsTrapAlarmShutdownImminentsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapssecond 23 }
- upsTrapAlarmTestInProgresssecond NOTIFICATION-TYPE
- OBJECTS { upsTestIdsecond }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapssecond 24 }
- upsTrapAlarmReceptacleOffsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapssecond 25 }
- upsTrapAlarmHighspeedBusFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapssecond 26 }
- upsTrapAlarmHighspeedBusJACRCFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapssecond 27 }
- upsTrapAlarmConnectivityBusFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { geUPSTrapssecond 28 }
- upsTrapAlarmHighspeedBusJBCRCFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapssecond 29 }
- upsTrapAlarmCurrentSharingFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapssecond 30 }
- upsTrapAlarmDCRippleFailuresecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapssecond 31 }
- upsTrapAlarmBatteryBadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapssecond 33 }
- upsTrapAlarmOnBatteryRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapssecond 34 }
- upsTrapAlarmLowBatteryRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapssecond 35 }
- upsTrapAlarmDepletedBatteryRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapssecond 36 }
- upsTrapAlarmTempBadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapssecond 37 }
- upsTrapAlarmInputBadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapssecond 38 }
- upsTrapAlarmOutputBadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapssecond 39 }
- upsTrapAlarmOutputOverloadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapssecond 40 }
- upsTrapAlarmOnBypassRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapssecond 41 }
- upsTrapAlarmBypassBadRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapssecond 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapssecond 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapssecond 44 }
- upsTrapAlarmChargerFailedRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapssecond 45 }
- upsTrapAlarmUpsOutputOnsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapssecond 46 }
- upsTrapAlarmUpsSystemOnsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapssecond 47 }
- upsTrapAlarmFanFailureRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapssecond 48 }
- upsTrapAlarmFuseFailureRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapssecond 49 }
- upsTrapAlarmGeneralFaultRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapssecond 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapssecond 51 }
- upsTrapAlarmCommunicationsLostRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapssecond 52 }
- upsTrapAlarmAwaitingPowerRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapssecond 53 }
- upsTrapAlarmShutdownPendingRestoredsecond NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaysecond }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapssecond 54 }
- upsTrapAlarmShutdownImminentRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapssecond 55 }
- upsTrapAlarmTestInProgressRestoredsecond NOTIFICATION-TYPE
- OBJECTS { upsTestIdsecond }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapssecond 56 }
- upsTrapAlarmReceptacleOnsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapssecond 57 }
- upsTrapAlarmHighspeedBusRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapssecond 58 }
- upsTrapAlarmHighspeedBusJACRCRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapssecond 59 }
- upsTrapAlarmConnectivityBusRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapssecond 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapssecond 61 }
- upsTrapAlarmCurrentSharingRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapssecond 62 }
- upsTrapAlarmDCRippleRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapssecond 63 }
- upsTrapAlarmValueLowsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapssecond 129 }
- upsTrapAlarmValueHighsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapssecond 130 }
- upsTrapAlarmValueLowRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapssecond 133 }
- upsTrapAlarmValueHighRestoredsecond NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapssecond 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatussecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticsecond 1 }
- upsDiagnosticBusJBCommunicationStatussecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticsecond 2 }
- upsDiagnosticBatteryLifetimesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsecond 3 }
- upsDiagnosticFansLifetimesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsecond 4 }
- upsDiagnosticDCcapacitorsLifetimesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsecond 5 }
- upsDiagnosticACcapacitorsLifetimesecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsecond 6 }
- upsDiagnosticGlobalServiceChecksecond OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsecond 7 }
- --
- -- The Device Identification group. Third
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturerthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentthird 1 }
- upsIdentModelthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentthird 2 }
- upsIdentUPSSoftwareVersionthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentthird 3 }
- upsIdentAgentSoftwareVersionthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentthird 4 }
- upsIdentNamethird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentthird 5 }
- upsIdentAttachedDevicesthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentthird 6 }
- upsIdentUPSSerialNumberthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentthird 7 }
- upsIdentComProtVersionthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentthird 8 }
- upsIdentOperatingTimethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentthird 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatusthird OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatterythird 1 }
- upsSecondsOnBatterythird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Seconds"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatterythird 2 }
- upsEstimatedMinutesRemainingthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatterythird 3 }
- upsEstimatedChargeRemainingthird OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatterythird 4 }
- upsBatteryVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatterythird 5 }
- upsBatteryCurrentthird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatterythird 6 }
- upsBatteryTemperaturethird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatterythird 7 }
- upsBatteryRipplethird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatterythird 8 }
- --
- -- Input Group
- --
- upsInputLineBadsthird OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputthird 1 }
- upsInputNumLinesthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputthird 2 }
- upsInputThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputthird 3 }
- upsInputThirdEntry OBJECT-TYPE
- SYNTAX UpsInputThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexthird }
- ::= { upsInputThirdTable 1 }
- UpsInputThirdEntry ::= SEQUENCE {
- upsInputLineIndexthird PositiveInteger32,
- upsInputFrequencythird NonNegativeInteger32,
- upsInputVoltagethird NonNegativeInteger32,
- upsInputCurrentthird NonNegativeInteger32,
- upsInputTruePowerthird NonNegativeInteger32,
- upsInputVoltageMinthird NonNegativeInteger32,
- upsInputVoltageMaxthird NonNegativeInteger32
- }
- upsInputLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputThirdEntry 1 }
- upsInputFrequencythird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputThirdEntry 2 }
- upsInputVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputThirdEntry 3 }
- upsInputCurrentthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputThirdEntry 4 }
- upsInputTruePowerthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputThirdEntry 5 }
- upsInputVoltageMinthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputThirdEntry 6 }
- upsInputVoltageMaxthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputThirdEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcethird OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputthird 1 }
- upsOutputFrequencythird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputthird 2 }
- upsOutputNumLinesthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputthird 3 }
- upsOutputThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputthird 4 }
- upsOutputThirdEntry OBJECT-TYPE
- SYNTAX UpsOutputThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexthird }
- ::= { upsOutputThirdTable 1 }
- UpsOutputThirdEntry ::= SEQUENCE {
- upsOutputLineIndexthird PositiveInteger32,
- upsOutputVoltagethird NonNegativeInteger32,
- upsOutputCurrentthird NonNegativeInteger32,
- upsOutputPowerthird NonNegativeInteger32,
- upsOutputPercentLoadthird Integer32,
- upsOutputPowerFactorthird Integer32,
- upsOutputPeakCurrentthird Integer32,
- upsOutputShareCurrentthird Integer32
- }
- upsOutputLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputThirdEntry 1 }
- upsOutputVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputThirdEntry 2 }
- upsOutputCurrentthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputThirdEntry 3 }
- upsOutputPowerthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputThirdEntry 4 }
- upsOutputPercentLoadthird OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputThirdEntry 5 }
- upsOutputPowerFactorthird OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputThirdEntry 6 }
- upsOutputPeakCurrentthird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputThirdEntry 7 }
- upsOutputShareCurrentthird OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputThirdEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencythird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypassthird 1 }
- upsBypassNumLinesthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypassthird 2 }
- upsBypassThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypassthird 3 }
- upsBypassThirdEntry OBJECT-TYPE
- SYNTAX UpsBypassThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexthird }
- ::= { upsBypassThirdTable 1 }
- UpsBypassThirdEntry ::= SEQUENCE {
- upsBypassLineIndexthird PositiveInteger32,
- upsBypassVoltagethird NonNegativeInteger32,
- upsBypassCurrentthird NonNegativeInteger32,
- upsBypassPowerthird NonNegativeInteger32
- }
- upsBypassLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassThirdEntry 1 }
- upsBypassVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassThirdEntry 2 }
- upsBypassCurrentthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassThirdEntry 3 }
- upsBypassPowerthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassThirdEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentthird OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmthird 1 }
- upsAlarmThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmthird 2 }
- upsAlarmThirdEntry OBJECT-TYPE
- SYNTAX UpsAlarmThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdthird }
- ::= { upsAlarmThirdTable 1 }
- UpsAlarmThirdEntry ::= SEQUENCE {
- upsAlarmIdthird PositiveInteger32,
- upsAlarmDescrthird AutonomousType,
- upsAlarmTimethird TimeStamp
- }
- upsAlarmIdthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmThirdEntry 1 }
- upsAlarmDescrthird OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmThirdEntry 2 }
- upsAlarmTimethird OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmThirdEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmsthird 1 }
- upsAlarmOnBatterythird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmsthird 2 }
- upsAlarmLowBatterythird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmsthird 3 }
- upsAlarmDepletedBatterythird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmsthird 4 }
- upsAlarmTempBadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsthird 5 }
- upsAlarmInputBadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsthird 6 }
- upsAlarmOutputBadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmsthird 7 }
- upsAlarmOutputOverloadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmsthird 8 }
- upsAlarmOnBypassthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmsthird 9 }
- upsAlarmBypassBadthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsthird 10 }
- upsAlarmOutputOffAsRequestedthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmsthird 11 }
- upsAlarmUpsOffAsRequestedthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmsthird 12 }
- upsAlarmChargerFailedthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmsthird 13 }
- upsAlarmUpsOutputOffthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmsthird 14 }
- upsAlarmUpsSystemOffthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmsthird 15 }
- upsAlarmFanFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmsthird 16 }
- upsAlarmFuseFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmsthird 17 }
- upsAlarmGeneralFaultthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmsthird 18 }
- upsAlarmDiagnosticTestFailedthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmsthird 19 }
- upsAlarmCommunicationsLostthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmsthird 20 }
- upsAlarmAwaitingPowerthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmsthird 21 }
- upsAlarmShutdownPendingthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmsthird 22 }
- upsAlarmShutdownImminentthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 seconds; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmsthird 23 }
- upsAlarmTestInProgressthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmsthird 24 }
- upsAlarmReceptacleOffthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmsthird 25 }
- upsAlarmHighSpeedBusFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmsthird 26 }
- upsAlarmHighSpeedBusJACRCFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmsthird 27 }
- upsAlarmConnectivityBusFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmsthird 28 }
- upsAlarmHighSpeedBusJBCRCFailurethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmsthird 29 }
- upsAlarmCurrentSharingthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmsthird 30 }
- upsAlarmDCRipplethird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmsthird 31 }
- upsAlarmMaskAthird OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmthird 4 }
- --
- -- The Test Group generic
- --
- upsTestIdthird OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestthird 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockthird OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestthird 2 }
- upsTestResultsSummarythird OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestthird 3 }
- upsTestResultsDetailthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestthird 4 }
- upsTestStartTimethird OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestthird 5 }
- upsTestElapsedTimethird OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestthird 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTeststhird 1 }
- upsTestAbortTestInProgressthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTeststhird 2 }
- upsTestGeneralSystemsTestthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTeststhird 3 }
- upsTestQuickBatteryTestthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTeststhird 4 }
- upsTestDeepBatteryCalibrationthird OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTeststhird 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypethird OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlthird 1 }
- upsShutdownAfterDelaythird OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "Seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of Seconds, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- seconds remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlthird 2 }
- upsStartupAfterDelaythird OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "Seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of seconds, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of seconds until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlthird 3 }
- upsRebootWithDurationthird OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "Seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of seconds, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of seconds required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 seconds. When read, upsRebootWithDuration
- shall return the number of seconds remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlthird 4 }
- upsAutoRestartthird OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlthird 5 }
- upsReceptaclesNumthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlthird 6 }
- upsReceptacleThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlthird 7 }
- upsReceptacleThirdEntry OBJECT-TYPE
- SYNTAX UpsReceptacleThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexthird }
- ::= { upsReceptacleThirdTable 1 }
- UpsReceptacleThirdEntry ::= SEQUENCE {
- upsReceptacleLineIndexthird PositiveInteger32,
- upsReceptacleOnOffthird INTEGER
- }
- upsReceptacleLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleThirdEntry 1 }
- upsReceptacleOnOffthird OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleThirdEntry 2 }
- upsUPSModethird OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlthird 8 }
- upsRectifierOnOffthird OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlthird 9 }
- upsBatteryChargeMethodthird OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlthird 10 }
- upsInverterOnOffthird OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlthird 11 }
- upsBypassOnOffthird OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlthird 12 }
- upsLoadSourcethird OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlthird 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigthird 1 }
- upsConfigInputFreqthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigthird 2 }
- upsConfigOutputVoltagethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigthird 3 }
- upsConfigOutputFreqthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigthird 4 }
- upsConfigOutputVAthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigthird 5 }
- upsConfigOutputPowerthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigthird 6 }
- upsConfigLowBattTimethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigthird 7 }
- upsConfigAudibleStatusthird OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigthird 8 }
- upsConfigLowVoltageTransferPointthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigthird 9 }
- upsConfigHighVoltageTransferPointthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigthird 10 }
- upsConfigBatteryCapacitythird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigthird 11 }
- upsConfigBatteryChargeCurrentthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigthird 12 }
- upsConfigNoLoadShutdownthird OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigthird 13 }
- upsConfigStartDelaythird OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigthird 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetthird 1 }
- upsEventGetPreviousthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetthird 2 }
- upsEventSetStartingTimeStampthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetthird 3 }
- upsEventRetreiveCurrentTimeStampthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetthird 4 }
- upsEventTableSizethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetthird 5 }
- upsEventThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetthird 6 }
- upsEventThirdEntry OBJECT-TYPE
- SYNTAX UpsEventThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexthird }
- ::= { upsEventThirdTable 1 }
- UpsEventThirdEntry ::= SEQUENCE {
- upsEventLineIndexthird PositiveInteger32,
- upsEventCodethird Integer32,
- upsEventStatusthird NonNegativeInteger32,
- upsEventTimethird NonNegativeInteger32
- }
- upsEventLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventThirdEntry 1 }
- upsEventCodethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventThirdEntry 2 }
- upsEventStatusthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventThirdEntry 3 }
- upsEventTimethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventThirdEntry 4 }
- upsParametersReadthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetthird 7 }
- upsParametersWritethird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the third value
- of the table with the lowest index number."
- ::= { upsGetSetthird 8 }
- upsParametersStartAddressthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetthird 9 }
- upsParameterTableSizethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetthird 10 }
- upsParameterThirdTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetthird 11 }
- upsParameterThirdEntry OBJECT-TYPE
- SYNTAX UpsParameterThirdEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexthird }
- ::= { upsParameterThirdTable 1 }
- UpsParameterThirdEntry ::= SEQUENCE {
- upsParameterLineIndexthird PositiveInteger32,
- upsParameterValuethird Integer32
- }
- upsParameterLineIndexthird OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterThirdEntry 1 }
- upsParameterValuethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterThirdEntry 2 }
- upsStatusthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetthird 12 }
- upsMainsStatisticsMBfailthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetthird 13 }
- upsMainsStatisticsMRfailthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetthird 14 }
- upsMainsStatisticsB2third OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetthird 15 }
- upsMainsStatisticsB5third OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetthird 16 }
- upsMainsStatisticsB10third OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetthird 17 }
- upsMainsStatisticsB200third OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetthird 18 }
- upsMainsStatisticsBypRelthird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetthird 19 }
- upsTimethird OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMP second ERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetthird 20 }
- upsRequestPermissionthird OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetthird 21 }
- upsEventGetCodethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetthird 22 }
- upsEventSpinLockthird OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetthird 23 }
- upsParameterSpinLockthird OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetthird 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapsthird 1 }
- upsTrapAlarmOnBatterythird NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatterythird }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapsthird 2 }
- upsTrapAlarmLowBatterythird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapsthird 3 }
- upsTrapAlarmDepletedBatterythird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapsthird 4 }
- upsTrapAlarmTempBadthird NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapsthird 5 }
- upsTrapAlarmInputBadthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapsthird 6 }
- upsTrapAlarmOutputBadthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapsthird 7 }
- upsTrapAlarmOutputOverloadthird NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinesthird, upsOutputPercentLoadthird }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapsthird 8 }
- upsTrapAlarmOnBypassthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapsthird 9 }
- upsTrapAlarmBypassBadthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapsthird 10 }
- upsTrapAlarmOutputOffAsRequestedthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapsthird 11 }
- upsTrapAlarmUpsOffAsRequestedthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapsthird 12 }
- upsTrapAlarmChargerFailedthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapsthird 13 }
- upsTrapAlarmUpsOutputOffthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapsthird 14 }
- upsTrapAlarmUpsSystemOffthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapsthird 15 }
- upsTrapAlarmFanFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapsthird 16 }
- upsTrapAlarmFuseFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapsthird 17 }
- upsTrapAlarmGeneralFaultthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapsthird 18 }
- upsTrapAlarmDiagnosticTestFailedthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapsthird 19 }
- upsTrapAlarmCommunicationsLostthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapsthird 20 }
- upsTrapAlarmAwaitingPowerthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapsthird 21 }
- upsTrapAlarmShutdownPendingthird NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaythird }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapsthird 22 }
- upsTrapAlarmShutdownImminentthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 secondss; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapsthird 23 }
- upsTrapAlarmTestInProgressthird NOTIFICATION-TYPE
- OBJECTS { upsTestIdthird }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapsthird 24 }
- upsTrapAlarmReceptacleOffthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapsthird 25 }
- upsTrapAlarmHighspeedBusFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapsthird 26 }
- upsTrapAlarmHighspeedBusJACRCFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapsthird 27 }
- upsTrapAlarmConnectivityBusFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { geUPSTrapsthird 28 }
- upsTrapAlarmHighspeedBusJBCRCFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsthird 29 }
- upsTrapAlarmCurrentSharingFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapsthird 30 }
- upsTrapAlarmDCRippleFailurethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapsthird 31 }
- upsTrapAlarmBatteryBadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapsthird 33 }
- upsTrapAlarmOnBatteryRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapsthird 34 }
- upsTrapAlarmLowBatteryRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapsthird 35 }
- upsTrapAlarmDepletedBatteryRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapsthird 36 }
- upsTrapAlarmTempBadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapsthird 37 }
- upsTrapAlarmInputBadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapsthird 38 }
- upsTrapAlarmOutputBadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapsthird 39 }
- upsTrapAlarmOutputOverloadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapsthird 40 }
- upsTrapAlarmOnBypassRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapsthird 41 }
- upsTrapAlarmBypassBadRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapsthird 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapsthird 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapsthird 44 }
- upsTrapAlarmChargerFailedRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapsthird 45 }
- upsTrapAlarmUpsOutputOnthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapsthird 46 }
- upsTrapAlarmUpsSystemOnthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapsthird 47 }
- upsTrapAlarmFanFailureRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapsthird 48 }
- upsTrapAlarmFuseFailureRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapsthird 49 }
- upsTrapAlarmGeneralFaultRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapsthird 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapsthird 51 }
- upsTrapAlarmCommunicationsLostRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapsthird 52 }
- upsTrapAlarmAwaitingPowerRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapsthird 53 }
- upsTrapAlarmShutdownPendingRestoredthird NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaythird }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapsthird 54 }
- upsTrapAlarmShutdownImminentRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapsthird 55 }
- upsTrapAlarmTestInProgressRestoredthird NOTIFICATION-TYPE
- OBJECTS { upsTestIdthird }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapsthird 56 }
- upsTrapAlarmReceptacleOnthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapsthird 57 }
- upsTrapAlarmHighspeedBusRestorethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapsthird 58 }
- upsTrapAlarmHighspeedBusJACRCRestorethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapsthird 59 }
- upsTrapAlarmConnectivityBusRestorethird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapsthird 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapsthird 61 }
- upsTrapAlarmCurrentSharingRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapsthird 62 }
- upsTrapAlarmDCRippleRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapsthird 63 }
- upsTrapAlarmValueLowthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapsthird 129 }
- upsTrapAlarmValueHighthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapsthird 130 }
- upsTrapAlarmValueLowRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapsthird 133 }
- upsTrapAlarmValueHighRestoredthird NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapsthird 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatusthird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticthird 1 }
- upsDiagnosticBusJBCommunicationStatusthird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticthird 2 }
- upsDiagnosticBatteryLifetimethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticthird 3 }
- upsDiagnosticFansLifetimethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticthird 4 }
- upsDiagnosticDCcapacitorsLifetimethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticthird 5 }
- upsDiagnosticACcapacitorsLifetimethird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticthird 6 }
- upsDiagnosticGlobalServiceCheckthird OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticthird 7 }
- --
- -- The Device Identification group. Fourth
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturerfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentfourth 1 }
- upsIdentModelfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentfourth 2 }
- upsIdentUPSSoftwareVersionfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfourth 3 }
- upsIdentAgentSoftwareVersionfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfourth 4 }
- upsIdentNamefourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentfourth 5 }
- upsIdentAttachedDevicesfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentfourth 6 }
- upsIdentUPSSerialNumberfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentfourth 7 }
- upsIdentComProtVersionfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentfourth 8 }
- upsIdentOperatingTimefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "fourths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentfourth 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatusfourth OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatteryfourth 1 }
- upsSecondsOnBatteryfourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "fourths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatteryfourth 2 }
- upsEstimatedMinutesRemainingfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatteryfourth 3 }
- upsEstimatedChargeRemainingfourth OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatteryfourth 4 }
- upsBatteryVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatteryfourth 5 }
- upsBatteryCurrentfourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatteryfourth 6 }
- upsBatteryTemperaturefourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatteryfourth 7 }
- upsBatteryRipplefourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatteryfourth 8 }
- --
- -- Input Group
- --
- upsInputLineBadsfourth OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputfourth 1 }
- upsInputNumLinesfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputfourth 2 }
- upsInputFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputfourth 3 }
- upsInputFourthEntry OBJECT-TYPE
- SYNTAX UpsInputFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexfourth }
- ::= { upsInputFourthTable 1 }
- UpsInputFourthEntry ::= SEQUENCE {
- upsInputLineIndexfourth PositiveInteger32,
- upsInputFrequencyfourth NonNegativeInteger32,
- upsInputVoltagefourth NonNegativeInteger32,
- upsInputCurrentfourth NonNegativeInteger32,
- upsInputTruePowerfourth NonNegativeInteger32,
- upsInputVoltageMinfourth NonNegativeInteger32,
- upsInputVoltageMaxfourth NonNegativeInteger32
- }
- upsInputLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputFourthEntry 1 }
- upsInputFrequencyfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputFourthEntry 2 }
- upsInputVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputFourthEntry 3 }
- upsInputCurrentfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputFourthEntry 4 }
- upsInputTruePowerfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputFourthEntry 5 }
- upsInputVoltageMinfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputFourthEntry 6 }
- upsInputVoltageMaxfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputFourthEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcefourth OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputfourth 1 }
- upsOutputFrequencyfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputfourth 2 }
- upsOutputNumLinesfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputfourth 3 }
- upsOutputFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputfourth 4 }
- upsOutputFourthEntry OBJECT-TYPE
- SYNTAX UpsOutputFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexfourth }
- ::= { upsOutputFourthTable 1 }
- UpsOutputFourthEntry ::= SEQUENCE {
- upsOutputLineIndexfourth PositiveInteger32,
- upsOutputVoltagefourth NonNegativeInteger32,
- upsOutputCurrentfourth NonNegativeInteger32,
- upsOutputPowerfourth NonNegativeInteger32,
- upsOutputPercentLoadfourth Integer32,
- upsOutputPowerFactorfourth Integer32,
- upsOutputPeakCurrentfourth Integer32,
- upsOutputShareCurrentfourth Integer32
- }
- upsOutputLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputFourthEntry 1 }
- upsOutputVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputFourthEntry 2 }
- upsOutputCurrentfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputFourthEntry 3 }
- upsOutputPowerfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputFourthEntry 4 }
- upsOutputPercentLoadfourth OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputFourthEntry 5 }
- upsOutputPowerFactorfourth OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputFourthEntry 6 }
- upsOutputPeakCurrentfourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputFourthEntry 7 }
- upsOutputShareCurrentfourth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputFourthEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencyfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypassfourth 1 }
- upsBypassNumLinesfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypassfourth 2 }
- upsBypassFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypassfourth 3 }
- upsBypassFourthEntry OBJECT-TYPE
- SYNTAX UpsBypassFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexfourth }
- ::= { upsBypassFourthTable 1 }
- UpsBypassFourthEntry ::= SEQUENCE {
- upsBypassLineIndexfourth PositiveInteger32,
- upsBypassVoltagefourth NonNegativeInteger32,
- upsBypassCurrentfourth NonNegativeInteger32,
- upsBypassPowerfourth NonNegativeInteger32
- }
- upsBypassLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassFourthEntry 1 }
- upsBypassVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassFourthEntry 2 }
- upsBypassCurrentfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassFourthEntry 3 }
- upsBypassPowerfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassFourthEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentfourth OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmfourth 1 }
- upsAlarmFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmfourth 2 }
- upsAlarmFourthEntry OBJECT-TYPE
- SYNTAX UpsAlarmFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdfourth }
- ::= { upsAlarmFourthTable 1 }
- UpsAlarmFourthEntry ::= SEQUENCE {
- upsAlarmIdfourth PositiveInteger32,
- upsAlarmDescrfourth AutonomousType,
- upsAlarmTimefourth TimeStamp
- }
- upsAlarmIdfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmFourthEntry 1 }
- upsAlarmDescrfourth OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmFourthEntry 2 }
- upsAlarmTimefourth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmFourthEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmsfourth 1 }
- upsAlarmOnBatteryfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmsfourth 2 }
- upsAlarmLowBatteryfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmsfourth 3 }
- upsAlarmDepletedBatteryfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmsfourth 4 }
- upsAlarmTempBadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfourth 5 }
- upsAlarmInputBadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfourth 6 }
- upsAlarmOutputBadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfourth 7 }
- upsAlarmOutputOverloadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmsfourth 8 }
- upsAlarmOnBypassfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmsfourth 9 }
- upsAlarmBypassBadfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfourth 10 }
- upsAlarmOutputOffAsRequestedfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmsfourth 11 }
- upsAlarmUpsOffAsRequestedfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmsfourth 12 }
- upsAlarmChargerFailedfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmsfourth 13 }
- upsAlarmUpsOutputOfffourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmsfourth 14 }
- upsAlarmUpsSystemOfffourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmsfourth 15 }
- upsAlarmFanFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmsfourth 16 }
- upsAlarmFuseFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmsfourth 17 }
- upsAlarmGeneralFaultfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmsfourth 18 }
- upsAlarmDiagnosticTestFailedfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmsfourth 19 }
- upsAlarmCommunicationsLostfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmsfourth 20 }
- upsAlarmAwaitingPowerfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmsfourth 21 }
- upsAlarmShutdownPendingfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmsfourth 22 }
- upsAlarmShutdownImminentfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 fourths; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmsfourth 23 }
- upsAlarmTestInProgressfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmsfourth 24 }
- upsAlarmReceptacleOfffourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmsfourth 25 }
- upsAlarmHighSpeedBusFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmsfourth 26 }
- upsAlarmHighSpeedBusJACRCFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmsfourth 27 }
- upsAlarmConnectivityBusFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { upsWellKnownAlarmsfourth 28 }
- upsAlarmHighSpeedBusJBCRCFailurefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmsfourth 29 }
- upsAlarmCurrentSharingfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmsfourth 30 }
- upsAlarmDCRipplefourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmsfourth 31 }
- upsAlarmMaskAfourth OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmfourth 4 }
- --
- -- The Test Group generic
- --
- upsTestIdfourth OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestfourth 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockfourth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestfourth 2 }
- upsTestResultsSummaryfourth OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestfourth 3 }
- upsTestResultsDetailfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestfourth 4 }
- upsTestStartTimefourth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestfourth 5 }
- upsTestElapsedTimefourth OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestfourth 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestsfourth 1 }
- upsTestAbortTestInProgressfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestsfourth 2 }
- upsTestGeneralSystemsTestfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestsfourth 3 }
- upsTestQuickBatteryTestfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestsfourth 4 }
- upsTestDeepBatteryCalibrationfourth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestsfourth 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypefourth OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlfourth 1 }
- upsShutdownAfterDelayfourth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "fourths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of fourths, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- fourths remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlfourth 2 }
- upsStartupAfterDelayfourth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "fourths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of fourths, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of fourths until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlfourth 3 }
- upsRebootWithDurationfourth OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "fourths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of fourths, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of fourths required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 fourths. When read, upsRebootWithDuration
- shall return the number of fourths remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlfourth 4 }
- upsAutoRestartfourth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlfourth 5 }
- upsReceptaclesNumfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlfourth 6 }
- upsReceptacleFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlfourth 7 }
- upsReceptacleFourthEntry OBJECT-TYPE
- SYNTAX UpsReceptacleFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexfourth }
- ::= { upsReceptacleFourthTable 1 }
- UpsReceptacleFourthEntry ::= SEQUENCE {
- upsReceptacleLineIndexfourth PositiveInteger32,
- upsReceptacleOnOfffourth INTEGER
- }
- upsReceptacleLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleFourthEntry 1 }
- upsReceptacleOnOfffourth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleFourthEntry 2 }
- upsUPSModefourth OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlfourth 8 }
- upsRectifierOnOfffourth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlfourth 9 }
- upsBatteryChargeMethodfourth OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlfourth 10 }
- upsInverterOnOfffourth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlfourth 11 }
- upsBypassOnOfffourth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlfourth 12 }
- upsLoadSourcefourth OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlfourth 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfourth 1 }
- upsConfigInputFreqfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfourth 2 }
- upsConfigOutputVoltagefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfourth 3 }
- upsConfigOutputFreqfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfourth 4 }
- upsConfigOutputVAfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigfourth 5 }
- upsConfigOutputPowerfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigfourth 6 }
- upsConfigLowBattTimefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigfourth 7 }
- upsConfigAudibleStatusfourth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigfourth 8 }
- upsConfigLowVoltageTransferPointfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfourth 9 }
- upsConfigHighVoltageTransferPointfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfourth 10 }
- upsConfigBatteryCapacityfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigfourth 11 }
- upsConfigBatteryChargeCurrentfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigfourth 12 }
- upsConfigNoLoadShutdownfourth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigfourth 13 }
- upsConfigStartDelayfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigfourth 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetfourth 1 }
- upsEventGetPreviousfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetfourth 2 }
- upsEventSetStartingTimeStampfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetfourth 3 }
- upsEventRetreiveCurrentTimeStampfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetfourth 4 }
- upsEventTableSizefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetfourth 5 }
- upsEventFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetfourth 6 }
- upsEventFourthEntry OBJECT-TYPE
- SYNTAX UpsEventFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexfourth }
- ::= { upsEventFourthTable 1 }
- UpsEventFourthEntry ::= SEQUENCE {
- upsEventLineIndexfourth PositiveInteger32,
- upsEventCodefourth Integer32,
- upsEventStatusfourth NonNegativeInteger32,
- upsEventTimefourth NonNegativeInteger32
- }
- upsEventLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventFourthEntry 1 }
- upsEventCodefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventFourthEntry 2 }
- upsEventStatusfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventFourthEntry 3 }
- upsEventTimefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventFourthEntry 4 }
- upsParametersReadfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetfourth 7 }
- upsParametersWritefourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the fourth value
- of the table with the lowest index number."
- ::= { upsGetSetfourth 8 }
- upsParametersStartAddressfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetfourth 9 }
- upsParameterTableSizefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetfourth 10 }
- upsParameterFourthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetfourth 11 }
- upsParameterFourthEntry OBJECT-TYPE
- SYNTAX UpsParameterFourthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexfourth }
- ::= { upsParameterFourthTable 1 }
- UpsParameterFourthEntry ::= SEQUENCE {
- upsParameterLineIndexfourth PositiveInteger32,
- upsParameterValuefourth Integer32
- }
- upsParameterLineIndexfourth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterFourthEntry 1 }
- upsParameterValuefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterFourthEntry 2 }
- upsStatusfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetfourth 12 }
- upsMainsStatisticsMBfailfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetfourth 13 }
- upsMainsStatisticsMRfailfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetfourth 14 }
- upsMainsStatisticsB2fourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetfourth 15 }
- upsMainsStatisticsB5fourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetfourth 16 }
- upsMainsStatisticsB10fourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetfourth 17 }
- upsMainsStatisticsB200fourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetfourth 18 }
- upsMainsStatisticsBypRelfourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetfourth 19 }
- upsTimefourth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPfourthERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetfourth 20 }
- upsRequestPermissionfourth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetfourth 21 }
- upsEventGetCodefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetfourth 22 }
- upsEventSpinLockfourth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetfourth 23 }
- upsParameterSpinLockfourth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetfourth 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapsfourth 1 }
- upsTrapAlarmOnBatteryfourth NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatteryfourth }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapsfourth 2 }
- upsTrapAlarmLowBatteryfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapsfourth 3 }
- upsTrapAlarmDepletedBatteryfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapsfourth 4 }
- upsTrapAlarmTempBadfourth NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapsfourth 5 }
- upsTrapAlarmInputBadfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapsfourth 6 }
- upsTrapAlarmOutputBadfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapsfourth 7 }
- upsTrapAlarmOutputOverloadfourth NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinesfourth, upsOutputPercentLoadfourth }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapsfourth 8 }
- upsTrapAlarmOnBypassfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapsfourth 9 }
- upsTrapAlarmBypassBadfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapsfourth 10 }
- upsTrapAlarmOutputOffAsRequestedfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapsfourth 11 }
- upsTrapAlarmUpsOffAsRequestedfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapsfourth 12 }
- upsTrapAlarmChargerFailedfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapsfourth 13 }
- upsTrapAlarmUpsOutputOfffourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapsfourth 14 }
- upsTrapAlarmUpsSystemOfffourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapsfourth 15 }
- upsTrapAlarmFanFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapsfourth 16 }
- upsTrapAlarmFuseFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapsfourth 17 }
- upsTrapAlarmGeneralFaultfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapsfourth 18 }
- upsTrapAlarmDiagnosticTestFailedfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapsfourth 19 }
- upsTrapAlarmCommunicationsLostfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapsfourth 20 }
- upsTrapAlarmAwaitingPowerfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapsfourth 21 }
- upsTrapAlarmShutdownPendingfourth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfourth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapsfourth 22 }
- upsTrapAlarmShutdownImminentfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 fourths; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapsfourth 23 }
- upsTrapAlarmTestInProgressfourth NOTIFICATION-TYPE
- OBJECTS { upsTestIdfourth }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapsfourth 24 }
- upsTrapAlarmReceptacleOfffourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapsfourth 25 }
- upsTrapAlarmHighspeedBusFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapsfourth 26 }
- upsTrapAlarmHighspeedBusJACRCFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapsfourth 27 }
- upsTrapAlarmConnectivityBusFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { geUPSTrapsfourth 28 }
- upsTrapAlarmHighspeedBusJBCRCFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsfourth 29 }
- upsTrapAlarmCurrentSharingFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapsfourth 30 }
- upsTrapAlarmDCRippleFailurefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapsfourth 31 }
- upsTrapAlarmBatteryBadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapsfourth 33 }
- upsTrapAlarmOnBatteryRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapsfourth 34 }
- upsTrapAlarmLowBatteryRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapsfourth 35 }
- upsTrapAlarmDepletedBatteryRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapsfourth 36 }
- upsTrapAlarmTempBadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapsfourth 37 }
- upsTrapAlarmInputBadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapsfourth 38 }
- upsTrapAlarmOutputBadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapsfourth 39 }
- upsTrapAlarmOutputOverloadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapsfourth 40 }
- upsTrapAlarmOnBypassRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapsfourth 41 }
- upsTrapAlarmBypassBadRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapsfourth 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapsfourth 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapsfourth 44 }
- upsTrapAlarmChargerFailedRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapsfourth 45 }
- upsTrapAlarmUpsOutputOnfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapsfourth 46 }
- upsTrapAlarmUpsSystemOnfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapsfourth 47 }
- upsTrapAlarmFanFailureRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapsfourth 48 }
- upsTrapAlarmFuseFailureRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapsfourth 49 }
- upsTrapAlarmGeneralFaultRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapsfourth 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapsfourth 51 }
- upsTrapAlarmCommunicationsLostRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapsfourth 52 }
- upsTrapAlarmAwaitingPowerRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapsfourth 53 }
- upsTrapAlarmShutdownPendingRestoredfourth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfourth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapsfourth 54 }
- upsTrapAlarmShutdownImminentRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapsfourth 55 }
- upsTrapAlarmTestInProgressRestoredfourth NOTIFICATION-TYPE
- OBJECTS { upsTestIdfourth }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapsfourth 56 }
- upsTrapAlarmReceptacleOnfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapsfourth 57 }
- upsTrapAlarmHighspeedBusRestorefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapsfourth 58 }
- upsTrapAlarmHighspeedBusJACRCRestorefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapsfourth 59 }
- upsTrapAlarmConnectivityBusRestorefourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapsfourth 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapsfourth 61 }
- upsTrapAlarmCurrentSharingRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapsfourth 62 }
- upsTrapAlarmDCRippleRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapsfourth 63 }
- upsTrapAlarmValueLowfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapsfourth 129 }
- upsTrapAlarmValueHighfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapsfourth 130 }
- upsTrapAlarmValueLowRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapsfourth 133 }
- upsTrapAlarmValueHighRestoredfourth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapsfourth 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatusfourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfourth 1 }
- upsDiagnosticBusJBCommunicationStatusfourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfourth 2 }
- upsDiagnosticBatteryLifetimefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfourth 3 }
- upsDiagnosticFansLifetimefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfourth 4 }
- upsDiagnosticDCcapacitorsLifetimefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfourth 5 }
- upsDiagnosticACcapacitorsLifetimefourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfourth 6 }
- upsDiagnosticGlobalServiceCheckfourth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfourth 7 }
- --
- -- The Device Identification group. Fifth
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturerfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentfifth 1 }
- upsIdentModelfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentfifth 2 }
- upsIdentUPSSoftwareVersionfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfifth 3 }
- upsIdentAgentSoftwareVersionfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentfifth 4 }
- upsIdentNamefifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentfifth 5 }
- upsIdentAttachedDevicesfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentfifth 6 }
- upsIdentUPSSerialNumberfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentfifth 7 }
- upsIdentComProtVersionfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentfifth 8 }
- upsIdentOperatingTimefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "fifths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentfifth 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatusfifth OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatteryfifth 1 }
- upsSecondsOnBatteryfifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "fifths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatteryfifth 2 }
- upsEstimatedMinutesRemainingfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatteryfifth 3 }
- upsEstimatedChargeRemainingfifth OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatteryfifth 4 }
- upsBatteryVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatteryfifth 5 }
- upsBatteryCurrentfifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatteryfifth 6 }
- upsBatteryTemperaturefifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatteryfifth 7 }
- upsBatteryRipplefifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatteryfifth 8 }
- --
- -- Input Group
- --
- upsInputLineBadsfifth OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputfifth 1 }
- upsInputNumLinesfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputfifth 2 }
- upsInputFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputfifth 3 }
- upsInputFifthEntry OBJECT-TYPE
- SYNTAX UpsInputFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexfifth }
- ::= { upsInputFifthTable 1 }
- UpsInputFifthEntry ::= SEQUENCE {
- upsInputLineIndexfifth PositiveInteger32,
- upsInputFrequencyfifth NonNegativeInteger32,
- upsInputVoltagefifth NonNegativeInteger32,
- upsInputCurrentfifth NonNegativeInteger32,
- upsInputTruePowerfifth NonNegativeInteger32,
- upsInputVoltageMinfifth NonNegativeInteger32,
- upsInputVoltageMaxfifth NonNegativeInteger32
- }
- upsInputLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputFifthEntry 1 }
- upsInputFrequencyfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputFifthEntry 2 }
- upsInputVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputFifthEntry 3 }
- upsInputCurrentfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputFifthEntry 4 }
- upsInputTruePowerfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputFifthEntry 5 }
- upsInputVoltageMinfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputFifthEntry 6 }
- upsInputVoltageMaxfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputFifthEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcefifth OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputfifth 1 }
- upsOutputFrequencyfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputfifth 2 }
- upsOutputNumLinesfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputfifth 3 }
- upsOutputFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputfifth 4 }
- upsOutputFifthEntry OBJECT-TYPE
- SYNTAX UpsOutputFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexfifth }
- ::= { upsOutputFifthTable 1 }
- UpsOutputFifthEntry ::= SEQUENCE {
- upsOutputLineIndexfifth PositiveInteger32,
- upsOutputVoltagefifth NonNegativeInteger32,
- upsOutputCurrentfifth NonNegativeInteger32,
- upsOutputPowerfifth NonNegativeInteger32,
- upsOutputPercentLoadfifth Integer32,
- upsOutputPowerFactorfifth Integer32,
- upsOutputPeakCurrentfifth Integer32,
- upsOutputShareCurrentfifth Integer32
- }
- upsOutputLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputFifthEntry 1 }
- upsOutputVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputFifthEntry 2 }
- upsOutputCurrentfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputFifthEntry 3 }
- upsOutputPowerfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputFifthEntry 4 }
- upsOutputPercentLoadfifth OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputFifthEntry 5 }
- upsOutputPowerFactorfifth OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputFifthEntry 6 }
- upsOutputPeakCurrentfifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputFifthEntry 7 }
- upsOutputShareCurrentfifth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputFifthEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencyfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypassfifth 1 }
- upsBypassNumLinesfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypassfifth 2 }
- upsBypassFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypassfifth 3 }
- upsBypassFifthEntry OBJECT-TYPE
- SYNTAX UpsBypassFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexfifth }
- ::= { upsBypassFifthTable 1 }
- UpsBypassFifthEntry ::= SEQUENCE {
- upsBypassLineIndexfifth PositiveInteger32,
- upsBypassVoltagefifth NonNegativeInteger32,
- upsBypassCurrentfifth NonNegativeInteger32,
- upsBypassPowerfifth NonNegativeInteger32
- }
- upsBypassLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassFifthEntry 1 }
- upsBypassVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassFifthEntry 2 }
- upsBypassCurrentfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassFifthEntry 3 }
- upsBypassPowerfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassFifthEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentfifth OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmfifth 1 }
- upsAlarmFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmfifth 2 }
- upsAlarmFifthEntry OBJECT-TYPE
- SYNTAX UpsAlarmFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdfifth }
- ::= { upsAlarmFifthTable 1 }
- UpsAlarmFifthEntry ::= SEQUENCE {
- upsAlarmIdfifth PositiveInteger32,
- upsAlarmDescrfifth AutonomousType,
- upsAlarmTimefifth TimeStamp
- }
- upsAlarmIdfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmFifthEntry 1 }
- upsAlarmDescrfifth OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmFifthEntry 2 }
- upsAlarmTimefifth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmFifthEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmsfifth 1 }
- upsAlarmOnBatteryfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmsfifth 2 }
- upsAlarmLowBatteryfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmsfifth 3 }
- upsAlarmDepletedBatteryfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmsfifth 4 }
- upsAlarmTempBadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfifth 5 }
- upsAlarmInputBadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfifth 6 }
- upsAlarmOutputBadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfifth 7 }
- upsAlarmOutputOverloadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmsfifth 8 }
- upsAlarmOnBypassfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmsfifth 9 }
- upsAlarmBypassBadfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsfifth 10 }
- upsAlarmOutputOffAsRequestedfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmsfifth 11 }
- upsAlarmUpsOffAsRequestedfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmsfifth 12 }
- upsAlarmChargerFailedfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmsfifth 13 }
- upsAlarmUpsOutputOfffifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmsfifth 14 }
- upsAlarmUpsSystemOfffifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmsfifth 15 }
- upsAlarmFanFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmsfifth 16 }
- upsAlarmFuseFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmsfifth 17 }
- upsAlarmGeneralFaultfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmsfifth 18 }
- upsAlarmDiagnosticTestFailedfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmsfifth 19 }
- upsAlarmCommunicationsLostfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmsfifth 20 }
- upsAlarmAwaitingPowerfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmsfifth 21 }
- upsAlarmShutdownPendingfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmsfifth 22 }
- upsAlarmShutdownImminentfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 fifths; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmsfifth 23 }
- upsAlarmTestInProgressfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmsfifth 24 }
- upsAlarmReceptacleOfffifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmsfifth 25 }
- upsAlarmHighSpeedBusFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmsfifth 26 }
- upsAlarmHighSpeedBusJACRCFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmsfifth 27 }
- upsAlarmConnectivityBusFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmsfifth 28 }
- upsAlarmHighSpeedBusJBCRCFailurefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmsfifth 29 }
- upsAlarmCurrentSharingfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmsfifth 30 }
- upsAlarmDCRipplefifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmsfifth 31 }
- upsAlarmMaskAfifth OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmfifth 4 }
- --
- -- The Test Group generic
- --
- upsTestIdfifth OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestfifth 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockfifth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestfifth 2 }
- upsTestResultsSummaryfifth OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestfifth 3 }
- upsTestResultsDetailfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestfifth 4 }
- upsTestStartTimefifth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestfifth 5 }
- upsTestElapsedTimefifth OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestfifth 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestsfifth 1 }
- upsTestAbortTestInProgressfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestsfifth 2 }
- upsTestGeneralSystemsTestfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestsfifth 3 }
- upsTestQuickBatteryTestfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestsfifth 4 }
- upsTestDeepBatteryCalibrationfifth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestsfifth 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypefifth OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlfifth 1 }
- upsShutdownAfterDelayfifth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "fifths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of fifths, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- fifths remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlfifth 2 }
- upsStartupAfterDelayfifth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "fifths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of fifths, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of fifths until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlfifth 3 }
- upsRebootWithDurationfifth OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "fifths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of fifths, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of fifths required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 fifths. When read, upsRebootWithDuration
- shall return the number of fifths remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlfifth 4 }
- upsAutoRestartfifth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlfifth 5 }
- upsReceptaclesNumfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlfifth 6 }
- upsReceptacleFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlfifth 7 }
- upsReceptacleFifthEntry OBJECT-TYPE
- SYNTAX UpsReceptacleFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexfifth }
- ::= { upsReceptacleFifthTable 1 }
- UpsReceptacleFifthEntry ::= SEQUENCE {
- upsReceptacleLineIndexfifth PositiveInteger32,
- upsReceptacleOnOfffifth INTEGER
- }
- upsReceptacleLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleFifthEntry 1 }
- upsReceptacleOnOfffifth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleFifthEntry 2 }
- upsUPSModefifth OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlfifth 8 }
- upsRectifierOnOfffifth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlfifth 9 }
- upsBatteryChargeMethodfifth OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlfifth 10 }
- upsInverterOnOfffifth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlfifth 11 }
- upsBypassOnOfffifth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlfifth 12 }
- upsLoadSourcefifth OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlfifth 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfifth 1 }
- upsConfigInputFreqfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfifth 2 }
- upsConfigOutputVoltagefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfifth 3 }
- upsConfigOutputFreqfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigfifth 4 }
- upsConfigOutputVAfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigfifth 5 }
- upsConfigOutputPowerfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigfifth 6 }
- upsConfigLowBattTimefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigfifth 7 }
- upsConfigAudibleStatusfifth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigfifth 8 }
- upsConfigLowVoltageTransferPointfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfifth 9 }
- upsConfigHighVoltageTransferPointfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigfifth 10 }
- upsConfigBatteryCapacityfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigfifth 11 }
- upsConfigBatteryChargeCurrentfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigfifth 12 }
- upsConfigNoLoadShutdownfifth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigfifth 13 }
- upsConfigStartDelayfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigfifth 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetfifth 1 }
- upsEventGetPreviousfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetfifth 2 }
- upsEventSetStartingTimeStampfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetfifth 3 }
- upsEventRetreiveCurrentTimeStampfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetfifth 4 }
- upsEventTableSizefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetfifth 5 }
- upsEventFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetfifth 6 }
- upsEventFifthEntry OBJECT-TYPE
- SYNTAX UpsEventFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexfifth }
- ::= { upsEventFifthTable 1 }
- UpsEventFifthEntry ::= SEQUENCE {
- upsEventLineIndexfifth PositiveInteger32,
- upsEventCodefifth Integer32,
- upsEventStatusfifth NonNegativeInteger32,
- upsEventTimefifth NonNegativeInteger32
- }
- upsEventLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventFifthEntry 1 }
- upsEventCodefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventFifthEntry 2 }
- upsEventStatusfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventFifthEntry 3 }
- upsEventTimefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventFifthEntry 4 }
- upsParametersReadfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetfifth 7 }
- upsParametersWritefifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the fifth value
- of the table with the lowest index number."
- ::= { upsGetSetfifth 8 }
- upsParametersStartAddressfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetfifth 9 }
- upsParameterTableSizefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetfifth 10 }
- upsParameterFifthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetfifth 11 }
- upsParameterFifthEntry OBJECT-TYPE
- SYNTAX UpsParameterFifthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexfifth }
- ::= { upsParameterFifthTable 1 }
- UpsParameterFifthEntry ::= SEQUENCE {
- upsParameterLineIndexfifth PositiveInteger32,
- upsParameterValuefifth Integer32
- }
- upsParameterLineIndexfifth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterFifthEntry 1 }
- upsParameterValuefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterFifthEntry 2 }
- upsStatusfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetfifth 12 }
- upsMainsStatisticsMBfailfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetfifth 13 }
- upsMainsStatisticsMRfailfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetfifth 14 }
- upsMainsStatisticsB2fifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetfifth 15 }
- upsMainsStatisticsB5fifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetfifth 16 }
- upsMainsStatisticsB10fifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetfifth 17 }
- upsMainsStatisticsB200fifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetfifth 18 }
- upsMainsStatisticsBypRelfifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetfifth 19 }
- upsTimefifth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPfifthERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetfifth 20 }
- upsRequestPermissionfifth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetfifth 21 }
- upsEventGetCodefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetfifth 22 }
- upsEventSpinLockfifth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetfifth 23 }
- upsParameterSpinLockfifth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetfifth 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapsfifth 1 }
- upsTrapAlarmOnBatteryfifth NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatteryfifth }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapsfifth 2 }
- upsTrapAlarmLowBatteryfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapsfifth 3 }
- upsTrapAlarmDepletedBatteryfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapsfifth 4 }
- upsTrapAlarmTempBadfifth NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapsfifth 5 }
- upsTrapAlarmInputBadfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapsfifth 6 }
- upsTrapAlarmOutputBadfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapsfifth 7 }
- upsTrapAlarmOutputOverloadfifth NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinesfifth, upsOutputPercentLoadfifth }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapsfifth 8 }
- upsTrapAlarmOnBypassfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapsfifth 9 }
- upsTrapAlarmBypassBadfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapsfifth 10 }
- upsTrapAlarmOutputOffAsRequestedfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapsfifth 11 }
- upsTrapAlarmUpsOffAsRequestedfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapsfifth 12 }
- upsTrapAlarmChargerFailedfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapsfifth 13 }
- upsTrapAlarmUpsOutputOfffifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapsfifth 14 }
- upsTrapAlarmUpsSystemOfffifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapsfifth 15 }
- upsTrapAlarmFanFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapsfifth 16 }
- upsTrapAlarmFuseFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapsfifth 17 }
- upsTrapAlarmGeneralFaultfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapsfifth 18 }
- upsTrapAlarmDiagnosticTestFailedfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapsfifth 19 }
- upsTrapAlarmCommunicationsLostfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapsfifth 20 }
- upsTrapAlarmAwaitingPowerfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapsfifth 21 }
- upsTrapAlarmShutdownPendingfifth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfifth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapsfifth 22 }
- upsTrapAlarmShutdownImminentfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 fifths; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapsfifth 23 }
- upsTrapAlarmTestInProgressfifth NOTIFICATION-TYPE
- OBJECTS { upsTestIdfifth }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapsfifth 24 }
- upsTrapAlarmReceptacleOfffifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapsfifth 25 }
- upsTrapAlarmHighspeedBusFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapsfifth 26 }
- upsTrapAlarmHighspeedBusJACRCFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { geUPSTrapsfifth 27 }
- upsTrapAlarmConnectivityBusFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { geUPSTrapsfifth 28 }
- upsTrapAlarmHighspeedBusJBCRCFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsfifth 29 }
- upsTrapAlarmCurrentSharingFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapsfifth 30 }
- upsTrapAlarmDCRippleFailurefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapsfifth 31 }
- upsTrapAlarmBatteryBadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapsfifth 33 }
- upsTrapAlarmOnBatteryRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapsfifth 34 }
- upsTrapAlarmLowBatteryRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapsfifth 35 }
- upsTrapAlarmDepletedBatteryRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapsfifth 36 }
- upsTrapAlarmTempBadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapsfifth 37 }
- upsTrapAlarmInputBadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapsfifth 38 }
- upsTrapAlarmOutputBadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapsfifth 39 }
- upsTrapAlarmOutputOverloadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapsfifth 40 }
- upsTrapAlarmOnBypassRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapsfifth 41 }
- upsTrapAlarmBypassBadRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapsfifth 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapsfifth 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapsfifth 44 }
- upsTrapAlarmChargerFailedRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapsfifth 45 }
- upsTrapAlarmUpsOutputOnfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapsfifth 46 }
- upsTrapAlarmUpsSystemOnfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapsfifth 47 }
- upsTrapAlarmFanFailureRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapsfifth 48 }
- upsTrapAlarmFuseFailureRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapsfifth 49 }
- upsTrapAlarmGeneralFaultRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapsfifth 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapsfifth 51 }
- upsTrapAlarmCommunicationsLostRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapsfifth 52 }
- upsTrapAlarmAwaitingPowerRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapsfifth 53 }
- upsTrapAlarmShutdownPendingRestoredfifth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayfifth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapsfifth 54 }
- upsTrapAlarmShutdownImminentRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapsfifth 55 }
- upsTrapAlarmTestInProgressRestoredfifth NOTIFICATION-TYPE
- OBJECTS { upsTestIdfifth }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapsfifth 56 }
- upsTrapAlarmReceptacleOnfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapsfifth 57 }
- upsTrapAlarmHighspeedBusRestorefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapsfifth 58 }
- upsTrapAlarmHighspeedBusJACRCRestorefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapsfifth 59 }
- upsTrapAlarmConnectivityBusRestorefifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapsfifth 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapsfifth 61 }
- upsTrapAlarmCurrentSharingRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapsfifth 62 }
- upsTrapAlarmDCRippleRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapsfifth 63 }
- upsTrapAlarmValueLowfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapsfifth 129 }
- upsTrapAlarmValueHighfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapsfifth 130 }
- upsTrapAlarmValueLowRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapsfifth 133 }
- upsTrapAlarmValueHighRestoredfifth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapsfifth 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatusfifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfifth 1 }
- upsDiagnosticBusJBCommunicationStatusfifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticfifth 2 }
- upsDiagnosticBatteryLifetimefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfifth 3 }
- upsDiagnosticFansLifetimefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfifth 4 }
- upsDiagnosticDCcapacitorsLifetimefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfifth 5 }
- upsDiagnosticACcapacitorsLifetimefifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfifth 6 }
- upsDiagnosticGlobalServiceCheckfifth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticfifth 7 }
- --
- -- The Device Identification group. Sixth
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturersixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentsixth 1 }
- upsIdentModelsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentsixth 2 }
- upsIdentUPSSoftwareVersionsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentsixth 3 }
- upsIdentAgentSoftwareVersionsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentsixth 4 }
- upsIdentNamesixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentsixth 5 }
- upsIdentAttachedDevicessixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentsixth 6 }
- upsIdentUPSSerialNumbersixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentsixth 7 }
- upsIdentComProtVersionsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentsixth 8 }
- upsIdentOperatingTimesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "sixths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentsixth 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatussixth OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatterysixth 1 }
- upsSecondsOnBatterysixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "sixths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatterysixth 2 }
- upsEstimatedMinutesRemainingsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatterysixth 3 }
- upsEstimatedChargeRemainingsixth OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatterysixth 4 }
- upsBatteryVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatterysixth 5 }
- upsBatteryCurrentsixth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatterysixth 6 }
- upsBatteryTemperaturesixth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatterysixth 7 }
- upsBatteryRipplesixth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatterysixth 8 }
- --
- -- Input Group
- --
- upsInputLineBadssixth OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputsixth 1 }
- upsInputNumLinessixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputsixth 2 }
- upsInputSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputsixth 3 }
- upsInputSixthEntry OBJECT-TYPE
- SYNTAX UpsInputSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexsixth }
- ::= { upsInputSixthTable 1 }
- UpsInputSixthEntry ::= SEQUENCE {
- upsInputLineIndexsixth PositiveInteger32,
- upsInputFrequencysixth NonNegativeInteger32,
- upsInputVoltagesixth NonNegativeInteger32,
- upsInputCurrentsixth NonNegativeInteger32,
- upsInputTruePowersixth NonNegativeInteger32,
- upsInputVoltageMinsixth NonNegativeInteger32,
- upsInputVoltageMaxsixth NonNegativeInteger32
- }
- upsInputLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputSixthEntry 1 }
- upsInputFrequencysixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputSixthEntry 2 }
- upsInputVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputSixthEntry 3 }
- upsInputCurrentsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputSixthEntry 4 }
- upsInputTruePowersixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputSixthEntry 5 }
- upsInputVoltageMinsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputSixthEntry 6 }
- upsInputVoltageMaxsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputSixthEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourcesixth OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputsixth 1 }
- upsOutputFrequencysixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputsixth 2 }
- upsOutputNumLinessixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputsixth 3 }
- upsOutputSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputsixth 4 }
- upsOutputSixthEntry OBJECT-TYPE
- SYNTAX UpsOutputSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexsixth }
- ::= { upsOutputSixthTable 1 }
- UpsOutputSixthEntry ::= SEQUENCE {
- upsOutputLineIndexsixth PositiveInteger32,
- upsOutputVoltagesixth NonNegativeInteger32,
- upsOutputCurrentsixth NonNegativeInteger32,
- upsOutputPowersixth NonNegativeInteger32,
- upsOutputPercentLoadsixth Integer32,
- upsOutputPowerFactorsixth Integer32,
- upsOutputPeakCurrentsixth Integer32,
- upsOutputShareCurrentsixth Integer32
- }
- upsOutputLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputSixthEntry 1 }
- upsOutputVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputSixthEntry 2 }
- upsOutputCurrentsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputSixthEntry 3 }
- upsOutputPowersixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputSixthEntry 4 }
- upsOutputPercentLoadsixth OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputSixthEntry 5 }
- upsOutputPowerFactorsixth OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputSixthEntry 6 }
- upsOutputPeakCurrentsixth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputSixthEntry 7 }
- upsOutputShareCurrentsixth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputSixthEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencysixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypasssixth 1 }
- upsBypassNumLinessixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypasssixth 2 }
- upsBypassSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypasssixth 3 }
- upsBypassSixthEntry OBJECT-TYPE
- SYNTAX UpsBypassSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexsixth }
- ::= { upsBypassSixthTable 1 }
- UpsBypassSixthEntry ::= SEQUENCE {
- upsBypassLineIndexsixth PositiveInteger32,
- upsBypassVoltagesixth NonNegativeInteger32,
- upsBypassCurrentsixth NonNegativeInteger32,
- upsBypassPowersixth NonNegativeInteger32
- }
- upsBypassLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassSixthEntry 1 }
- upsBypassVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassSixthEntry 2 }
- upsBypassCurrentsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassSixthEntry 3 }
- upsBypassPowersixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassSixthEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentsixth OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmsixth 1 }
- upsAlarmSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmsixth 2 }
- upsAlarmSixthEntry OBJECT-TYPE
- SYNTAX UpsAlarmSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdsixth }
- ::= { upsAlarmSixthTable 1 }
- UpsAlarmSixthEntry ::= SEQUENCE {
- upsAlarmIdsixth PositiveInteger32,
- upsAlarmDescrsixth AutonomousType,
- upsAlarmTimesixth TimeStamp
- }
- upsAlarmIdsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmSixthEntry 1 }
- upsAlarmDescrsixth OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmSixthEntry 2 }
- upsAlarmTimesixth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmSixthEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmssixth 1 }
- upsAlarmOnBatterysixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmssixth 2 }
- upsAlarmLowBatterysixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmssixth 3 }
- upsAlarmDepletedBatterysixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmssixth 4 }
- upsAlarmTempBadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssixth 5 }
- upsAlarmInputBadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssixth 6 }
- upsAlarmOutputBadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmssixth 7 }
- upsAlarmOutputOverloadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmssixth 8 }
- upsAlarmOnBypasssixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmssixth 9 }
- upsAlarmBypassBadsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmssixth 10 }
- upsAlarmOutputOffAsRequestedsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmssixth 11 }
- upsAlarmUpsOffAsRequestedsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmssixth 12 }
- upsAlarmChargerFailedsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmssixth 13 }
- upsAlarmUpsOutputOffsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmssixth 14 }
- upsAlarmUpsSystemOffsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmssixth 15 }
- upsAlarmFanFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmssixth 16 }
- upsAlarmFuseFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmssixth 17 }
- upsAlarmGeneralFaultsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmssixth 18 }
- upsAlarmDiagnosticTestFailedsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmssixth 19 }
- upsAlarmCommunicationsLostsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmssixth 20 }
- upsAlarmAwaitingPowersixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmssixth 21 }
- upsAlarmShutdownPendingsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmssixth 22 }
- upsAlarmShutdownImminentsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 sixths; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmssixth 23 }
- upsAlarmTestInProgresssixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmssixth 24 }
- upsAlarmReceptacleOffsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmssixth 25 }
- upsAlarmHighSpeedBusFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmssixth 26 }
- upsAlarmHighSpeedBusJACRCFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmssixth 27 }
- upsAlarmConnectivityBusFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmssixth 28 }
- upsAlarmHighSpeedBusJBCRCFailuresixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmssixth 29 }
- upsAlarmCurrentSharingsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmssixth 30 }
- upsAlarmDCRipplesixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmssixth 31 }
- upsAlarmMaskAsixth OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmsixth 4 }
- --
- -- The Test Group generic
- --
- upsTestIdsixth OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestsixth 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLocksixth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestsixth 2 }
- upsTestResultsSummarysixth OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestsixth 3 }
- upsTestResultsDetailsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestsixth 4 }
- upsTestStartTimesixth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestsixth 5 }
- upsTestElapsedTimesixth OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestsixth 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestssixth 1 }
- upsTestAbortTestInProgresssixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestssixth 2 }
- upsTestGeneralSystemsTestsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestssixth 3 }
- upsTestQuickBatteryTestsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestssixth 4 }
- upsTestDeepBatteryCalibrationsixth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestssixth 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypesixth OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlsixth 1 }
- upsShutdownAfterDelaysixth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "sixths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of sixths, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- sixths remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlsixth 2 }
- upsStartupAfterDelaysixth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "sixths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of sixths, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of sixths until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlsixth 3 }
- upsRebootWithDurationsixth OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "sixths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of sixths, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of sixths required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 sixths. When read, upsRebootWithDuration
- shall return the number of sixths remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlsixth 4 }
- upsAutoRestartsixth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlsixth 5 }
- upsReceptaclesNumsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlsixth 6 }
- upsReceptacleSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlsixth 7 }
- upsReceptacleSixthEntry OBJECT-TYPE
- SYNTAX UpsReceptacleSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexsixth }
- ::= { upsReceptacleSixthTable 1 }
- UpsReceptacleSixthEntry ::= SEQUENCE {
- upsReceptacleLineIndexsixth PositiveInteger32,
- upsReceptacleOnOffsixth INTEGER
- }
- upsReceptacleLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleSixthEntry 1 }
- upsReceptacleOnOffsixth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleSixthEntry 2 }
- upsUPSModesixth OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlsixth 8 }
- upsRectifierOnOffsixth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlsixth 9 }
- upsBatteryChargeMethodsixth OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlsixth 10 }
- upsInverterOnOffsixth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlsixth 11 }
- upsBypassOnOffsixth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlsixth 12 }
- upsLoadSourcesixth OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlsixth 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsixth 1 }
- upsConfigInputFreqsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsixth 2 }
- upsConfigOutputVoltagesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsixth 3 }
- upsConfigOutputFreqsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigsixth 4 }
- upsConfigOutputVAsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigsixth 5 }
- upsConfigOutputPowersixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigsixth 6 }
- upsConfigLowBattTimesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigsixth 7 }
- upsConfigAudibleStatussixth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigsixth 8 }
- upsConfigLowVoltageTransferPointsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigsixth 9 }
- upsConfigHighVoltageTransferPointsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigsixth 10 }
- upsConfigBatteryCapacitysixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigsixth 11 }
- upsConfigBatteryChargeCurrentsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigsixth 12 }
- upsConfigNoLoadShutdownsixth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigsixth 13 }
- upsConfigStartDelaysixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigsixth 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetsixth 1 }
- upsEventGetPrevioussixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetsixth 2 }
- upsEventSetStartingTimeStampsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetsixth 3 }
- upsEventRetreiveCurrentTimeStampsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetsixth 4 }
- upsEventTableSizesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetsixth 5 }
- upsEventSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetsixth 6 }
- upsEventSixthEntry OBJECT-TYPE
- SYNTAX UpsEventSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexsixth }
- ::= { upsEventSixthTable 1 }
- UpsEventSixthEntry ::= SEQUENCE {
- upsEventLineIndexsixth PositiveInteger32,
- upsEventCodesixth Integer32,
- upsEventStatussixth NonNegativeInteger32,
- upsEventTimesixth NonNegativeInteger32
- }
- upsEventLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventSixthEntry 1 }
- upsEventCodesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventSixthEntry 2 }
- upsEventStatussixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventSixthEntry 3 }
- upsEventTimesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventSixthEntry 4 }
- upsParametersReadsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetsixth 7 }
- upsParametersWritesixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the sixth value
- of the table with the lowest index number."
- ::= { upsGetSetsixth 8 }
- upsParametersStartAddresssixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetsixth 9 }
- upsParameterTableSizesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetsixth 10 }
- upsParameterSixthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetsixth 11 }
- upsParameterSixthEntry OBJECT-TYPE
- SYNTAX UpsParameterSixthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexsixth }
- ::= { upsParameterSixthTable 1 }
- UpsParameterSixthEntry ::= SEQUENCE {
- upsParameterLineIndexsixth PositiveInteger32,
- upsParameterValuesixth Integer32
- }
- upsParameterLineIndexsixth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterSixthEntry 1 }
- upsParameterValuesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterSixthEntry 2 }
- upsStatussixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetsixth 12 }
- upsMainsStatisticsMBfailsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetsixth 13 }
- upsMainsStatisticsMRfailsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetsixth 14 }
- upsMainsStatisticsB2sixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetsixth 15 }
- upsMainsStatisticsB5sixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetsixth 16 }
- upsMainsStatisticsB10sixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetsixth 17 }
- upsMainsStatisticsB200sixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetsixth 18 }
- upsMainsStatisticsBypRelsixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetsixth 19 }
- upsTimesixth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPsixthERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetsixth 20 }
- upsRequestPermissionsixth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetsixth 21 }
- upsEventGetCodesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetsixth 22 }
- upsEventSpinLocksixth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetsixth 23 }
- upsParameterSpinLocksixth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetsixth 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapssixth 1 }
- upsTrapAlarmOnBatterysixth NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatterysixth }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapssixth 2 }
- upsTrapAlarmLowBatterysixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapssixth 3 }
- upsTrapAlarmDepletedBatterysixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapssixth 4 }
- upsTrapAlarmTempBadsixth NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapssixth 5 }
- upsTrapAlarmInputBadsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapssixth 6 }
- upsTrapAlarmOutputBadsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapssixth 7 }
- upsTrapAlarmOutputOverloadsixth NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinessixth, upsOutputPercentLoadsixth }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapssixth 8 }
- upsTrapAlarmOnBypasssixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapssixth 9 }
- upsTrapAlarmBypassBadsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapssixth 10 }
- upsTrapAlarmOutputOffAsRequestedsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapssixth 11 }
- upsTrapAlarmUpsOffAsRequestedsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapssixth 12 }
- upsTrapAlarmChargerFailedsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapssixth 13 }
- upsTrapAlarmUpsOutputOffsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapssixth 14 }
- upsTrapAlarmUpsSystemOffsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapssixth 15 }
- upsTrapAlarmFanFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapssixth 16 }
- upsTrapAlarmFuseFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapssixth 17 }
- upsTrapAlarmGeneralFaultsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapssixth 18 }
- upsTrapAlarmDiagnosticTestFailedsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapssixth 19 }
- upsTrapAlarmCommunicationsLostsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapssixth 20 }
- upsTrapAlarmAwaitingPowersixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapssixth 21 }
- upsTrapAlarmShutdownPendingsixth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaysixth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapssixth 22 }
- upsTrapAlarmShutdownImminentsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 sixths; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapssixth 23 }
- upsTrapAlarmTestInProgresssixth NOTIFICATION-TYPE
- OBJECTS { upsTestIdsixth }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapssixth 24 }
- upsTrapAlarmReceptacleOffsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapssixth 25 }
- upsTrapAlarmHighspeedBusFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapssixth 26 }
- upsTrapAlarmHighspeedBusJACRCFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapssixth 27 }
- upsTrapAlarmConnectivityBusFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { geUPSTrapssixth 28 }
- upsTrapAlarmHighspeedBusJBCRCFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapssixth 29 }
- upsTrapAlarmCurrentSharingFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapssixth 30 }
- upsTrapAlarmDCRippleFailuresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapssixth 31 }
- upsTrapAlarmBatteryBadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapssixth 33 }
- upsTrapAlarmOnBatteryRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapssixth 34 }
- upsTrapAlarmLowBatteryRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapssixth 35 }
- upsTrapAlarmDepletedBatteryRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapssixth 36 }
- upsTrapAlarmTempBadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapssixth 37 }
- upsTrapAlarmInputBadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapssixth 38 }
- upsTrapAlarmOutputBadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapssixth 39 }
- upsTrapAlarmOutputOverloadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapssixth 40 }
- upsTrapAlarmOnBypassRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapssixth 41 }
- upsTrapAlarmBypassBadRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapssixth 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapssixth 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapssixth 44 }
- upsTrapAlarmChargerFailedRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapssixth 45 }
- upsTrapAlarmUpsOutputOnsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapssixth 46 }
- upsTrapAlarmUpsSystemOnsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapssixth 47 }
- upsTrapAlarmFanFailureRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapssixth 48 }
- upsTrapAlarmFuseFailureRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapssixth 49 }
- upsTrapAlarmGeneralFaultRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapssixth 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapssixth 51 }
- upsTrapAlarmCommunicationsLostRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapssixth 52 }
- upsTrapAlarmAwaitingPowerRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapssixth 53 }
- upsTrapAlarmShutdownPendingRestoredsixth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelaysixth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapssixth 54 }
- upsTrapAlarmShutdownImminentRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapssixth 55 }
- upsTrapAlarmTestInProgressRestoredsixth NOTIFICATION-TYPE
- OBJECTS { upsTestIdsixth }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapssixth 56 }
- upsTrapAlarmReceptacleOnsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapssixth 57 }
- upsTrapAlarmHighspeedBusRestoresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapssixth 58 }
- upsTrapAlarmHighspeedBusJACRCRestoresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapssixth 59 }
- upsTrapAlarmConnectivityBusRestoresixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapssixth 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapssixth 61 }
- upsTrapAlarmCurrentSharingRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapssixth 62 }
- upsTrapAlarmDCRippleRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapssixth 63 }
- upsTrapAlarmValueLowsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapssixth 129 }
- upsTrapAlarmValueHighsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapssixth 130 }
- upsTrapAlarmValueLowRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapssixth 133 }
- upsTrapAlarmValueHighRestoredsixth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapssixth 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatussixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticsixth 1 }
- upsDiagnosticBusJBCommunicationStatussixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticsixth 2 }
- upsDiagnosticBatteryLifetimesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsixth 3 }
- upsDiagnosticFansLifetimesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsixth 4 }
- upsDiagnosticDCcapacitorsLifetimesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsixth 5 }
- upsDiagnosticACcapacitorsLifetimesixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsixth 6 }
- upsDiagnosticGlobalServiceChecksixth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticsixth 7 }
- --
- -- The Device Identification group. Seventh
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturerseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdentseventh 1 }
- upsIdentModelseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdentseventh 2 }
- upsIdentUPSSoftwareVersionseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdentseventh 3 }
- upsIdentAgentSoftwareVersionseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdentseventh 4 }
- upsIdentNameseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdentseventh 5 }
- upsIdentAttachedDevicesseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdentseventh 6 }
- upsIdentUPSSerialNumberseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdentseventh 7 }
- upsIdentComProtVersionseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdentseventh 8 }
- upsIdentOperatingTimeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "sevenths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdentseventh 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatusseventh OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatteryseventh 1 }
- upsSecondsOnBatteryseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "sevenths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatteryseventh 2 }
- upsEstimatedMinutesRemainingseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatteryseventh 3 }
- upsEstimatedChargeRemainingseventh OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatteryseventh 4 }
- upsBatteryVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatteryseventh 5 }
- upsBatteryCurrentseventh OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatteryseventh 6 }
- upsBatteryTemperatureseventh OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatteryseventh 7 }
- upsBatteryRippleseventh OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatteryseventh 8 }
- --
- -- Input Group
- --
- upsInputLineBadsseventh OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputseventh 1 }
- upsInputNumLinesseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputseventh 2 }
- upsInputSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputseventh 3 }
- upsInputSeventhEntry OBJECT-TYPE
- SYNTAX UpsInputSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexseventh }
- ::= { upsInputSeventhTable 1 }
- UpsInputSeventhEntry ::= SEQUENCE {
- upsInputLineIndexseventh PositiveInteger32,
- upsInputFrequencyseventh NonNegativeInteger32,
- upsInputVoltageseventh NonNegativeInteger32,
- upsInputCurrentseventh NonNegativeInteger32,
- upsInputTruePowerseventh NonNegativeInteger32,
- upsInputVoltageMinseventh NonNegativeInteger32,
- upsInputVoltageMaxseventh NonNegativeInteger32
- }
- upsInputLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputSeventhEntry 1 }
- upsInputFrequencyseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputSeventhEntry 2 }
- upsInputVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputSeventhEntry 3 }
- upsInputCurrentseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputSeventhEntry 4 }
- upsInputTruePowerseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputSeventhEntry 5 }
- upsInputVoltageMinseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputSeventhEntry 6 }
- upsInputVoltageMaxseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputSeventhEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourceseventh OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputseventh 1 }
- upsOutputFrequencyseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputseventh 2 }
- upsOutputNumLinesseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputseventh 3 }
- upsOutputSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputseventh 4 }
- upsOutputSeventhEntry OBJECT-TYPE
- SYNTAX UpsOutputSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexseventh }
- ::= { upsOutputSeventhTable 1 }
- UpsOutputSeventhEntry ::= SEQUENCE {
- upsOutputLineIndexseventh PositiveInteger32,
- upsOutputVoltageseventh NonNegativeInteger32,
- upsOutputCurrentseventh NonNegativeInteger32,
- upsOutputPowerseventh NonNegativeInteger32,
- upsOutputPercentLoadseventh Integer32,
- upsOutputPowerFactorseventh Integer32,
- upsOutputPeakCurrentseventh Integer32,
- upsOutputShareCurrentseventh Integer32
- }
- upsOutputLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputSeventhEntry 1 }
- upsOutputVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputSeventhEntry 2 }
- upsOutputCurrentseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputSeventhEntry 3 }
- upsOutputPowerseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputSeventhEntry 4 }
- upsOutputPercentLoadseventh OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputSeventhEntry 5 }
- upsOutputPowerFactorseventh OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputSeventhEntry 6 }
- upsOutputPeakCurrentseventh OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputSeventhEntry 7 }
- upsOutputShareCurrentseventh OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputSeventhEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencyseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypassseventh 1 }
- upsBypassNumLinesseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypassseventh 2 }
- upsBypassSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypassseventh 3 }
- upsBypassSeventhEntry OBJECT-TYPE
- SYNTAX UpsBypassSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexseventh }
- ::= { upsBypassSeventhTable 1 }
- UpsBypassSeventhEntry ::= SEQUENCE {
- upsBypassLineIndexseventh PositiveInteger32,
- upsBypassVoltageseventh NonNegativeInteger32,
- upsBypassCurrentseventh NonNegativeInteger32,
- upsBypassPowerseventh NonNegativeInteger32
- }
- upsBypassLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassSeventhEntry 1 }
- upsBypassVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassSeventhEntry 2 }
- upsBypassCurrentseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassSeventhEntry 3 }
- upsBypassPowerseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassSeventhEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresentseventh OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmseventh 1 }
- upsAlarmSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmseventh 2 }
- upsAlarmSeventhEntry OBJECT-TYPE
- SYNTAX UpsAlarmSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdseventh }
- ::= { upsAlarmSeventhTable 1 }
- UpsAlarmSeventhEntry ::= SEQUENCE {
- upsAlarmIdseventh PositiveInteger32,
- upsAlarmDescrseventh AutonomousType,
- upsAlarmTimeseventh TimeStamp
- }
- upsAlarmIdseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmSeventhEntry 1 }
- upsAlarmDescrseventh OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmSeventhEntry 2 }
- upsAlarmTimeseventh OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmSeventhEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmsseventh 1 }
- upsAlarmOnBatteryseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmsseventh 2 }
- upsAlarmLowBatteryseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmsseventh 3 }
- upsAlarmDepletedBatteryseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmsseventh 4 }
- upsAlarmTempBadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsseventh 5 }
- upsAlarmInputBadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsseventh 6 }
- upsAlarmOutputBadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmsseventh 7 }
- upsAlarmOutputOverloadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmsseventh 8 }
- upsAlarmOnBypassseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmsseventh 9 }
- upsAlarmBypassBadseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmsseventh 10 }
- upsAlarmOutputOffAsRequestedseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmsseventh 11 }
- upsAlarmUpsOffAsRequestedseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmsseventh 12 }
- upsAlarmChargerFailedseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmsseventh 13 }
- upsAlarmUpsOutputOffseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmsseventh 14 }
- upsAlarmUpsSystemOffseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmsseventh 15 }
- upsAlarmFanFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmsseventh 16 }
- upsAlarmFuseFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmsseventh 17 }
- upsAlarmGeneralFaultseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmsseventh 18 }
- upsAlarmDiagnosticTestFailedseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmsseventh 19 }
- upsAlarmCommunicationsLostseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmsseventh 20 }
- upsAlarmAwaitingPowerseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmsseventh 21 }
- upsAlarmShutdownPendingseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmsseventh 22 }
- upsAlarmShutdownImminentseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 sevenths; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmsseventh 23 }
- upsAlarmTestInProgressseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmsseventh 24 }
- upsAlarmReceptacleOffseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmsseventh 25 }
- upsAlarmHighSpeedBusFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmsseventh 26 }
- upsAlarmHighSpeedBusJACRCFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmsseventh 27 }
- upsAlarmConnectivityBusFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { upsWellKnownAlarmsseventh 28 }
- upsAlarmHighSpeedBusJBCRCFailureseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmsseventh 29 }
- upsAlarmCurrentSharingseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmsseventh 30 }
- upsAlarmDCRippleseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmsseventh 31 }
- upsAlarmMaskAseventh OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmseventh 4 }
- --
- -- The Test Group generic
- --
- upsTestIdseventh OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTestseventh 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockseventh OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTestseventh 2 }
- upsTestResultsSummaryseventh OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTestseventh 3 }
- upsTestResultsDetailseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTestseventh 4 }
- upsTestStartTimeseventh OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTestseventh 5 }
- upsTestElapsedTimeseventh OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTestseventh 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestsseventh 1 }
- upsTestAbortTestInProgressseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestsseventh 2 }
- upsTestGeneralSystemsTestseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestsseventh 3 }
- upsTestQuickBatteryTestseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestsseventh 4 }
- upsTestDeepBatteryCalibrationseventh OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestsseventh 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypeseventh OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControlseventh 1 }
- upsShutdownAfterDelayseventh OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "sevenths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of sevenths, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- sevenths remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControlseventh 2 }
- upsStartupAfterDelayseventh OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "sevenths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of sevenths, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of sevenths until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControlseventh 3 }
- upsRebootWithDurationseventh OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "sevenths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of sevenths, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of sevenths required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 sevenths. When read, upsRebootWithDuration
- shall return the number of sevenths remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControlseventh 4 }
- upsAutoRestartseventh OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControlseventh 5 }
- upsReceptaclesNumseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControlseventh 6 }
- upsReceptacleSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControlseventh 7 }
- upsReceptacleSeventhEntry OBJECT-TYPE
- SYNTAX UpsReceptacleSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexseventh }
- ::= { upsReceptacleSeventhTable 1 }
- UpsReceptacleSeventhEntry ::= SEQUENCE {
- upsReceptacleLineIndexseventh PositiveInteger32,
- upsReceptacleOnOffseventh INTEGER
- }
- upsReceptacleLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleSeventhEntry 1 }
- upsReceptacleOnOffseventh OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleSeventhEntry 2 }
- upsUPSModeseventh OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControlseventh 8 }
- upsRectifierOnOffseventh OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControlseventh 9 }
- upsBatteryChargeMethodseventh OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControlseventh 10 }
- upsInverterOnOffseventh OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControlseventh 11 }
- upsBypassOnOffseventh OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControlseventh 12 }
- upsLoadSourceseventh OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControlseventh 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigseventh 1 }
- upsConfigInputFreqseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigseventh 2 }
- upsConfigOutputVoltageseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigseventh 3 }
- upsConfigOutputFreqseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigseventh 4 }
- upsConfigOutputVAseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigseventh 5 }
- upsConfigOutputPowerseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigseventh 6 }
- upsConfigLowBattTimeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigseventh 7 }
- upsConfigAudibleStatusseventh OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigseventh 8 }
- upsConfigLowVoltageTransferPointseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigseventh 9 }
- upsConfigHighVoltageTransferPointseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigseventh 10 }
- upsConfigBatteryCapacityseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigseventh 11 }
- upsConfigBatteryChargeCurrentseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigseventh 12 }
- upsConfigNoLoadShutdownseventh OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigseventh 13 }
- upsConfigStartDelayseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigseventh 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNextseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSetseventh 1 }
- upsEventGetPreviousseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSetseventh 2 }
- upsEventSetStartingTimeStampseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSetseventh 3 }
- upsEventRetreiveCurrentTimeStampseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSetseventh 4 }
- upsEventTableSizeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSetseventh 5 }
- upsEventSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSetseventh 6 }
- upsEventSeventhEntry OBJECT-TYPE
- SYNTAX UpsEventSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexseventh }
- ::= { upsEventSeventhTable 1 }
- UpsEventSeventhEntry ::= SEQUENCE {
- upsEventLineIndexseventh PositiveInteger32,
- upsEventCodeseventh Integer32,
- upsEventStatusseventh NonNegativeInteger32,
- upsEventTimeseventh NonNegativeInteger32
- }
- upsEventLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventSeventhEntry 1 }
- upsEventCodeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventSeventhEntry 2 }
- upsEventStatusseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventSeventhEntry 3 }
- upsEventTimeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventSeventhEntry 4 }
- upsParametersReadseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSetseventh 7 }
- upsParametersWriteseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the seventh value
- of the table with the lowest index number."
- ::= { upsGetSetseventh 8 }
- upsParametersStartAddressseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSetseventh 9 }
- upsParameterTableSizeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSetseventh 10 }
- upsParameterSeventhTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSetseventh 11 }
- upsParameterSeventhEntry OBJECT-TYPE
- SYNTAX UpsParameterSeventhEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexseventh }
- ::= { upsParameterSeventhTable 1 }
- UpsParameterSeventhEntry ::= SEQUENCE {
- upsParameterLineIndexseventh PositiveInteger32,
- upsParameterValueseventh Integer32
- }
- upsParameterLineIndexseventh OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterSeventhEntry 1 }
- upsParameterValueseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterSeventhEntry 2 }
- upsStatusseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSetseventh 12 }
- upsMainsStatisticsMBfailseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSetseventh 13 }
- upsMainsStatisticsMRfailseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSetseventh 14 }
- upsMainsStatisticsB2seventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSetseventh 15 }
- upsMainsStatisticsB5seventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSetseventh 16 }
- upsMainsStatisticsB10seventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSetseventh 17 }
- upsMainsStatisticsB200seventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSetseventh 18 }
- upsMainsStatisticsBypRelseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSetseventh 19 }
- upsTimeseventh OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPseventhERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSetseventh 20 }
- upsRequestPermissionseventh OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSetseventh 21 }
- upsEventGetCodeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSetseventh 22 }
- upsEventSpinLockseventh OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSetseventh 23 }
- upsParameterSpinLockseventh OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSetseventh 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapsseventh 1 }
- upsTrapAlarmOnBatteryseventh NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatteryseventh }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapsseventh 2 }
- upsTrapAlarmLowBatteryseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapsseventh 3 }
- upsTrapAlarmDepletedBatteryseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapsseventh 4 }
- upsTrapAlarmTempBadseventh NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapsseventh 5 }
- upsTrapAlarmInputBadseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapsseventh 6 }
- upsTrapAlarmOutputBadseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapsseventh 7 }
- upsTrapAlarmOutputOverloadseventh NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLinesseventh, upsOutputPercentLoadseventh }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapsseventh 8 }
- upsTrapAlarmOnBypassseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapsseventh 9 }
- upsTrapAlarmBypassBadseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapsseventh 10 }
- upsTrapAlarmOutputOffAsRequestedseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapsseventh 11 }
- upsTrapAlarmUpsOffAsRequestedseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapsseventh 12 }
- upsTrapAlarmChargerFailedseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapsseventh 13 }
- upsTrapAlarmUpsOutputOffseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapsseventh 14 }
- upsTrapAlarmUpsSystemOffseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapsseventh 15 }
- upsTrapAlarmFanFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapsseventh 16 }
- upsTrapAlarmFuseFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapsseventh 17 }
- upsTrapAlarmGeneralFaultseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapsseventh 18 }
- upsTrapAlarmDiagnosticTestFailedseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapsseventh 19 }
- upsTrapAlarmCommunicationsLostseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapsseventh 20 }
- upsTrapAlarmAwaitingPowerseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapsseventh 21 }
- upsTrapAlarmShutdownPendingseventh NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayseventh }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapsseventh 22 }
- upsTrapAlarmShutdownImminentseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 sevenths; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapsseventh 23 }
- upsTrapAlarmTestInProgressseventh NOTIFICATION-TYPE
- OBJECTS { upsTestIdseventh }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapsseventh 24 }
- upsTrapAlarmReceptacleOffseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapsseventh 25 }
- upsTrapAlarmHighspeedBusFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapsseventh 26 }
- upsTrapAlarmHighspeedBusJACRCFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapsseventh 27 }
- upsTrapAlarmConnectivityBusFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { geUPSTrapsseventh 28 }
- upsTrapAlarmHighspeedBusJBCRCFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapsseventh 29 }
- upsTrapAlarmCurrentSharingFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapsseventh 30 }
- upsTrapAlarmDCRippleFailureseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapsseventh 31 }
- upsTrapAlarmBatteryBadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapsseventh 33 }
- upsTrapAlarmOnBatteryRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapsseventh 34 }
- upsTrapAlarmLowBatteryRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapsseventh 35 }
- upsTrapAlarmDepletedBatteryRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapsseventh 36 }
- upsTrapAlarmTempBadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapsseventh 37 }
- upsTrapAlarmInputBadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapsseventh 38 }
- upsTrapAlarmOutputBadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapsseventh 39 }
- upsTrapAlarmOutputOverloadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapsseventh 40 }
- upsTrapAlarmOnBypassRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapsseventh 41 }
- upsTrapAlarmBypassBadRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapsseventh 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapsseventh 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapsseventh 44 }
- upsTrapAlarmChargerFailedRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapsseventh 45 }
- upsTrapAlarmUpsOutputOnseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapsseventh 46 }
- upsTrapAlarmUpsSystemOnseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapsseventh 47 }
- upsTrapAlarmFanFailureRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapsseventh 48 }
- upsTrapAlarmFuseFailureRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapsseventh 49 }
- upsTrapAlarmGeneralFaultRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapsseventh 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapsseventh 51 }
- upsTrapAlarmCommunicationsLostRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapsseventh 52 }
- upsTrapAlarmAwaitingPowerRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapsseventh 53 }
- upsTrapAlarmShutdownPendingRestoredseventh NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayseventh }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapsseventh 54 }
- upsTrapAlarmShutdownImminentRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapsseventh 55 }
- upsTrapAlarmTestInProgressRestoredseventh NOTIFICATION-TYPE
- OBJECTS { upsTestIdseventh }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapsseventh 56 }
- upsTrapAlarmReceptacleOnseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapsseventh 57 }
- upsTrapAlarmHighspeedBusRestoreseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapsseventh 58 }
- upsTrapAlarmHighspeedBusJACRCRestoreseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapsseventh 59 }
- upsTrapAlarmConnectivityBusRestoreseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapsseventh 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapsseventh 61 }
- upsTrapAlarmCurrentSharingRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapsseventh 62 }
- upsTrapAlarmDCRippleRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapsseventh 63 }
- upsTrapAlarmValueLowseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapsseventh 129 }
- upsTrapAlarmValueHighseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapsseventh 130 }
- upsTrapAlarmValueLowRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapsseventh 133 }
- upsTrapAlarmValueHighRestoredseventh NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapsseventh 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatusseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticseventh 1 }
- upsDiagnosticBusJBCommunicationStatusseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticseventh 2 }
- upsDiagnosticBatteryLifetimeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticseventh 3 }
- upsDiagnosticFansLifetimeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticseventh 4 }
- upsDiagnosticDCcapacitorsLifetimeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticseventh 5 }
- upsDiagnosticACcapacitorsLifetimeseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticseventh 6 }
- upsDiagnosticGlobalServiceCheckseventh OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticseventh 7 }
- --
- -- The Device Identification group. Eighth
- -- All objects in this group except for upsIdentName and
- -- upsIdentAttachedDevices are set at device initialization
- -- and remain static.
- --
- upsIdentManufacturereighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The name of the UPS manufacturer.(*)"
- ::= { upsIdenteighth 1 }
- upsIdentModeleighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS Model designation.(*)"
- ::= { upsIdenteighth 2 }
- upsIdentUPSSoftwareVersioneighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS firmware/software version(s). This variable
- may or may not have the same value as
- upsIdentAgentSoftwareVersion in some implementations.(*)"
- ::= { upsIdenteighth 3 }
- upsIdentAgentSoftwareVersioneighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS agent software version. This variable may or
- may not have the same value as
- upsIdentUPSSoftwareVersion in some implementations.(*)"
- ::= { upsIdenteighth 4 }
- upsIdentNameeighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the UPS. This object should be
- set by the administrator.(*)"
- ::= { upsIdenteighth 5 }
- upsIdentAttachedDeviceseighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A string identifying the devices attached to the
- output(s) of the UPS. This object should be set by
- the administrator.(*)"
- ::= { upsIdenteighth 6 }
- upsIdentUPSSerialNumbereighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The UPS serial number"
- ::= { upsIdenteighth 7 }
- upsIdentComProtVersioneighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The IMV communication protocol version"
- ::= { upsIdenteighth 8 }
- upsIdentOperatingTimeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "eighths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present value of the operating time.
- total 'on' time since UPS manufactured"
- ::= { upsIdenteighth 9 }
- --
- -- Battery Group Generic
- --
- upsBatteryStatuseighth OBJECT-TYPE
- SYNTAX INTEGER {
- unknown(1),
- batteryNormal(2),
- batteryLow(3),
- batteryDepleted(4)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The indication of the capacity remaining in the UPS
- system's batteries. A value of batteryNormal
- indicates that the remaining run-time is greater than
- upsConfigLowBattTime. A value of batteryLow indicates
- that the remaining battery run-time is less than or
- equal to upsConfigLowBattTime. A value of
- batteryDepleted indicates that the UPS will be unable
- to sustain the present load when and if the utility
- power is lost (including the possibility that the
- utility power is currently absent and the UPS is
- unable to sustain the output).(*)"
- ::= { upsBatteryeighth 1 }
- upsSecondsOnBatteryeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "eighths"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "If the unit is on battery power, the elapsed time
- since the UPS last switched to battery power, or the
- time since the network management subsystem was last
- restarted, whichever is less. Zero shall be returned
- if the unit is not on battery power.(*)"
- ::= { upsBatteryeighth 2 }
- upsEstimatedMinutesRemainingeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the time to battery charge depletion
- under the present load conditions if the utility power
- is off and remains off, or if it were to be lost and
- remain off.(*)"
- ::= { upsBatteryeighth 3 }
- upsEstimatedChargeRemainingeighth OBJECT-TYPE
- SYNTAX Integer32 (0..100)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "An estimate of the battery charge remaining expressed
- as a percent of full charge.(*)"
- ::= { upsBatteryeighth 4 }
- upsBatteryVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Volt DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present battery voltage.(*)"
- ::= { upsBatteryeighth 5 }
- upsBatteryCurrenteighth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present battery current.(*)"
- ::= { upsBatteryeighth 6 }
- upsBatteryTemperatureeighth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "degrees Centigrade"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The ambient temperature at or near the UPS Battery
- casing.(*)"
- ::= { upsBatteryeighth 7 }
- upsBatteryRippleeighth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 Volt RMS"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present DC link RMS voltage ripple.(*)"
- ::= { upsBatteryeighth 8 }
- --
- -- Input Group
- --
- upsInputLineBadseighth OBJECT-TYPE
- SYNTAX Counter32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A count of the number of times the input entered an
- out-of-tolerance condition as defined by the
- manufacturer. This count is incremented by one each
- time the input transitions from zero out-of-tolerance
- lines to one or more input lines out-of-tolerance.(*)"
- ::= { upsInputeighth 1 }
- upsInputNumLineseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of input lines utilized in this device.
- This variable indicates the number of rows in the
- input table.(*)"
- ::= { upsInputeighth 2 }
- upsInputEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsInputEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of input table entries. The number of entries
- is given by the value of upsInputNumLines.(*)"
- ::= { upsInputeighth 3 }
- upsInputEighthEntry OBJECT-TYPE
- SYNTAX UpsInputEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular input line.(*)"
- INDEX { upsInputLineIndexeighth }
- ::= { upsInputEighthTable 1 }
- UpsInputEighthEntry ::= SEQUENCE {
- upsInputLineIndexeighth PositiveInteger32,
- upsInputFrequencyeighth NonNegativeInteger32,
- upsInputVoltageeighth NonNegativeInteger32,
- upsInputCurrenteighth NonNegativeInteger32,
- upsInputTruePowereighth NonNegativeInteger32,
- upsInputVoltageMineighth NonNegativeInteger32,
- upsInputVoltageMaxeighth NonNegativeInteger32
- }
- upsInputLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The input line identifier.(*)"
- ::= { upsInputEighthEntry 1 }
- upsInputFrequencyeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present input frequency.(*)"
- ::= { upsInputEighthEntry 2 }
- upsInputVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input voltage.(*)"
- ::= { upsInputEighthEntry 3 }
- upsInputCurrenteighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input current.(*)"
- ::= { upsInputEighthEntry 4 }
- upsInputTruePowereighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the present input true power.(*)"
- ::= { upsInputEighthEntry 5 }
- upsInputVoltageMineighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The lowest magnitude of the input voltage since last read out."
- ::= { upsInputEighthEntry 6 }
- upsInputVoltageMaxeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The highest magnitude of the input voltage since last read out."
- ::= { upsInputEighthEntry 7 }
- --
- -- The Output group.
- --
- upsOutputSourceeighth OBJECT-TYPE
- SYNTAX INTEGER {
- other(1),
- none(2),
- normal(3),
- bypass(4),
- battery(5),
- booster(6),
- reducer(7)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present source of output power. The enumeration
- none(2) indicates that there is no source of output
- power (and therefore no output power), for example,
- the system has opened the output breaker.(*)"
- ::= { upsOutputeighth 1 }
- upsOutputFrequencyeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output frequency.(*)"
- ::= { upsOutputeighth 2 }
- upsOutputNumLineseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of output lines utilized in this device.
- This variable indicates the number of rows in the
- output table.(*)"
- ::= { upsOutputeighth 3 }
- upsOutputEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsOutputEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of output table entries. The number of
- entries is given by the value of upsOutputNumLines.(*)"
- ::= { upsOutputeighth 4 }
- upsOutputEighthEntry OBJECT-TYPE
- SYNTAX UpsOutputEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular output line.(*)"
- INDEX { upsOutputLineIndexeighth }
- ::= { upsOutputEighthTable 1 }
- UpsOutputEighthEntry ::= SEQUENCE {
- upsOutputLineIndexeighth PositiveInteger32,
- upsOutputVoltageeighth NonNegativeInteger32,
- upsOutputCurrenteighth NonNegativeInteger32,
- upsOutputPowereighth NonNegativeInteger32,
- upsOutputPercentLoadeighth Integer32,
- upsOutputPowerFactoreighth Integer32,
- upsOutputPeakCurrenteighth Integer32,
- upsOutputShareCurrenteighth Integer32
- }
- upsOutputLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The output line identifier.(*)"
- ::= { upsOutputEighthEntry 1 }
- upsOutputVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output voltage.(*)"
- ::= { upsOutputEighthEntry 2 }
- upsOutputCurrenteighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output current.(*)"
- ::= { upsOutputEighthEntry 3 }
- upsOutputPowereighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output true power.(*)"
- ::= { upsOutputEighthEntry 4 }
- upsOutputPercentLoadeighth OBJECT-TYPE
- SYNTAX Integer32 (0..200)
- UNITS "percent"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The percentage of the UPS power capacity presently
- being used on this output line, i.e., the greater of
- the percent load of true power capacity and the
- percent load of VA.(*)"
- ::= { upsOutputEighthEntry 5 }
- upsOutputPowerFactoreighth OBJECT-TYPE
- SYNTAX Integer32 (-99..100)
- UNITS "0.01 cos phi"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output power factor.
- The returned value correspond to the cosf of the load.
- A positive value indicate an inductive load;
- a negative value indicate a capacitive load;
- value 1 indicate a resistive load.
- If the measure is not available due to a small load for
- a consistent calculation, the NA value is then returned.(*)"
- ::= { upsOutputEighthEntry 6 }
- upsOutputPeakCurrenteighth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present output peak current.(*)"
- ::= { upsOutputEighthEntry 7 }
- upsOutputShareCurrenteighth OBJECT-TYPE
- SYNTAX Integer32
- UNITS "Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "In a parallel system ideally all the UPS are requested to
- contribute to the load with the same amount of current,
- i.e. with no current share. The current share occurs when an
- UPS exchanges some current with another UPS, so that this
- current component doesn't feed the load.
- The share part of the UPS current represents an undesired UPS
- loading, and therefore it should be minimized. If the share
- current is too high, the UPS results overloaded and in some
- conditions (i.e. very high load) the system could turn on
- bypass reducing dramatically the global system reliability.
- PMAD detects the amount of share currents in a parallel system,
- generating an alarm if this value is above a parameter-based threshold.
- Single UPS systems don't have this feature, NA will be provided.(*)"
- ::= { upsOutputEighthEntry 8 }
- --
- -- The Bypass group generic.
- --
- upsBypassFrequencyeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass frequency.(*)"
- ::= { upsBypasseighth 1 }
- upsBypassNumLineseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of bypass lines utilized in this device.
- This entry indicates the number of rows in the bypass
- table.(*)"
- ::= { upsBypasseighth 2 }
- upsBypassEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsBypassEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of bypass table entries. The number of
- entries is given by the value of upsBypassNumLines.(*)"
- ::= { upsBypasseighth 3 }
- upsBypassEighthEntry OBJECT-TYPE
- SYNTAX UpsBypassEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular bypass input.(*)"
- INDEX { upsBypassLineIndexeighth }
- ::= { upsBypassEighthTable 1 }
- UpsBypassEighthEntry ::= SEQUENCE {
- upsBypassLineIndexeighth PositiveInteger32,
- upsBypassVoltageeighth NonNegativeInteger32,
- upsBypassCurrenteighth NonNegativeInteger32,
- upsBypassPowereighth NonNegativeInteger32
- }
- upsBypassLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The bypass line identifier.(*)"
- ::= { upsBypassEighthEntry 1 }
- upsBypassVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass voltage.(*)"
- ::= { upsBypassEighthEntry 2 }
- upsBypassCurrenteighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 RMS Amp"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present bypass current.(*)"
- ::= { upsBypassEighthEntry 3 }
- upsBypassPowereighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present true power conveyed by the bypass.(*)"
- ::= { upsBypassEighthEntry 4 }
- --
- -- The Alarm group generic.
- --
- upsAlarmsPresenteighth OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The present number of active alarm conditions.(*)"
- ::= { upsAlarmeighth 1 }
- upsAlarmEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsAlarmEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of alarm table entries. The table contains
- zero, one, or many rows at any moment, depending upon
- the number of alarm conditions in effect. The table
- is initially empty at agent startup. The agent
- creates a row in the table each time a condition is
- detected and deletes that row when that condition no
- longer pertains. The agent creates the first row with
- upsAlarmId equal to 1, and increments the value of
- upsAlarmId each time a new row is created, wrapping to
- the first free value greater than or equal to 1 when
- the maximum value of upsAlarmId would otherwise be
- exceeded. Consequently, after multiple operations,
- the table may become sparse, e.g., containing entries
- for rows 95, 100, 101, and 203 and the entries should
- not be assumed to be in chronological order because
- upsAlarmId might have wrapped.
- Alarms are named by an AutonomousType (OBJECT
- IDENTIFIER), upsAlarmDescr, to allow a single table to
- reflect well known alarms plus alarms defined by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device. No
- two rows will have the same value of upsAlarmDescr,
- since alarms define conditions. In order to meet this
- requirement, care should be taken in the definition of
- alarm conditions to insure that a system cannot enter
- the same condition multiple times simultaneously.
- The number of rows in the table at any given time is
- reflected by the value of upsAlarmsPresent.(*)"
- ::= { upsAlarmeighth 2 }
- upsAlarmEighthEntry OBJECT-TYPE
- SYNTAX UpsAlarmEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular alarm.(*)"
- INDEX { upsAlarmIdeighth }
- ::= { upsAlarmEighthTable 1 }
- UpsAlarmEighthEntry ::= SEQUENCE {
- upsAlarmIdeighth PositiveInteger32,
- upsAlarmDescreighth AutonomousType,
- upsAlarmTimeeighth TimeStamp
- }
- upsAlarmIdeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A unique identifier for an alarm condition. This
- value must remain constant.(*)"
- ::= { upsAlarmEighthEntry 1 }
- upsAlarmDescreighth OBJECT-TYPE
- SYNTAX AutonomousType
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A reference to an alarm description object. The
- object referenced should not be accessible, but rather
- be used to provide a unique description of the alarm
- condition.(*)"
- ::= { upsAlarmEighthEntry 2 }
- upsAlarmTimeeighth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime when the alarm condition was
- detected. If the alarm condition was detected at the
- time of agent startup and presumably existed before
- agent startup, the value of upsAlarmTime shall equal
- 0.(*)"
- ::= { upsAlarmEighthEntry 3 }
- --
- -- Well known alarm conditions generic.
- --
- upsAlarmBatteryBadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement.(*)"
- ::= { upsWellKnownAlarmseighth 1 }
- upsAlarmOnBatteryeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries.(*)"
- ::= { upsWellKnownAlarmseighth 2 }
- upsAlarmLowBatteryeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime.(*)"
- ::= { upsWellKnownAlarmseighth 3 }
- upsAlarmDepletedBatteryeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost.(*)"
- ::= { upsWellKnownAlarmseighth 4 }
- upsAlarmTempBadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance.(*)"
- ::= { upsWellKnownAlarmseighth 5 }
- upsAlarmInputBadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance.(*)"
- ::= { upsWellKnownAlarmseighth 6 }
- upsAlarmOutputBadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance.(*)"
- ::= { upsWellKnownAlarmseighth 7 }
- upsAlarmOutputOverloadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity.(*)"
- ::= { upsWellKnownAlarmseighth 8 }
- upsAlarmOnBypasseighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS.(*)"
- ::= { upsWellKnownAlarmseighth 9 }
- upsAlarmBypassBadeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance.(*)"
- ::= { upsWellKnownAlarmseighth 10 }
- upsAlarmOutputOffAsRequestedeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off.(*)"
- ::= { upsWellKnownAlarmseighth 11 }
- upsAlarmUpsOffAsRequestedeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded.(*)"
- ::= { upsWellKnownAlarmseighth 12 }
- upsAlarmChargerFailedeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem.(*)"
- ::= { upsWellKnownAlarmseighth 13 }
- upsAlarmUpsOutputOffeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state.(*)"
- ::= { upsWellKnownAlarmseighth 14 }
- upsAlarmUpsSystemOffeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state.(*)"
- ::= { upsWellKnownAlarmseighth 15 }
- upsAlarmFanFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected.(*)"
- ::= { upsWellKnownAlarmseighth 16 }
- upsAlarmFuseFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected.(*)"
- ::= { upsWellKnownAlarmseighth 17 }
- upsAlarmGeneralFaulteighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected.(*)"
- ::= { upsWellKnownAlarmseighth 18 }
- upsAlarmDiagnosticTestFailedeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure.(*)"
- ::= { upsWellKnownAlarmseighth 19 }
- upsAlarmCommunicationsLosteighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communications
- between the agent and the UPS.(*)"
- ::= { upsWellKnownAlarmseighth 20 }
- upsAlarmAwaitingPowereighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of input power.(*)"
- ::= { upsWellKnownAlarmseighth 21 }
- upsAlarmShutdownPendingeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway.(*)"
- ::= { upsWellKnownAlarmseighth 22 }
- upsAlarmShutdownImminenteighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 eighths; this may be either a timed shutdown or a
- low battery shutdown.(*)"
- ::= { upsWellKnownAlarmseighth 23 }
- upsAlarmTestInProgresseighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY.(*)"
- ::= { upsWellKnownAlarmseighth 24 }
- upsAlarmReceptacleOffeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The receptacle are switch off "
- ::= { upsWellKnownAlarmseighth 25 }
- upsAlarmHighSpeedBusFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the High Speed Bus communication is detected"
- ::= { upsWellKnownAlarmseighth 26 }
- upsAlarmHighSpeedBusJACRCFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JA is detected."
- ::= { upsWellKnownAlarmseighth 27 }
- upsAlarmConnectivityBusFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected"
- ::= { upsWellKnownAlarmseighth 28 }
- upsAlarmHighSpeedBusJBCRCFailureeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A High Speed Bus CRC failure on Bus JB is detected."
- ::= { upsWellKnownAlarmseighth 29 }
- upsAlarmCurrentSharingeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high current sharing on the parallel system."
- ::= { upsWellKnownAlarmseighth 30 }
- upsAlarmDCRippleeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The UPS detects an high ripple voltage on his DC link."
- ::= { upsWellKnownAlarmseighth 31 }
- upsAlarmMaskAeighth OBJECT-TYPE
- SYNTAX Unsigned32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Specifies which alarm can be handled by the UPS.
- The 'Mask' parameter is a Long Integer32. The meaning
- of every bit is the same as for the 'upsAlarmGroupA'
- command. A bit having value=1 indicates that the
- corresponding alarm is handled by the UPS."
- ::= { upsAlarmeighth 4 }
- --
- -- The Test Group generic
- --
- upsTestIdeighth OBJECT-TYPE
- SYNTAX OBJECT IDENTIFIER
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The test is named by an OBJECT IDENTIFIER which
- allows a standard mechanism for the initiation of
- tests, including the well known tests identified in
- this document as well as those introduced by a
- particular implementation, i.e., as documented in the
- private enterprise MIB definition for the device.
- Setting this variable initiates the named test. Sets
- to this variable require the presence of
- upsTestSpinLock in the same SNMP message.
- The set request will be rejected with an appropriate
- error message if the requested test cannot be
- performed, including attempts to start a test when
- another test is already in progress. The status of
- the current or last test is maintained in
- upsTestResultsSummary. Tests in progress may be
- aborted by setting the upsTestId variable to
- upsTestAbortTestInProgress.
- Read operations return the value of the name of the
- test in progress if a test is in progress or the name
- of the last test performed if no test is in progress,
- unless no test has been run, in which case the well
- known value upsTestNoTestsInitiated is returned.(*)"
- ::= { upsTesteighth 1 }
- -- see [6] for more information on the semantics of objects with
- -- syntax of TestAndIncr
- upsTestSpinLockeighth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the test subsystem. The spinlock is
- used as follows.
- Before starting a test, a manager-station should make
- sure that a test is not in progress as follows:
- tryagain:
- get (upsTestSpinLock)
- while (upsTestResultsSummary == inProgress) {
- /* loop while a test is running for another
- manager */
- short delay
- get (upsTestSpinLock)
- }
- lockvalue = upsTestSpinLock
- /* no test in progress, start the test */
- set (upsTestSpinLock = lockvalue, upsTestId =
- requestedtest)
- if (errorindex == 1) { /* (upsTestSpinLock
- failed) */
- /* if problem is not access control, then
- some other manager slipped in ahead of us
- */
- goto tryagain
- }
- if (errorindex == 2) { /* (upsTestId) */
- /* cannot perform the test */
- give up
- }
- /* test started ok */
- /* wait for test completion by polling
- upsTestResultsSummary */
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- while (upsTestResultsSummary == inProgress) {
- short delay
- get (upsTestSpinLock, upsTestResultsSummary,
- upsTestResultsDetail)
- }
- /* when test completes, retrieve any additional
- test results */
- /* if upsTestSpinLock == lockvalue + 1, then
- these are our test */
- /* results (as opposed to another manager's */
- The initial value of upsTestSpinLock at agent
- initialization shall
- be 1.(*)"
- ::= { upsTesteighth 2 }
- upsTestResultsSummaryeighth OBJECT-TYPE
- SYNTAX INTEGER {
- donePass(1),
- doneWarning(2),
- doneError(3),
- aborted(4),
- inProgress(5),
- noTestsInitiated(6)
- }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The results of the current or last UPS diagnostics
- test performed. The values for donePass(1),
- doneWarning(2), and doneError(3) indicate that the
- test completed either successfully, with a warning, or
- with an error, respectively. The value aborted(4) is
- returned for tests which are aborted by setting the
- value of upsTestId to upsTestAbortTestInProgress.
- Tests which have not yet concluded are indicated by
- inProgress(5). The value noTestsInitiated(6)
- indicates that no previous test results are available,
- such as is the case when no tests have been run since
- the last reinitialization of the network management
- subsystem and the system has no provision for non-
- volatile storage of test results.(*)"
- ::= { upsTesteighth 3 }
- upsTestResultsDetaileighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Additional information about upsTestResultsSummary.
- If no additional information available, a zero length
- string is returned.(*)"
- ::= { upsTesteighth 4 }
- upsTestStartTimeeighth OBJECT-TYPE
- SYNTAX TimeStamp
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The value of sysUpTime at the time the test in
- progress was initiated, or, if no test is in progress,
- the time the previous test was initiated. If the
- value of upsTestResultsSummary is noTestsInitiated(6),
- upsTestStartTime has the value 0.(*)"
- ::= { upsTesteighth 5 }
- upsTestElapsedTimeeighth OBJECT-TYPE
- SYNTAX TimeInterval
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The amount of time, in TimeTicks, since the test in
- progress was initiated, or, if no test is in progress,
- the previous test took to complete. If the value of
- upsTestResultsSummary is noTestsInitiated(6),
- upsTestElapsedTime has the value 0.(*)"
- ::= { upsTesteighth 6 }
- --
- -- Well known tests generic.
- --
- upsTestNoTestsInitiatedeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "No tests have been initiated and no test is in
- progress.(*)"
- ::= { upsWellKnownTestseighth 1 }
- upsTestAbortTestInProgresseighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The test in progress is to be aborted / the test in
- progress was aborted.(*)"
- ::= { upsWellKnownTestseighth 2 }
- upsTestGeneralSystemsTesteighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The manufacturer's standard test of UPS device
- systems.(*)"
- ::= { upsWellKnownTestseighth 3 }
- upsTestQuickBatteryTesteighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "A test that is sufficient to determine if the battery
- needs replacement.(*)"
- ::= { upsWellKnownTestseighth 4 }
- upsTestDeepBatteryCalibrationeighth OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "The system is placed on battery to a discharge level,
- set by the manufacturer, sufficient to determine
- battery replacement and battery run-time with a high
- degree of confidence. WARNING: this test will leave
- the battery in a low charge state and will require
- time for recharging to a level sufficient to provide
- normal battery duration for the protected load.(*)"
- ::= { upsWellKnownTestseighth 5 }
- --
- -- The Control group generic.
- --
- upsShutdownTypeeighth OBJECT-TYPE
- SYNTAX INTEGER {
- output(1),
- system(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "This object determines the nature of the action to be
- taken at the time when the countdown of the
- upsShutdownAfterDelay and upsRebootWithDuration
- objects reaches zero.
- Setting this object to output(1) indicates that
- shutdown requests should cause only the output of the
- UPS to turn off. Setting this object to system(2)
- indicates that shutdown requests will cause the entire
- UPS system to turn off.(*)"
- ::= { upsControleighth 1 }
- upsShutdownAfterDelayeighth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "eighths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will shutdown (i.e., turn off)
- either the UPS output or the UPS system (as determined
- by the value of upsShutdownType at the time of
- shutdown) after the indicated number of eighths, or
- less if the UPS batteries become depleted. Setting
- this object to 0 will cause the shutdown to occur
- immediately. Setting this object to -1 will abort the
- countdown. If the system is already in the desired
- state at the time the countdown reaches 0, then
- nothing will happen. That is, there is no additional
- action at that time if upsShutdownType = system and
- the system is already off. Similarly, there is no
- additional action at that time if upsShutdownType =
- output and the output is already off. When read,
- upsShutdownAfterDelay will return the number of
- eighths remaining until shutdown, or -1 if no shutdown
- countdown is in effect. On some systems, if the agent
- is restarted while a shutdown countdown is in effect,
- the countdown may be aborted. Sets to this object
- override any upsShutdownAfterDelay already in effect.(*)"
- ::= { upsControleighth 2 }
- upsStartupAfterDelayeighth OBJECT-TYPE
- SYNTAX Integer32 (-1..2147483647)
- UNITS "eighths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will start the output after the
- indicated number of eighths, including starting the
- UPS, if necessary. Setting this object to 0 will
- cause the startup to occur immediately. Setting this
- object to -1 will abort the countdown. If the output
- is already on at the time the countdown reaches 0,
- then nothing will happen. Sets to this object
- override the effect of any upsStartupAfterDelay
- countdown or upsRebootWithDuration countdown in
- progress. When read, upsStartupAfterDelay will return
- the number of eighths until startup, or -1 if no
- startup countdown is in effect. If the countdown
- expires during a utility failure, the startup shall
- not occur until the utility power is restored. On
- some systems, if the agent is restarted while a
- startup countdown is in effect, the countdown is
- aborted.(*)"
- ::= { upsControleighth 3 }
- upsRebootWithDurationeighth OBJECT-TYPE
- SYNTAX Integer32 (-1..300)
- UNITS "eighths"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object will immediately shutdown (i.e.,
- turn off) either the UPS output or the UPS system (as
- determined by the value of upsShutdownType at the time
- of shutdown) for a period equal to the indicated
- number of eighths, after which time the output will be
- started, including starting the UPS, if necessary. If
- the number of eighths required to perform the request
- is greater than the requested duration, then the
- requested shutdown and startup cycle shall be
- performed in the minimum time possible, but in no case
- shall this require more than the requested duration
- plus 60 eighths. When read, upsRebootWithDuration
- shall return the number of eighths remaining in the
- countdown, or -1 if no countdown is in progress. If
- the startup should occur during a utility failure, the
- startup shall not occur until the utility power is
- restored.(*)"
- ::= { upsControleighth 4 }
- upsAutoRestarteighth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Setting this object to 'on' will cause the UPS system
- to restart after a shutdown if the shutdown occurred
- during a power loss as a result of either a
- upsShutdownAfterDelay or an internal battery depleted
- condition. Setting this object to 'off' will prevent
- the UPS system from restarting after a shutdown until
- an operator manually or remotely explicitly restarts
- it. If the UPS is in a startup or reboot countdown,
- then the UPS will not restart until that delay has
- been satisfied.(*)"
- ::= { upsControleighth 5 }
- upsReceptaclesNumeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of receptacles utilized in this device.
- This entry indicates the number of rows in the receptacle
- table."
- ::= { upsControleighth 6 }
- upsReceptacleEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsReceptacleEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of receptacle table entries. The number of
- entries is given by the value of upsReceptacleNum."
- ::= { upsControleighth 7 }
- upsReceptacleEighthEntry OBJECT-TYPE
- SYNTAX UpsReceptacleEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular receptacle."
- INDEX { upsReceptacleLineIndexeighth }
- ::= { upsReceptacleEighthTable 1 }
- UpsReceptacleEighthEntry ::= SEQUENCE {
- upsReceptacleLineIndexeighth PositiveInteger32,
- upsReceptacleOnOffeighth INTEGER
- }
- upsReceptacleLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The receptacle line identifier."
- ::= { upsReceptacleEighthEntry 1 }
- upsReceptacleOnOffeighth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the receptacle. Setting this
- object to 'on' will cause the receptacle to be turned
- on. Setting this object to 'off' will turn the
- receptacle off. If the receptacle is already in the
- desired state nothing will happen. After an
- autorestart (see upsAutoRestart) the receptacle will
- be on."
- ::= { upsReceptacleEighthEntry 2 }
- upsUPSModeeighth OBJECT-TYPE
- SYNTAX INTEGER {
- offLine(1),
- onLine(2),
- ecomode(3),
- iem(4)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The operation mode off the UPS. Off-line indicates a
- mode in which the input power is transferred to the
- output directly or via a step-up or step-down
- transformer. On-line mode indicates a mode in which
- the output power is regenerated through some convertor.
- the operating mode of the UPS may be fixed, or may be
- selectable (e.g. an on-line UPS with ecomode)"
- ::= { upsControleighth 8 }
- upsRectifierOnOffeighth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the rectifier. Setting this
- object to 'on' will cause the rectifier to be turned
- on. Setting this object to 'off' will turn the
- rectifier off. If the rectifier is already in the
- desired state nothing will happen. "
- ::= { upsControleighth 9 }
- upsBatteryChargeMethodeighth OBJECT-TYPE
- SYNTAX INTEGER {
- normalcharge(1),
- boostcharge(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the charge method. Setting this
- object to 'Normal charge' will cause the battery to be
- charged using the normal method. Setting this object to
- 'Boost charge' will charge the battery in boost mode.
- If the charge method is already in the desired state
- nothing will happen. "
- ::= { upsControleighth 10 }
- upsInverterOnOffeighth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the inverter. Setting this
- object to 'on' will cause the inverter to be turned
- on. Setting this object to 'off' will turn the
- inverter off. If the inverter is already in the
- desired state nothing will happen. "
- ::= { upsControleighth 11 }
- upsBypassOnOffeighth OBJECT-TYPE
- SYNTAX INTEGER {
- on(1),
- off(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present state of the bypass. Setting this
- object to 'on' will cause the bypass to be activated.
- Setting this object to 'off' will deactivate the
- bypass. If the UPS is already in the
- desired state nothing will happen. "
- ::= { upsControleighth 12 }
- upsLoadSourceeighth OBJECT-TYPE
- SYNTAX INTEGER {
- onbypass(1),
- onInverter(2),
- onDetour(3),
- loadOff(4),
- other (5)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The present source of the load. Setting this
- object to 'On bypass' will cause the load to be
- supplied by the bypass.
- Setting this object to 'On inverter' will cause the
- load to be supplied by the inverter.
- If the load is already supplied by the desired
- source nothing will happen. "
- ::= { upsControleighth 13 }
- --
- -- The Configuration group generic.
- --
- upsConfigInputVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal input voltage. On those
- systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigeighth 1 }
- upsConfigInputFreqeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal input frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigeighth 2 }
- upsConfigOutputVoltageeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal output voltage. On
- those systems which support read-write access to this
- object, if there is an attempt to set this variable to
- a value that is not supported, the request must be
- rejected and the agent shall respond with an
- appropriate error message, i.e., badValue for SNMPv1,
- or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigeighth 3 }
- upsConfigOutputFreqeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Hertz"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The nominal output frequency. On those systems which
- support read-write access to this object, if there is
- an attempt to set this variable to a value that is not
- supported, the request must be rejected and the agent
- shall respond with an appropriate error message, i.e.,
- badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
- ::= { upsConfigeighth 4 }
- upsConfigOutputVAeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal Volt-Amp rating.(*)"
- ::= { upsConfigeighth 5 }
- upsConfigOutputPowereighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The magnitude of the nominal true power rating.(*)"
- ::= { upsConfigeighth 6 }
- upsConfigLowBattTimeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The value of upsEstimatedMinutesRemaining at which a
- lowBattery condition is declared. For agents which
- support only discrete (discontinuous) values, then the
- agent shall round up to the next supported value. If
- the requested value is larger than the largest
- supported value, then the largest supported value
- shall be selected.(*)"
- ::= { upsConfigeighth 7 }
- upsConfigAudibleStatuseighth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2),
- muted(3)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The requested state of the audible alarm. When in
- the disabled state, the audible alarm should never
- sound. The enabled state is self-describing. Setting
- this object to muted(3) when the audible alarm is
- sounding shall temporarily silence the alarm. It will
- remain muted until it would normally stop sounding and
- the value returned for read operations during this
- period shall equal muted(3). At the end of this
- period, the value shall revert to enabled(2). Writes
- of the value muted(3) when the audible alarm is not
- sounding shall be accepted but otherwise shall have no
- effect.(*)"
- ::= { upsConfigeighth 8 }
- upsConfigLowVoltageTransferPointeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The minimum input line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigeighth 9 }
- upsConfigHighVoltageTransferPointeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "RMS Volts"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum line voltage allowed before the UPS
- system transfers to battery backup.(*)"
- ::= { upsConfigeighth 10 }
- upsConfigBatteryCapacityeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "Amps Hours"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The installed battery capacity. This value is the 'factory'-value,
- not the value after calibration."
- ::= { upsConfigeighth 11 }
- upsConfigBatteryChargeCurrenteighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- UNITS "0.1 Amp DC"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The maximum battery charge current, including external chargers."
- ::= { upsConfigeighth 12 }
- upsConfigNoLoadShutdowneighth OBJECT-TYPE
- SYNTAX INTEGER {
- disabled(1),
- enabled(2)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Dis- or enable 'no load' shutdown from the contact interface."
- ::= { upsConfigeighth 13 }
- upsConfigStartDelayeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- UNITS "minutes"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum required autonomy time before the UPS may perform an
- autorestart."
- ::= { upsConfigeighth 14 }
- --
- -- The GetSet group generic.
- --
- upsEventGetNexteighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventSetStartingTimeStamp
- will be used as the start value of the table with the lowest index number."
- ::= { upsGetSeteighth 1 }
- upsEventGetPreviouseighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of events to retreive from the UPS event buffer.
- When this object is set the EventTable will be filled with the
- requested number of entries. The value upsEventLastTime will
- be used as the last value of the table with the highest index number.
- Returns SNMPNOSUCHNAME for UPSs that don't support this command."
- ::= { upsGetSeteighth 2 }
- upsEventSetStartingTimeStampeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The timestamp which is used as starting point for downloading
- events from the UPS event buffer"
- ::= { upsGetSeteighth 3 }
- upsEventRetreiveCurrentTimeStampeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The current timestamp is retreived from the UPS"
- ::= { upsGetSeteighth 4 }
- upsEventTableSizeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the event table.
- This object indicates the number of rows in the event table."
- ::= { upsGetSeteighth 5 }
- upsEventEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsEventEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of event table entries. The number of entries is always
- 10, and the value of upsEventTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..10)):
- PDU-SET upsSetStartingTimeStamp <time>
- PDU-SET upsEventGetNext <number>
- PDU-GET upsEventTableSize
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
- PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
- ..
- PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsEventTableSize.
- "
- ::= { upsGetSeteighth 6 }
- upsEventEighthEntry OBJECT-TYPE
- SYNTAX UpsEventEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular event."
- INDEX { upsEventLineIndexeighth }
- ::= { upsEventEighthTable 1 }
- UpsEventEighthEntry ::= SEQUENCE {
- upsEventLineIndexeighth PositiveInteger32,
- upsEventCodeeighth Integer32,
- upsEventStatuseighth NonNegativeInteger32,
- upsEventTimeeighth NonNegativeInteger32
- }
- upsEventLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The event line identifier."
- ::= { upsEventEighthEntry 1 }
- upsEventCodeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The event code in numerical format."
- ::= { upsEventEighthEntry 2 }
- upsEventStatuseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The status of the UPS at the moment that the event was generated.
- The format is specified at the 'upsStatus' command.
- If the UPS is not able to deliver status information, then
- SNMPNOSUCHNAME is returned."
- ::= { upsEventEighthEntry 3 }
- upsEventTimeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The timestamp of the moment the event was generated."
- ::= { upsEventEighthEntry 4 }
- upsParametersReadeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to retreive from the UPS.
- When this object is set the ParameterTable will be filled with the
- requested number of entries. The value upsParametersStartAddress
- will be used as the start value of the table with the lowest index
- number."
- ::= { upsGetSeteighth 7 }
- upsParametersWriteeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The number of parameters to write to the UPS.
- When this object is set the ParameterTable will be send to the ups.
- The value upsParametersStartAddress will be used for the eighth value
- of the table with the lowest index number."
- ::= { upsGetSeteighth 8 }
- upsParametersStartAddresseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The address which is used as starting point for downloading
- parameters from the UPS"
- ::= { upsGetSeteighth 9 }
- upsParameterTableSizeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of entries in the parameter table.
- This object indicates the number of rows in the parameter table."
- ::= { upsGetSeteighth 10 }
- upsParameterEighthTable OBJECT-TYPE
- SYNTAX SEQUENCE OF UpsParameterEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "A list of parameter entries. The number of entries is always
- 16, and the value of upsParameterTableSize gives the number of valid
- entries from the begging of the table. Invalid entries return 0.
- To prevent problems with simultaneous queries from several agents,
- these values MUST be accessed using several PDUs in the
- same SNMP message (<number> is (1..16)):
- Read sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParametersRead <number>
- PDU-GET upsParameterTableSize
- PDU-GET upsParameterValue 1
- PDU-GET upsParameterValue 2
- ..
- PDU-GET upsParameterValue <number>
- The table is read up to requested number of events and the
- management software afterwards decides which entries are
- valid, as indicated by the upsParameterTableSize.
- Write sequence:
- PDU-SET upsSetStartingAddress <addr>
- PDU-SET upsParameterValue 1
- PDU-SET upsParameterValue 2
- ..
- PDU-SET upsParameterValue <number>
- PDU-SET upsParametersWrite <number>
- "
- ::= { upsGetSeteighth 11 }
- upsParameterEighthEntry OBJECT-TYPE
- SYNTAX UpsParameterEighthEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing information applicable to a
- particular parameter."
- INDEX { upsParameterLineIndexeighth }
- ::= { upsParameterEighthTable 1 }
- UpsParameterEighthEntry ::= SEQUENCE {
- upsParameterLineIndexeighth PositiveInteger32,
- upsParameterValueeighth Integer32
- }
- upsParameterLineIndexeighth OBJECT-TYPE
- SYNTAX PositiveInteger32
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "The parameter line identifier."
- ::= { upsParameterEighthEntry 1 }
- upsParameterValueeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The parameter value in numerical format."
- ::= { upsParameterEighthEntry 2 }
- upsStatuseighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The global UPS status is returned. Every bit reflects a specific
- status condition. Unused bits returns as 0. The status value can
- also be found on other commands. The value SNMPNOSUCHNAME means
- 'invalid status' or 'status value non available'.
- Status
- 1 0000 0001h upsStatusEcomodeIsOn
- 2 0000 0002h upsStatusBatteryIsCharging
- 4 0000 0004h upsStatusBatteryIsDischarging
- 8 0000 0008h upsStatusAlarmIsActive
- 16 0000 0010h upsStatusRectifierIsOn
- 32 0000 0020h upsStatusLowBattery
- 64 0000 0040h upsStatusOnBypass
- 128 0000 0080h upsStatusMainsBypassOK
- 256 0000 0100h upsStatusMainsRectifierOK
- 512 0000 0200h upsStatusDetourIsOn
- 1024 0000 0400h upsStatusAcousticAlarmIsOn
- 2048 0000 0800h upsStatusGlobalServiceCheck
- 4096 0000 1000h upsStatusInverterIsOn
- 8192 0000 2000h upsStatusNotInParallel (Q1 open)
- 16384 0000 4000h upsStatusResetLoadOff
- 32768 0000 8000h upsStatusLoadOff
- 65536 0001 0000h upsStatusBoostMode
- 131072 0002 0000h upsStatusBuckMode
- 262144 0004 0000h upsStatusIemModeIsOn
- 524288 0008 0000h upsStatus5thFilterIsOn
- 1048576 0010 0000h upsStatus11thFilterIsOn
- 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
- 4194304 0040 0000h - reserved -
- 8388608 0080 0000h - reserved -
- 16777216 0100 0000h - reserved -
- 33554432 0200 0000h - reserved -
- 67108864 0400 0000h - reserved -
- 134217728 0800 0000h - reserved -
- 268435456 1000 0000h upsGlobalParallelValues "
- ::= { upsGetSeteighth 12 }
- upsMainsStatisticsMBfaileighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of main bypass failures (>200 ms), since UPS installation."
- ::= { upsGetSeteighth 13 }
- upsMainsStatisticsMRfaileighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of mains rectifier failures (>200 ms), since UPS installation."
- ::= { upsGetSeteighth 14 }
- upsMainsStatisticsB2eighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (0..2 ms), during the last 7 days."
- ::= { upsGetSeteighth 15 }
- upsMainsStatisticsB5eighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (2..5 ms), during the last 7 days."
- ::= { upsGetSeteighth 16 }
- upsMainsStatisticsB10eighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (5..10 ms), during the last 7 days."
- ::= { upsGetSeteighth 17 }
- upsMainsStatisticsB200eighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Count of transients on the mains bypass (10..200 ms), during the last 7 days."
- ::= { upsGetSeteighth 18 }
- upsMainsStatisticsBypReleighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
- ::= { upsGetSeteighth 19 }
- upsTimeeighth OBJECT-TYPE
- SYNTAX NonNegativeInteger32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The current timestamp (or real-time) of the UPS. For the format,
- see 'Timestamp' specifications. The write-command has to comply with the
- correct timestamp format expected by the UPS (counter value or real-time-clock
- value). Missing to doing so will result in a SNMPeighthERROR,
- meaning 'command not supported'. It is possible to know which is the timestamp
- format supported by the UPS, by issuing a read-command or by reading events,
- which includes timestamps."
- ::= { upsGetSeteighth 20 }
- upsRequestPermissioneighth OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "An encrypted code is send to enable use of restricted write objects during
- a limited period of time."
- ::= { upsGetSeteighth 21 }
- upsEventGetCodeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The code which is used as starting point to downloading the events from the
- UPS event buffer."
- ::= { upsGetSeteighth 22 }
- upsEventSpinLockeighth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the event subsystem. "
- ::= { upsGetSeteighth 23 }
- upsParameterSpinLockeighth OBJECT-TYPE
- SYNTAX TestAndIncr
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A spin lock on the parameters subsystem. "
- ::= { upsGetSeteighth 24 }
- --
- -- GE Trap group generic
- --
- upsTrapAlarmBatteryBadeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "One or more batteries have been determined to require
- replacement."
- ::= { geUPSTrapseighth 1 }
- upsTrapAlarmOnBatteryeighth NOTIFICATION-TYPE
- OBJECTS { upsSecondsOnBatteryeighth }
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from the batteries."
- ::= { geUPSTrapseighth 2 }
- upsTrapAlarmLowBatteryeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The remaining battery run-time is less than or equal
- to upsConfigLowBattTime."
- ::= { geUPSTrapseighth 3 }
- upsTrapAlarmDepletedBatteryeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will be unable to sustain the present load
- when and if the utility power is lost)"
- ::= { geUPSTrapseighth 4 }
- upsTrapAlarmTempBadeighth NOTIFICATION-TYPE
- OBJECTS { upsBatteryTemperature }
- STATUS current
- DESCRIPTION
- "A temperature is out of tolerance."
- ::= { geUPSTrapseighth 5 }
- upsTrapAlarmInputBadeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input condition is out of tolerance."
- ::= { geUPSTrapseighth 6 }
- upsTrapAlarmOutputBadeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output condition (other than OutputOverload) is
- out of tolerance."
- ::= { geUPSTrapseighth 7 }
- upsTrapAlarmOutputOverloadeighth NOTIFICATION-TYPE
- OBJECTS { upsOutputNumLineseighth, upsOutputPercentLoadeighth }
- STATUS current
- DESCRIPTION
- "The output load exceeds the UPS output capacity."
- ::= { geUPSTrapseighth 8 }
- upsTrapAlarmOnBypasseighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is presently engaged on the UPS."
- ::= { geUPSTrapseighth 9 }
- upsTrapAlarmBypassBadeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The Bypass is out of tolerance."
- ::= { geUPSTrapseighth 10 }
- upsTrapAlarmOutputOffAsRequestedeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS has shutdown as requested, i.e., the output
- is off."
- ::= { geUPSTrapseighth 11 }
- upsTrapAlarmUpsOffAsRequestedeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The entire UPS has shutdown as commanded."
- ::= { geUPSTrapseighth 12 }
- upsTrapAlarmChargerFailedeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An uncorrected problem has been detected within the
- UPS charger subsystem."
- ::= { geUPSTrapseighth 13 }
- upsTrapAlarmUpsOutputOffeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS is in the off state."
- ::= { geUPSTrapseighth 14 }
- upsTrapAlarmUpsSystemOffeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is in the off state."
- ::= { geUPSTrapseighth 15 }
- upsTrapAlarmFanFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fans in the UPS has been
- detected."
- ::= { geUPSTrapseighth 16 }
- upsTrapAlarmFuseFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The failure of one or more fuses has been detected."
- ::= { geUPSTrapseighth 17 }
- upsTrapAlarmGeneralFaulteighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault in the UPS has been detected."
- ::= { geUPSTrapseighth 18 }
- upsTrapAlarmDiagnosticTestFailedeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The result of the last diagnostic test indicates a
- failure."
- ::= { geUPSTrapseighth 19 }
- upsTrapAlarmCommunicationsLosteighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem has been encountered in the communication
- between the agent and the UPS."
- ::= { geUPSTrapseighth 20 }
- upsTrapAlarmAwaitingPowereighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS output is off and the UPS is awaiting the
- return of the input power (*)."
- ::= { geUPSTrapseighth 21 }
- upsTrapAlarmShutdownPendingeighth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayeighth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is underway."
- ::= { geUPSTrapseighth 22 }
- upsTrapAlarmShutdownImminenteighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS will turn off power to the load in less than
- 5 eighths; this may be either a timed shutdown or a
- low battery shutdown."
- ::= { geUPSTrapseighth 23 }
- upsTrapAlarmTestInProgresseighth NOTIFICATION-TYPE
- OBJECTS { upsTestIdeighth }
- STATUS current
- DESCRIPTION
- "A test is in progress, as initiated and indicated by
- the Test Group. Tests initiated via other
- implementation-specific mechanisms can indicate the
- presence of the testing in the alarm table, if
- desired, via a OBJECT-IDENTITY macro in the MIB
- document specific to that implementation and are
- outside the scope of this OBJECT-IDENTITY."
- ::= { geUPSTrapseighth 24 }
- upsTrapAlarmReceptacleOffeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched off."
- ::= { geUPSTrapseighth 25 }
- upsTrapAlarmHighspeedBusFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is detected."
- ::= { geUPSTrapseighth 26 }
- upsTrapAlarmHighspeedBusJACRCFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is detected."
- ::= { geUPSTrapseighth 27 }
- upsTrapAlarmConnectivityBusFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is detected."
- ::= { geUPSTrapseighth 28 }
- upsTrapAlarmHighspeedBusJBCRCFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is detected."
- ::= { geUPSTrapseighth 29 }
- upsTrapAlarmCurrentSharingFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is detected."
- ::= { geUPSTrapseighth 30 }
- upsTrapAlarmDCRippleFailureeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is detected."
- ::= { geUPSTrapseighth 31 }
- upsTrapAlarmBatteryBadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Battery bad condition is restored."
- ::= { geUPSTrapseighth 33 }
- upsTrapAlarmOnBatteryRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS is drawing power from mains again."
- ::= { geUPSTrapseighth 34 }
- upsTrapAlarmLowBatteryRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Low Battery condition is restored."
- ::= { geUPSTrapseighth 35 }
- upsTrapAlarmDepletedBatteryRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Depleted Battery condition is restored."
- ::= { geUPSTrapseighth 36 }
- upsTrapAlarmTempBadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A bad temperature condition is restored."
- ::= { geUPSTrapseighth 37 }
- upsTrapAlarmInputBadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An input bad condition is restored."
- ::= { geUPSTrapseighth 38 }
- upsTrapAlarmOutputBadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output bad condition is restored."
- ::= { geUPSTrapseighth 39 }
- upsTrapAlarmOutputOverloadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An output overload condition is restored."
- ::= { geUPSTrapseighth 40 }
- upsTrapAlarmOnBypassRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An On Bypass condition is restored."
- ::= { geUPSTrapseighth 41 }
- upsTrapAlarmBypassBadRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Bypass bad condition is restored."
- ::= { geUPSTrapseighth 42 }
- upsTrapAlarmOutputOffAsRequestedRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A request shutdown has been restored."
- ::= { geUPSTrapseighth 43 }
- upsTrapAlarmUpsOffAsRequestedRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A entire UPS command has been restored."
- ::= { geUPSTrapseighth 44 }
- upsTrapAlarmChargerFailedRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Charger Failer condition is restored."
- ::= { geUPSTrapseighth 45 }
- upsTrapAlarmUpsOutputOneighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The output of the UPS switched in the on state."
- ::= { geUPSTrapseighth 46 }
- upsTrapAlarmUpsSystemOneighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "The UPS system is switched in the on state."
- ::= { geUPSTrapseighth 47 }
- upsTrapAlarmFanFailureRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fan failure condition is restored."
- ::= { geUPSTrapseighth 48 }
- upsTrapAlarmFuseFailureRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A Fuse failure condition is restored."
- ::= { geUPSTrapseighth 49 }
- upsTrapAlarmGeneralFaultRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A general fault is restored."
- ::= { geUPSTrapseighth 50 }
- upsTrapAlarmDiagnosticTestFailedRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A last diagnostic test indicates a failure is
- restored."
- ::= { geUPSTrapseighth 51 }
- upsTrapAlarmCommunicationsLostRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem in the communication between the agent
- and the UPS is restored."
- ::= { geUPSTrapseighth 52 }
- upsTrapAlarmAwaitingPowerRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A awaiting power condition is restored (*)."
- ::= { geUPSTrapseighth 53 }
- upsTrapAlarmShutdownPendingRestoredeighth NOTIFICATION-TYPE
- OBJECTS { upsShutdownAfterDelayeighth }
- STATUS current
- DESCRIPTION
- "A upsShutdownAfterDelay countdown is restored."
- ::= { geUPSTrapseighth 54 }
- upsTrapAlarmShutdownImminentRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A shutdown imminent condition is restored."
- ::= { geUPSTrapseighth 55 }
- upsTrapAlarmTestInProgressRestoredeighth NOTIFICATION-TYPE
- OBJECTS { upsTestIdeighth }
- STATUS current
- DESCRIPTION
- "The test is in progress is terminated."
- ::= { geUPSTrapseighth 56 }
- upsTrapAlarmReceptacleOneighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A receptacle has been switched on."
- ::= { geUPSTrapseighth 57 }
- upsTrapAlarmHighspeedBusRestoreeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Highspeed Bus communication is restored."
- ::= { geUPSTrapseighth 58 }
- upsTrapAlarmHighspeedBusJACRCRestoreeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JA is restored."
- ::= { geUPSTrapseighth 59 }
- upsTrapAlarmConnectivityBusRestoreeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A problem on the Connectivity Bus communication is restored."
- ::= { geUPSTrapseighth 60 }
- upsTrapAlarmHighspeedBusJBCRCRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A CRC failure on the Highspeed Bus JB is restored."
- ::= { geUPSTrapseighth 61 }
- upsTrapAlarmCurrentSharingRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high current sharing on the parallel system is restored."
- ::= { geUPSTrapseighth 62 }
- upsTrapAlarmDCRippleRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "An high ripple voltage on his DC link is restored."
- ::= { geUPSTrapseighth 63 }
- upsTrapAlarmValueLoweighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value below its low-level threshold."
- ::= { geUPSTrapseighth 129 }
- upsTrapAlarmValueHigheighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A measurement value reached a value higher than its high-level threshold."
- ::= { geUPSTrapseighth 130 }
- upsTrapAlarmValueLowRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueLow alarm condition is restored."
- ::= { geUPSTrapseighth 133 }
- upsTrapAlarmValueHighRestoredeighth NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "A ValueHigh alarm condition is restored."
- ::= { geUPSTrapseighth 134 }
- --
- -- Diagnostic Group Generic
- --
- upsDiagnosticBusJACommunicationStatuseighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticeighth 1 }
- upsDiagnosticBusJBCommunicationStatuseighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Bit oriented values associated to the ID of the UPS
- (bit0 = UPS1 ... bit7 = UPS8).
- The correspondent UPS is not present on the high speed
- bus communication JA if bit=0.(*)"
- ::= { upsDiagnosticeighth 2 }
- upsDiagnosticBatteryLifetimeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticeighth 3 }
- upsDiagnosticFansLifetimeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticeighth 4 }
- upsDiagnosticDCcapacitorsLifetimeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticeighth 5 }
- upsDiagnosticACcapacitorsLifetimeeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticeighth 6 }
- upsDiagnosticGlobalServiceCheckeighth OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The critical components are associated to Service
- parameters indicating the remaining lifetime.
- They are initially set to default values depending
- to the data given by the component supplier.
- The parameter values decrease over time and when one
- of them reaches zero (lifetime expiration) a service
- check warning is generated, indicating that a check or
- a replacement is suggested for that component.
- The service technician is then required to re-set the
- default value after the replacing of the component.(*)"
- ::= { upsDiagnosticeighth 7 }
- END