- VERTIV-BB-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- DisplayString FROM SNMPv2-TC
- SnmpAdminString FROM SNMP-FRAMEWORK-MIB
- MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY, enterprises, Integer32, Gauge32, NOTIFICATION-TYPE FROM SNMPv2-SMI
- sysName FROM SNMPv2-MIB;
- vertiv MODULE-IDENTITY
- LAST-UPDATED "201809100000Z"
- ORGANIZATION "Vertiv"
- CONTACT-INFO "support@geistglobal.com"
- DESCRIPTION "The MIB for Vertiv Products"
- REVISION "201809100000Z"
- DESCRIPTION "Modified for version 5 compliance"
- REVISION "201209110000Z"
- DESCRIPTION "Original version"
- ::= { enterprises 21239 }
- blackbird OBJECT IDENTIFIER
- ::= { vertiv 5 }
- watchdog100 OBJECT IDENTIFIER
- ::= { blackbird 1 }
- --###########################################################################################--
- --deviceInfo--
- --###########################################################################################--
- deviceInfo OBJECT IDENTIFIER
- ::= { watchdog100 1 }
- productTitle OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product name"
- ::= { deviceInfo 1 }
- productVersion OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product version"
- ::= { deviceInfo 2 }
- productFriendlyName OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "User-assigned name"
- ::= { deviceInfo 3 }
- productMacAddress OBJECT-TYPE
- SYNTAX OCTET STRING
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product's unique MAC address"
- ::= { deviceInfo 4 }
- deviceCount OBJECT-TYPE
- SYNTAX Integer32(0..5)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Total number of devices on unit"
- ::= { deviceInfo 6 }
- temperatureUnits OBJECT-TYPE
- SYNTAX INTEGER {
- fahrenheit(0),
- celsius(1)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Current units for temperature/dewpoint values:
- 0 = Degrees Fahrenheit
- 1 = Degrees Celsius"
- ::= { deviceInfo 7 }
- productModelNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product model number (factory-assigned)"
- ::= { deviceInfo 8 }
- productPartNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product part number (factory-assigned)"
- ::= { deviceInfo 9 }
- productSerialNumber OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product serial number (factory-assigned)"
- ::= { deviceInfo 10 }
- productPlatform OBJECT-TYPE
- SYNTAX SnmpAdminString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Product platform"
- ::= { deviceInfo 11 }
- --###########################################################################################--
- --internalTable--
- --###########################################################################################--
- internalTable OBJECT-TYPE
- SYNTAX SEQUENCE OF InternalEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Internal sensors for units"
- ::= { watchdog100 2 }
- internalEntry OBJECT-TYPE
- SYNTAX InternalEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the internalTable table: each entry contains an index and other sensor details"
- INDEX { internalIndex }
- ::= { internalTable 1 }
- InternalEntry ::= SEQUENCE {
- internalIndex Integer32,
- internalSerial DisplayString,
- internalLabel SnmpAdminString,
- internalAvail Gauge32,
- internalTemp Integer32,
- internalHumidity Integer32,
- internalDewPoint Integer32
- }
- internalIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { internalEntry 1 }
- internalSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { internalEntry 2 }
- internalLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { internalEntry 3 }
- internalAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
- ::= { internalEntry 4 }
- internalTemp OBJECT-TYPE
- SYNTAX Integer32(-40..200)
- UNITS "0.1 Degrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
- ::= { internalEntry 5 }
- internalHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity reading"
- ::= { internalEntry 6 }
- internalDewPoint OBJECT-TYPE
- SYNTAX Integer32(-40..200)
- UNITS "0.1 Degrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
- ::= { internalEntry 7 }
- --###########################################################################################--
- --tempSensorTable--
- --###########################################################################################--
- tempSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF TempSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature (RT) sensor"
- ::= { watchdog100 4 }
- tempSensorEntry OBJECT-TYPE
- SYNTAX TempSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the tempSensorTable table: each entry contains an index and other sensor details"
- INDEX { tempSensorIndex }
- ::= { tempSensorTable 1 }
- TempSensorEntry ::= SEQUENCE {
- tempSensorIndex Integer32,
- tempSensorSerial DisplayString,
- tempSensorLabel SnmpAdminString,
- tempSensorAvail Gauge32,
- tempSensorTemp Integer32
- }
- tempSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { tempSensorEntry 1 }
- tempSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { tempSensorEntry 2 }
- tempSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { tempSensorEntry 3 }
- tempSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { tempSensorEntry 4 }
- tempSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { tempSensorEntry 5 }
- --###########################################################################################--
- --airFlowSensorTable--
- --###########################################################################################--
- airFlowSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF AirFlowSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor"
- ::= { watchdog100 5 }
- airFlowSensorEntry OBJECT-TYPE
- SYNTAX AirFlowSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the airFlowSensorTable table: each entry contains an index and other sensor details"
- INDEX { airFlowSensorIndex }
- ::= { airFlowSensorTable 1 }
- AirFlowSensorEntry ::= SEQUENCE {
- airFlowSensorIndex Integer32,
- airFlowSensorSerial DisplayString,
- airFlowSensorLabel SnmpAdminString,
- airFlowSensorAvail Gauge32,
- airFlowSensorTemp Integer32,
- airFlowSensorFlow Integer32,
- airFlowSensorHumidity Integer32,
- airFlowSensorDewPoint Integer32
- }
- airFlowSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { airFlowSensorEntry 1 }
- airFlowSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { airFlowSensorEntry 2 }
- airFlowSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { airFlowSensorEntry 3 }
- airFlowSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { airFlowSensorEntry 4 }
- airFlowSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
- ::= { airFlowSensorEntry 5 }
- airFlowSensorFlow OBJECT-TYPE
- SYNTAX Integer32(0..100)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- " Airflow reading. Still air will be less than 20, while rushing air will be around 100."
- ::= { airFlowSensorEntry 6 }
- airFlowSensorHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity reading"
- ::= { airFlowSensorEntry 7 }
- airFlowSensorDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- " Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { airFlowSensorEntry 8 }
- --###########################################################################################--
- --dewPointSensorTable--
- --###########################################################################################--
- dewPointSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF DewPointSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Dew Point sensor"
- ::= { watchdog100 6 }
- dewPointSensorEntry OBJECT-TYPE
- SYNTAX DewPointSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the dewPointSensorTable table: each entry contains an index and other sensor details"
- INDEX { dewPointSensorIndex }
- ::= { dewPointSensorTable 1 }
- DewPointSensorEntry ::= SEQUENCE {
- dewPointSensorIndex Integer32,
- dewPointSensorSerial DisplayString,
- dewPointSensorName DisplayString,
- dewPointSensorAvail Gauge32,
- dewPointSensorTemp Integer32,
- dewPointSensorHumidity Integer32,
- dewPointSensorDewPoint Integer32
- }
- dewPointSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { dewPointSensorEntry 1 }
- dewPointSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { dewPointSensorEntry 2 }
- dewPointSensorName OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { dewPointSensorEntry 3 }
- dewPointSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { dewPointSensorEntry 4 }
- dewPointSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-40..200)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
- ::= { dewPointSensorEntry 5 }
- dewPointSensorHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity reading"
- ::= { dewPointSensorEntry 6 }
- dewPointSensorDewPoint OBJECT-TYPE
- SYNTAX Integer32(-40..200)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
- ::= { dewPointSensorEntry 7 }
- --###########################################################################################--
- --ccatSensorTable--
- --###########################################################################################--
- ccatSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF CcatSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote CCAT sensor"
- ::= { watchdog100 7 }
- ccatSensorEntry OBJECT-TYPE
- SYNTAX CcatSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the ccatSensorTable table: each entry contains an index and other sensor details"
- INDEX { ccatSensorIndex }
- ::= { ccatSensorTable 1 }
- CcatSensorEntry ::= SEQUENCE {
- ccatSensorIndex Integer32,
- ccatSensorSerial DisplayString,
- ccatSensorName DisplayString,
- ccatSensorAvail Gauge32,
- ccatSensorValue Integer32,
- ccatSensorType DisplayString,
- ccatSensorDescription DisplayString
- }
- ccatSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { ccatSensorEntry 1 }
- ccatSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { ccatSensorEntry 2 }
- ccatSensorName OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { ccatSensorEntry 3 }
- ccatSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { ccatSensorEntry 4 }
- ccatSensorValue OBJECT-TYPE
- SYNTAX Integer32(-100..5000)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "CCAT sensor reading"
- ::= { ccatSensorEntry 5 }
- ccatSensorType OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "CCAT sensor type"
- ::= { ccatSensorEntry 6 }
- ccatSensorDescription OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "CCAT sensor value description"
- ::= { ccatSensorEntry 7 }
- --###########################################################################################--
- --t3hdSensorTable--
- --###########################################################################################--
- t3hdSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF T3hdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature x 3, Humidity and Dewpoint Sensor"
- ::= { watchdog100 8 }
- t3hdSensorEntry OBJECT-TYPE
- SYNTAX T3hdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the t3hdSensorTable table: each entry contains an index and other sensor details"
- INDEX { t3hdSensorIndex }
- ::= { t3hdSensorTable 1 }
- T3hdSensorEntry ::= SEQUENCE {
- t3hdSensorIndex Integer32,
- t3hdSensorSerial DisplayString,
- t3hdSensorLabel SnmpAdminString,
- t3hdSensorAvail Gauge32,
- t3hdSensorIntLabel SnmpAdminString,
- t3hdSensorIntTemp Integer32,
- t3hdSensorIntHumidity Integer32,
- t3hdSensorIntDewPoint Integer32,
- t3hdSensorExtAAvail Gauge32,
- t3hdSensorExtALabel SnmpAdminString,
- t3hdSensorExtATemp Integer32,
- t3hdSensorExtBAvail Gauge32,
- t3hdSensorExtBLabel SnmpAdminString,
- t3hdSensorExtBTemp Integer32
- }
- t3hdSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { t3hdSensorEntry 1 }
- t3hdSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { t3hdSensorEntry 2 }
- t3hdSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { t3hdSensorEntry 3 }
- t3hdSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { t3hdSensorEntry 4 }
- t3hdSensorIntLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Internal label (user-defined)"
- ::= { t3hdSensorEntry 5 }
- t3hdSensorIntTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 6 }
- t3hdSensorIntHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal Humidity"
- ::= { t3hdSensorEntry 7 }
- t3hdSensorIntDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 8 }
- t3hdSensorExtAAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External A status:
- 0 =Unavailable
- 1 =Available"
- ::= { t3hdSensorEntry 9 }
- t3hdSensorExtALabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "External A label (user-defined)"
- ::= { t3hdSensorEntry 10 }
- t3hdSensorExtATemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- " External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 11 }
- t3hdSensorExtBAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External B status:
- 0 = Unavailable
- 1 = Available"
- ::= { t3hdSensorEntry 12 }
- t3hdSensorExtBLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "External B label (user-defined)"
- ::= { t3hdSensorEntry 13 }
- t3hdSensorExtBTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { t3hdSensorEntry 14 }
- --###########################################################################################--
- --thdSensorTable--
- --###########################################################################################--
- thdSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF ThdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Temperature, Humidity and Dewpoint (THD) Sensor"
- ::= { watchdog100 9 }
- thdSensorEntry OBJECT-TYPE
- SYNTAX ThdSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the thdSensorTable table: each entry contains an index and other sensor details"
- INDEX { thdSensorIndex }
- ::= { thdSensorTable 1 }
- ThdSensorEntry ::= SEQUENCE {
- thdSensorIndex Integer32,
- thdSensorSerial DisplayString,
- thdSensorLabel SnmpAdminString,
- thdSensorAvail Gauge32,
- thdSensorTemp Integer32,
- thdSensorHumidity Integer32,
- thdSensorDewPoint Integer32
- }
- thdSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { thdSensorEntry 1 }
- thdSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { thdSensorEntry 2 }
- thdSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { thdSensorEntry 3 }
- thdSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { thdSensorEntry 4 }
- thdSensorTemp OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- " Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { thdSensorEntry 5 }
- thdSensorHumidity OBJECT-TYPE
- SYNTAX Integer32(0..100)
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Humidity value"
- ::= { thdSensorEntry 6 }
- thdSensorDewPoint OBJECT-TYPE
- SYNTAX Integer32(-400..2540)
- UNITS "decidegrees"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo."
- ::= { thdSensorEntry 7 }
- --###########################################################################################--
- --rpmSensorTable--
- --###########################################################################################--
- rpmSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF RpmSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Remote Power Manager Sensor"
- ::= { watchdog100 10 }
- rpmSensorEntry OBJECT-TYPE
- SYNTAX RpmSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the rpmSensorTable table: each entry contains an index and other sensor details"
- INDEX { rpmSensorIndex }
- ::= { rpmSensorTable 1 }
- RpmSensorEntry ::= SEQUENCE {
- rpmSensorIndex Integer32,
- rpmSensorSerial DisplayString,
- rpmSensorName DisplayString,
- rpmSensorAvail Gauge32,
- rpmSensorEnergy Gauge32,
- rpmSensorVoltage Gauge32,
- rpmSensorVoltageMax Gauge32,
- rpmSensorVoltageMin Gauge32,
- rpmSensorVoltagePeak Gauge32,
- rpmSensorCurrent Gauge32,
- rpmSensorRealPower Gauge32,
- rpmSensorApparentPower Gauge32,
- rpmSensorPowerFactor Gauge32,
- rpmSensorOutlet1 Gauge32,
- rpmSensorOutlet2 Gauge32
- }
- rpmSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { rpmSensorEntry 1 }
- rpmSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { rpmSensorEntry 2 }
- rpmSensorName OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Friendly Name"
- ::= { rpmSensorEntry 3 }
- rpmSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { rpmSensorEntry 4 }
- rpmSensorEnergy OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "kWh"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Accumulated Energy"
- ::= { rpmSensorEntry 5 }
- rpmSensorVoltage OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Volts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Voltage"
- ::= { rpmSensorEntry 6 }
- rpmSensorVoltageMax OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Volts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Voltage (Max)"
- ::= { rpmSensorEntry 7 }
- rpmSensorVoltageMin OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Volts (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Voltage (Min)"
- ::= { rpmSensorEntry 8 }
- rpmSensorVoltagePeak OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Volts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Voltage (Peak)"
- ::= { rpmSensorEntry 9 }
- rpmSensorCurrent OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "0.1 Amps (rms)"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Current reading in deciAmps"
- ::= { rpmSensorEntry 10 }
- rpmSensorRealPower OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Watts"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Real Power"
- ::= { rpmSensorEntry 11 }
- rpmSensorApparentPower OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "Volt-Amps"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Apparent Power"
- ::= { rpmSensorEntry 12 }
- rpmSensorPowerFactor OBJECT-TYPE
- SYNTAX Gauge32
- UNITS "%"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Power Factor"
- ::= { rpmSensorEntry 13 }
- rpmSensorOutlet1 OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Outlet 1 State: 0 = off, 1 = on"
- ::= { rpmSensorEntry 14 }
- rpmSensorOutlet2 OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "RPM Sensor Outlet 2 State:
- 0 = off
- 1 = on"
- ::= { rpmSensorEntry 15 }
- --###########################################################################################--
- --a2dSensorTable--
- --###########################################################################################--
- a2dSensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF A2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Analog measurement (A2D) sensor (voltage, current, or dry-contact)"
- ::= { watchdog100 11 }
- a2dSensorEntry OBJECT-TYPE
- SYNTAX A2dSensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Entry in the a2dSensorTable table: each entry contains an index and other sensor details"
- INDEX { a2dSensorIndex }
- ::= { a2dSensorTable 1 }
- A2dSensorEntry ::= SEQUENCE {
- a2dSensorIndex Integer32,
- a2dSensorSerial DisplayString,
- a2dSensorLabel SnmpAdminString,
- a2dSensorAvail Gauge32,
- a2dSensorValue Integer32,
- a2dSensorDisplayValue SnmpAdminString,
- a2dSensorMode INTEGER,
- a2dSensorUnits SnmpAdminString,
- a2dSensorMin Integer32,
- a2dSensorMax Integer32,
- a2dSensorLowLabel SnmpAdminString,
- a2dSensorHighLabel SnmpAdminString,
- a2dSensorAnalogLabel SnmpAdminString
- }
- a2dSensorIndex OBJECT-TYPE
- SYNTAX Integer32(1..100)
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Table entry index value"
- ::= { a2dSensorEntry 1 }
- a2dSensorSerial OBJECT-TYPE
- SYNTAX DisplayString
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Serial Number"
- ::= { a2dSensorEntry 2 }
- a2dSensorLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "User-defined label"
- ::= { a2dSensorEntry 3 }
- a2dSensorAvail OBJECT-TYPE
- SYNTAX Gauge32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Device availability:
- 0 = Unavailable
- 1 = Available
- 2 = Partially Unavailable"
- ::= { a2dSensorEntry 4 }
- a2dSensorValue OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode."
- ::= { a2dSensorEntry 5 }
- a2dSensorDisplayValue OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- " For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue."
- ::= { a2dSensorEntry 6 }
- a2dSensorMode OBJECT-TYPE
- SYNTAX INTEGER {
- door(1),
- powerFailure(2),
- flood(3),
- wscLeak(4),
- wscFault(5),
- smoke(6),
- ivsNegGnd(7),
- ivsPosGnd(8),
- customVoltage(9),
- customBinary(10),
- customCurrent(11)
- }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 =Door (binary) 2 =Power failure (binary) 3 =Flood (binary) 4 =Water-sensing cable leak (binary) 5 =Water-sensing cable fault (binary) 6 =Smoke alarm (binary) 7 =Isolated voltage negative ground (voltage) 8 =Isolated voltage positive ground (voltage) 9 =Custom voltage (voltage) 10 =Custom binary (binary) 11 =Custom current (current)"
- ::= { a2dSensorEntry 7 }
- a2dSensorUnits OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..7))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 8 }
- a2dSensorMin OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 9 }
- a2dSensorMax OBJECT-TYPE
- SYNTAX Integer32(-1000000..1000000)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode."
- ::= { a2dSensorEntry 10 }
- a2dSensorLowLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode."
- ::= { a2dSensorEntry 11 }
- a2dSensorHighLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode."
- ::= { a2dSensorEntry 12 }
- a2dSensorAnalogLabel OBJECT-TYPE
- SYNTAX SnmpAdminString(SIZE (0..25))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- " Label for the analog measurement"
- ::= { a2dSensorEntry 13 }
- common OBJECT IDENTIFIER ::= { vertiv 42 }
- identity OBJECT IDENTIFIER ::= { common 1 }
- wd15 OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "Value (OID) used to identify a WD-15 unit"
- ::= { identity 31 }
- wd100 OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "Value (OID) used to identify a WD-100 unit"
- ::= { identity 32 }
- i02 OBJECT-IDENTITY
- STATUS current
- DESCRIPTION
- "Value (OID) used to identify a GU1 (I-02) unit"
- ::= { identity 52 }
- --###########################################################################################--
- --Notifications--
- --###########################################################################################--
- trap OBJECT IDENTIFIER ::= { watchdog100 32767 }
- trapPrefix OBJECT IDENTIFIER ::= { trap 0 }
- trapObj OBJECT IDENTIFIER ::= { trap 1 }
- trapSeverity OBJECT-TYPE
- SYNTAX INTEGER {
- none(0),
- warning(1),
- alarm(2)
- }
- MAX-ACCESS accessible-for-notify
- STATUS current
- DESCRIPTION
- "Indicates the severity of the trap:
- 0 = None,
- 1 = Warning,
- 2 = Alarm"
- ::= { trapObj 1 }
- trapThreshType OBJECT-TYPE
- SYNTAX INTEGER {
- low(1),
- high(2)
- }
- MAX-ACCESS accessible-for-notify
- STATUS current
- DESCRIPTION
- "Only sent for threshold alarms. Identifies the threshold type:
- 1 = Low,
- 2 = High"
- ::= { trapObj 2 }
- internalTestNOTIFY NOTIFICATION-TYPE
- STATUS current
- DESCRIPTION
- "Test SNMP Trap"
- ::= { trapPrefix 10101 }
- --#####deviceInfo#####--
- --#####internalTable#####--
- internalAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- internalAvail,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal device availability trap"
- ::= { trapPrefix 10205 }
- internalAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- internalAvail,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal device availability clear trap"
- ::= { trapPrefix 20205 }
- internalTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- internalTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal Temperature Sensor trap"
- ::= { trapPrefix 10206 }
- internalTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- internalTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal Temperature Sensor clear trap"
- ::= { trapPrefix 20206 }
- internalHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- internalHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal humidity trap"
- ::= { trapPrefix 10207 }
- internalHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- internalHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal humidity clear trap"
- ::= { trapPrefix 20207 }
- internalDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- internalDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal Dew Point Sensor trap"
- ::= { trapPrefix 10208 }
- internalDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- internalDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- internalLabel
- }
- STATUS current
- DESCRIPTION "Internal Dew Point Sensor clear trap"
- ::= { trapPrefix 20208 }
- --#####tempSensorTable#####--
- tempSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- tempSensorAvail,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT availability trap"
- ::= { trapPrefix 10404 }
- tempSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- tempSensorAvail,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT availability clear trap"
- ::= { trapPrefix 20404 }
- tempSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- tempSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT temperature trap"
- ::= { trapPrefix 10405 }
- tempSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- tempSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- tempSensorLabel
- }
- STATUS current
- DESCRIPTION "RT temperature clear trap"
- ::= { trapPrefix 20405 }
- --#####airFlowSensorTable#####--
- airFlowSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorAvail,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 availability trap"
- ::= { trapPrefix 10504 }
- airFlowSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorAvail,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 availability clear trap"
- ::= { trapPrefix 20504 }
- airFlowSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 temperature trap"
- ::= { trapPrefix 10505 }
- airFlowSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 temperature clear trap"
- ::= { trapPrefix 20505 }
- airFlowSensorFlowNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorFlow,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 airflow trap"
- ::= { trapPrefix 10506 }
- airFlowSensorFlowCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorFlow,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 airflow clear trap"
- ::= { trapPrefix 20506 }
- airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 humidity trap"
- ::= { trapPrefix 10507 }
- airFlowSensorHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 humidity clear trap"
- ::= { trapPrefix 20507 }
- airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 dewpoint trap"
- ::= { trapPrefix 10508 }
- airFlowSensorDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- airFlowSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- airFlowSensorLabel
- }
- STATUS current
- DESCRIPTION "AFHT3 dewpoint clear trap"
- ::= { trapPrefix 20508 }
- --#####dewPointSensorTable#####--
- dewPointSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorAvail,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint available trap"
- ::= { trapPrefix 10604 }
- dewPointSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorAvail,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint available clear trap"
- ::= { trapPrefix 20604 }
- dewPointSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint temperature trap"
- ::= { trapPrefix 10605 }
- dewPointSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint temperature clear trap"
- ::= { trapPrefix 20605 }
- dewPointSensorHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint humidity trap"
- ::= { trapPrefix 10606 }
- dewPointSensorHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint humidity clear trap"
- ::= { trapPrefix 20606 }
- dewPointSensorDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint dewpoint trap"
- ::= { trapPrefix 10607 }
- dewPointSensorDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- dewPointSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- dewPointSensorName
- }
- STATUS current
- DESCRIPTION "Dewpoint dewpoint clear trap"
- ::= { trapPrefix 20607 }
- --#####ccatSensorTable#####--
- ccatSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- ccatSensorAvail,
- trapSeverity,
- sysName,
- ccatSensorName
- }
- STATUS current
- DESCRIPTION "CCAT available trap"
- ::= { trapPrefix 10704 }
- ccatSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- ccatSensorAvail,
- trapSeverity,
- sysName,
- ccatSensorName
- }
- STATUS current
- DESCRIPTION "CCAT available clear trap"
- ::= { trapPrefix 20704 }
- ccatSensorValueNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- ccatSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- ccatSensorType,
- ccatSensorName
- }
- STATUS current
- DESCRIPTION "CCAT measurement trap"
- ::= { trapPrefix 10705 }
- ccatSensorValueCLEAR NOTIFICATION-TYPE
- OBJECTS {
- ccatSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- ccatSensorType,
- ccatSensorName
- }
- STATUS current
- DESCRIPTION "CCAT measurement clear trap"
- ::= { trapPrefix 20705 }
- --#####t3hdSensorTable#####--
- t3hdSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorAvail,
- trapSeverity,
- sysName,
- t3hdSensorLabel
- }
- STATUS current
- DESCRIPTION "T3HD availability trap"
- ::= { trapPrefix 10804 }
- t3hdSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorAvail,
- trapSeverity,
- sysName,
- t3hdSensorLabel
- }
- STATUS current
- DESCRIPTION "T3HD availability clear trap"
- ::= { trapPrefix 20804 }
- t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal temperature trap"
- ::= { trapPrefix 10806 }
- t3hdSensorIntTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal temperature clear trap"
- ::= { trapPrefix 20806 }
- t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal humidity trap"
- ::= { trapPrefix 10807 }
- t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD Internal humidity clear trap"
- ::= { trapPrefix 20807 }
- t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD dewpoint trap"
- ::= { trapPrefix 10808 }
- t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorIntDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorIntLabel
- }
- STATUS current
- DESCRIPTION "T3HD dewpoint clear trap"
- ::= { trapPrefix 20808 }
- t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtATemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtALabel
- }
- STATUS current
- DESCRIPTION "T3HD External A temperature trap"
- ::= { trapPrefix 10811 }
- t3hdSensorExtATempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtATemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtALabel
- }
- STATUS current
- DESCRIPTION "T3HD External A temperature clear trap"
- ::= { trapPrefix 20811 }
- t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtBTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtBLabel
- }
- STATUS current
- DESCRIPTION "T3HD External B temperature trap"
- ::= { trapPrefix 10814 }
- t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- t3hdSensorExtBTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- t3hdSensorLabel,
- t3hdSensorExtBLabel
- }
- STATUS current
- DESCRIPTION "T3HD External B temperature clear trap"
- ::= { trapPrefix 20814 }
- --#####thdSensorTable#####--
- thdSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorAvail,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD availability trap"
- ::= { trapPrefix 10904 }
- thdSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorAvail,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD availability clear trap"
- ::= { trapPrefix 20904 }
- thdSensorTempNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD temperature trap"
- ::= { trapPrefix 10905 }
- thdSensorTempCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorTemp,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD temperature clear trap"
- ::= { trapPrefix 20905 }
- thdSensorHumidityNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD humidity trap"
- ::= { trapPrefix 10906 }
- thdSensorHumidityCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorHumidity,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD humidity clear trap"
- ::= { trapPrefix 20906 }
- thdSensorDewPointNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- thdSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD dewpoint trap"
- ::= { trapPrefix 10907 }
- thdSensorDewPointCLEAR NOTIFICATION-TYPE
- OBJECTS {
- thdSensorDewPoint,
- temperatureUnits,
- trapThreshType,
- trapSeverity,
- sysName,
- thdSensorLabel
- }
- STATUS current
- DESCRIPTION "THD dewpoint clear trap"
- ::= { trapPrefix 20907 }
- --#####rpmSensorTable#####--
- rpmSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorAvail,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM available trap"
- ::= { trapPrefix 11004 }
- rpmSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorAvail,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM available clear trap"
- ::= { trapPrefix 21004 }
- rpmSensorEnergyNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM energy trap"
- ::= { trapPrefix 11005 }
- rpmSensorEnergyCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorEnergy,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM energy clear trap"
- ::= { trapPrefix 21005 }
- rpmSensorVoltageNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage trap"
- ::= { trapPrefix 11006 }
- rpmSensorVoltageCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltage,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage clear trap"
- ::= { trapPrefix 21006 }
- rpmSensorVoltageMaxNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltageMax,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (max) trap"
- ::= { trapPrefix 11007 }
- rpmSensorVoltageMaxCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltageMax,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (max) clear trap"
- ::= { trapPrefix 21007 }
- rpmSensorVoltageMinNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltageMin,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (min) trap"
- ::= { trapPrefix 11008 }
- rpmSensorVoltageMinCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltageMin,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (min) clear trap"
- ::= { trapPrefix 21008 }
- rpmSensorVoltagePeakNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltagePeak,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (peak) trap"
- ::= { trapPrefix 11009 }
- rpmSensorVoltagePeakCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorVoltagePeak,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM voltage (peak) clear trap"
- ::= { trapPrefix 21009 }
- rpmSensorCurrentNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM current trap"
- ::= { trapPrefix 11010 }
- rpmSensorCurrentCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorCurrent,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM current clear trap"
- ::= { trapPrefix 21010 }
- rpmSensorRealPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM real power trap"
- ::= { trapPrefix 11011 }
- rpmSensorRealPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorRealPower,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM real power clear trap"
- ::= { trapPrefix 21011 }
- rpmSensorApparentPowerNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM apparent power trap"
- ::= { trapPrefix 11012 }
- rpmSensorApparentPowerCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorApparentPower,
- trapThreshType,
- trapSeverity,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM apparent power clear trap"
- ::= { trapPrefix 21012 }
- rpmSensorPowerFactorNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorPowerFactor,
- trapSeverity,
- trapThreshType,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM power factor trap"
- ::= { trapPrefix 11013 }
- rpmSensorPowerFactorCLEAR NOTIFICATION-TYPE
- OBJECTS {
- rpmSensorPowerFactor,
- trapSeverity,
- trapThreshType,
- sysName,
- rpmSensorName
- }
- STATUS current
- DESCRIPTION "RPM power factor clear trap"
- ::= { trapPrefix 21013 }
- --#####a2dSensorTable#####--
- a2dSensorAvailNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorAvail,
- trapSeverity,
- sysName,
- a2dSensorLabel
- }
- STATUS current
- DESCRIPTION "A2D availability trap"
- ::= { trapPrefix 11104 }
- a2dSensorAvailCLEAR NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorAvail,
- trapSeverity,
- sysName,
- a2dSensorLabel
- }
- STATUS current
- DESCRIPTION "A2D availability clear trap"
- ::= { trapPrefix 21104 }
- a2dSensorValueNOTIFY NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- a2dSensorLabel,
- a2dSensorAnalogLabel,
- a2dSensorDisplayValue
- }
- STATUS current
- DESCRIPTION "A2D measurement trap"
- ::= { trapPrefix 11105 }
- a2dSensorValueCLEAR NOTIFICATION-TYPE
- OBJECTS {
- a2dSensorValue,
- trapThreshType,
- trapSeverity,
- sysName,
- a2dSensorLabel,
- a2dSensorAnalogLabel,
- a2dSensorDisplayValue
- }
- STATUS current
- DESCRIPTION "A2D measurement clear trap"
- ::= { trapPrefix 21105 }
- END