- GUDEADS-ESB7214-MIB DEFINITIONS ::= BEGIN
- IMPORTS
- enterprises,
- MODULE-IDENTITY,
- OBJECT-TYPE,
- NOTIFICATION-TYPE,
- Integer32,
- Unsigned32
- FROM SNMPv2-SMI
- OBJECT-GROUP,
- NOTIFICATION-GROUP
- FROM SNMPv2-CONF;
- gudeads MODULE-IDENTITY
- LAST-UPDATED "201904041600Z" -- Apr 4, 2019, 4:00:00 PM
- ORGANIZATION "GUDE Systems GmbH"
- CONTACT-INFO
- "Von-der-Wettern-Str. 23
- 51149 Cologne
- Germany
- https://www.gude.info"
- DESCRIPTION
- "Expert Power Control 7214 MIB"
- REVISION "201904041600Z" -- Apr 4, 2019, 4:00:00 PM
- DESCRIPTION
- ""
- -- 1.3.6.1.4.1.28507
- ::= { enterprises 28507 }
- esb7214PortResetDuration OBJECT-TYPE
- SYNTAX Integer32 (0..65535)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Delay in sec for turning Port on again after Reset action"
- DEFVAL { 0 }
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.8
- ::= { esb7214portEntry 8 }
- epc7214NTPClient OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.5.15
- ::= { esb7214IntSensors 15 }
- epc7214NTPUnixTime OBJECT-TYPE
- SYNTAX Unsigned32
- UNITS "s"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "show received NTP time as unixtime (secs since 1 January 1970)"
- -- 1.3.6.1.4.1.28507.67.1.5.15.2
- ::= { epc7214NTPClient 2 }
- epc7214NTPLastValidTimestamp OBJECT-TYPE
- SYNTAX Unsigned32
- UNITS "s"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "show seconds since last valid NTP timestamp received"
- -- 1.3.6.1.4.1.28507.67.1.5.15.3
- ::= { epc7214NTPClient 3 }
- epc7214NTPTimeValid OBJECT-TYPE
- SYNTAX INTEGER {
- notime(0),
- valid(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Show if valid Time is received"
- -- 1.3.6.1.4.1.28507.67.1.5.15.1
- ::= { epc7214NTPClient 1 }
- esb7214InputName OBJECT-TYPE
- SYNTAX OCTET STRING (SIZE (0..32))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A textual string containing name of
- the Input"
- -- 1.3.6.1.4.1.28507.67.1.5.6.2.1.32
- ::= { esb7214InputEntry 32 }
- esb7214ExtSensorName OBJECT-TYPE
- SYNTAX OCTET STRING (SIZE (0..32))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A textual string containing name of a
- external Sensor"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.32
- ::= { esb7214SensorEntry 32 }
- esb7214PwrSupplyTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Esb7214PwrSupplyEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "Power Supply Table - shows if Power Supply is avail"
- -- 1.3.6.1.4.1.28507.67.1.5.13
- ::= { esb7214IntSensors 13 }
- esb7214PwrSupplyEntry OBJECT-TYPE
- SYNTAX Esb7214PwrSupplyEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION ""
- INDEX {
- esb7214PwrSupplyIndex }
- -- 1.3.6.1.4.1.28507.67.1.5.13.1
- ::= { esb7214PwrSupplyTable 1 }
- Esb7214PwrSupplyEntry ::= SEQUENCE {
- esb7214PwrSupplyIndex Integer32,
- esb7214PwrSupplyStatus INTEGER }
- esb7214PwrSupplyIndex OBJECT-TYPE
- SYNTAX Integer32 (1..2)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Index of Power Supply entries"
- -- 1.3.6.1.4.1.28507.67.1.5.13.1.1
- ::= { esb7214PwrSupplyEntry 1 }
- esb7214PwrSupplyStatus OBJECT-TYPE
- SYNTAX INTEGER {
- up(1),
- down(0) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "shows status of the Power Supply
- 1 = fst, 2 = snd etc."
- -- 1.3.6.1.4.1.28507.67.1.5.13.1.2
- ::= { esb7214PwrSupplyEntry 2 }
- esb7214relayports OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.3.1
- ::= { esb7214IntActors 1 }
- esb7214portNumber OBJECT-TYPE
- SYNTAX Integer32 (1..12)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The number of Relay Ports"
- -- 1.3.6.1.4.1.28507.67.1.3.1.1
- ::= { esb7214relayports 1 }
- -- the Interfaces table
- -- The Interfaces table contains information on the entity's
- -- interfaces. Each sub-layer below the internetwork-layer
- -- of a network interface is considered to be an interface.
- esb7214portTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Esb7214portEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "list of all EPC Relay Ports"
- -- 1.3.6.1.4.1.28507.67.1.3.1.2
- ::= { esb7214relayports 2 }
- esb7214portEntry OBJECT-TYPE
- SYNTAX Esb7214portEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "An entry containing management information applicable to a
- particular relay port."
- INDEX {
- esb7214PortIndex }
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1
- ::= { esb7214portTable 1 }
- Esb7214portEntry ::= SEQUENCE {
- esb7214PortIndex Integer32,
- esb7214PortName OCTET STRING,
- esb7214PortState INTEGER,
- esb7214PortSwitchCount Integer32,
- esb7214PortStartupMode INTEGER,
- esb7214PortStartupDelay Integer32,
- esb7214PortRepowerTime Integer32,
- esb7214PortResetDuration Integer32 }
- esb7214PortIndex OBJECT-TYPE
- SYNTAX Integer32 (1..12)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A unique value, greater than zero, for each Relay Port."
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.1
- ::= { esb7214portEntry 1 }
- esb7214PortName OBJECT-TYPE
- SYNTAX OCTET STRING (SIZE (0..15))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "A textual string containing name of a Relay Port."
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.2
- ::= { esb7214portEntry 2 }
- esb7214PortState OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "current state of a Relay Port"
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.3
- ::= { esb7214portEntry 3 }
- esb7214PortSwitchCount OBJECT-TYPE
- SYNTAX Integer32
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "The total number of switch actions ocurred on a Relay Port.
- Does not count switch commands which will not switch
- the ralay state, so just real relay switches are displayed here."
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.4
- ::= { esb7214portEntry 4 }
- esb7214PortStartupMode OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1),
- laststate(2) }
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "set Mode of startup sequence (off, on , remember last state)"
- DEFVAL { off }
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.5
- ::= { esb7214portEntry 5 }
- esb7214PortStartupDelay OBJECT-TYPE
- SYNTAX Integer32
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Delay in sec for startup action"
- DEFVAL { 0 }
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.6
- ::= { esb7214portEntry 6 }
- esb7214PortRepowerTime OBJECT-TYPE
- SYNTAX Integer32 (0..65535)
- UNITS "seconds"
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "Delay in sec for repower port after switching off"
- DEFVAL { 0 }
- -- 1.3.6.1.4.1.28507.67.1.3.1.2.1.7
- ::= { esb7214portEntry 7 }
- esb7214AirPressure OBJECT-TYPE
- SYNTAX Integer32
- UNITS "1 hPA (hectopascal) ~ 1 milibar"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "actual air pressure"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.5
- ::= { esb7214SensorEntry 5 }
- esb7214DewPoint OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 degree Celsius"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "dew point for actual temperature and humidity"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.6
- ::= { esb7214SensorEntry 6 }
- esb7214DewPointDiff OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 degree Celsius"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "difference between dew point and actual
- temperature (Temp - DewPoint)"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.7
- ::= { esb7214SensorEntry 7 }
- esb7214POE OBJECT-TYPE
- SYNTAX Integer32 (0..1)
- UNITS "0 = no POE, 1 = POE available"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "signals POE availability"
- -- 1.3.6.1.4.1.28507.67.1.5.10
- ::= { esb7214IntSensors 10 }
- esb7214POEEvt NOTIFICATION-TYPE
- OBJECTS {
- esb7214POE}
- STATUS current
- DESCRIPTION
- "Power over Ethernet changed"
- -- 1.3.6.1.4.1.28507.67.3.8
- ::= { events 8 }
- gadsESB7214 OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67
- ::= { gudeads 67 }
- -- Notification Types
- --
- events OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.3
- ::= { gadsESB7214 3 }
- -- Scalars and Tables
- --
- esb7214Objects OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1
- ::= { gadsESB7214 1 }
- esb7214CommonConfig OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.1
- ::= { esb7214Objects 1 }
- esb7214SNMPaccess OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.1.1
- ::= { esb7214CommonConfig 1 }
- esb7214TrapCtrl OBJECT-TYPE
- SYNTAX Integer32 (0..3)
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "0 = off
- 1 = Ver. 1
- 2 = Ver. 2c
- 3 = Ver. 3"
- -- 1.3.6.1.4.1.28507.67.1.1.1.1
- ::= { esb7214SNMPaccess 1 }
- esb7214TrapIPTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Esb7214TrapIPEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "list of all Trap receiver"
- -- 1.3.6.1.4.1.28507.67.1.1.1.2
- ::= { esb7214SNMPaccess 2 }
- esb7214TrapIPEntry OBJECT-TYPE
- SYNTAX Esb7214TrapIPEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION
- "an entry containing management
- informations regarding the list of trap
- receivers"
- INDEX {
- esb7214TrapIPIndex }
- -- 1.3.6.1.4.1.28507.67.1.1.1.2.1
- ::= { esb7214TrapIPTable 1 }
- Esb7214TrapIPEntry ::= SEQUENCE {
- esb7214TrapIPIndex Integer32,
- esb7214TrapAddr OCTET STRING }
- esb7214TrapIPIndex OBJECT-TYPE
- SYNTAX Integer32 (1..8)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "A unique value, greater than zero, for each receiver slot."
- -- 1.3.6.1.4.1.28507.67.1.1.1.2.1.1
- ::= { esb7214TrapIPEntry 1 }
- esb7214TrapAddr OBJECT-TYPE
- SYNTAX OCTET STRING (SIZE (0..99))
- MAX-ACCESS read-write
- STATUS current
- DESCRIPTION
- "DNS name or IP address specifying one Trap receiver slot.
- A port can optionally be specified: 'name:port' An empty
- string disables this slot."
- -- 1.3.6.1.4.1.28507.67.1.1.1.2.1.2
- ::= { esb7214TrapIPEntry 2 }
- esb7214DeviceConfig OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.2
- ::= { esb7214Objects 2 }
- esb7214IntActors OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.3
- ::= { esb7214Objects 3 }
- esb7214ExtActors OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.4
- ::= { esb7214Objects 4 }
- esb7214IntSensors OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.5
- ::= { esb7214Objects 5 }
- esb7214ExtSensors OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.6
- ::= { esb7214Objects 6 }
- esb7214SensorTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Esb7214SensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION ""
- -- 1.3.6.1.4.1.28507.67.1.6.1
- ::= { esb7214ExtSensors 1 }
- esb7214SensorEntry OBJECT-TYPE
- SYNTAX Esb7214SensorEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION ""
- INDEX {
- esb7214SensorIndex }
- -- 1.3.6.1.4.1.28507.67.1.6.1.1
- ::= { esb7214SensorTable 1 }
- Esb7214SensorEntry ::= SEQUENCE {
- esb7214SensorIndex Integer32,
- esb7214TempSensor Integer32,
- esb7214HygroSensor Integer32,
- esb7214InputSensor INTEGER,
- esb7214AirPressure Integer32,
- esb7214DewPoint Integer32,
- esb7214DewPointDiff Integer32,
- esb7214ExtSensorName OCTET STRING }
- esb7214SensorIndex OBJECT-TYPE
- SYNTAX Integer32 (1..4)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION ""
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.1
- ::= { esb7214SensorEntry 1 }
- esb7214TempSensor OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 degree Celsius"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "actual temperature"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.2
- ::= { esb7214SensorEntry 2 }
- esb7214HygroSensor OBJECT-TYPE
- SYNTAX Integer32
- UNITS "0.1 percent humidity"
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "actual humidity"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.3
- ::= { esb7214SensorEntry 3 }
- esb7214InputSensor OBJECT-TYPE
- SYNTAX INTEGER {
- off(0),
- on(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "logical state of input sensor"
- -- 1.3.6.1.4.1.28507.67.1.6.1.1.4
- ::= { esb7214SensorEntry 4 }
- -- Conformance
- --
- esb7214Conf OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.2
- ::= { gadsESB7214 2 }
- -- Groups
- --
- esb7214Groups OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.2.1
- ::= { esb7214Conf 1 }
- -- Compliance
- --
- esb7214Compls OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.2.2
- ::= { esb7214Conf 2 }
- esb7214BasicGroup OBJECT-GROUP
- OBJECTS {
- esb7214TrapCtrl,
- esb7214TrapIPIndex,
- esb7214TrapAddr,
- esb7214portNumber,
- esb7214PortIndex,
- esb7214PortName,
- esb7214PortState,
- esb7214PortSwitchCount,
- esb7214PortStartupMode,
- esb7214PortStartupDelay,
- esb7214PortRepowerTime,
- esb7214ActiveInputs,
- esb7214InputIndex,
- esb7214Input,
- esb7214POE,
- esb7214SensorIndex,
- esb7214TempSensor,
- esb7214HygroSensor,
- esb7214InputSensor,
- esb7214AirPressure,
- esb7214DewPoint,
- esb7214DewPointDiff,
- esb7214PwrSupplyIndex,
- esb7214PwrSupplyStatus,
- esb7214ExtSensorName,
- esb7214InputName,
- epc7214NTPTimeValid,
- epc7214NTPUnixTime,
- epc7214NTPLastValidTimestamp,
- esb7214PortResetDuration }
- STATUS current
- DESCRIPTION
- "Basic objects."
- -- 1.3.6.1.4.1.28507.67.2.1.1
- ::= { esb7214Groups 1 }
- esb7214NotificationGroup NOTIFICATION-GROUP
- NOTIFICATIONS {
- esb7214InputEvt,
- esb7214TempEvtSen,
- esb7214HygroEvtSen,
- esb7214InputEvtSen,
- esb7214AirPressureEvtSen,
- esb7214DewPtDiffEvtSen,
- esb7214POEEvt,
- esb7214SwitchEvtPort,
- esb7214PwrSupplyChangeEvt }
- STATUS current
- DESCRIPTION ""
- -- 1.3.6.1.4.1.28507.67.2.1.2
- ::= { esb7214Groups 2 }
- esb7214Inputs OBJECT IDENTIFIER
- -- 1.3.6.1.4.1.28507.67.1.5.6
- ::= { esb7214IntSensors 6 }
- esb7214InputEntry OBJECT-TYPE
- SYNTAX Esb7214InputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION ""
- INDEX {
- esb7214InputIndex }
- -- 1.3.6.1.4.1.28507.67.1.5.6.2.1
- ::= { esb7214InputTable 1 }
- Esb7214InputEntry ::= SEQUENCE {
- esb7214InputIndex Integer32,
- esb7214Input INTEGER,
- esb7214InputName OCTET STRING }
- esb7214Input OBJECT-TYPE
- SYNTAX INTEGER {
- lo(0),
- hi(1) }
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Input state of device"
- -- 1.3.6.1.4.1.28507.67.1.5.6.2.1.2
- ::= { esb7214InputEntry 2 }
- esb7214InputEvt NOTIFICATION-TYPE
- OBJECTS {
- esb7214InputIndex,
- esb7214Input}
- STATUS current
- DESCRIPTION
- "Change of device input."
- -- 1.3.6.1.4.1.28507.67.3.2
- ::= { events 2 }
- esb7214ActiveInputs OBJECT-TYPE
- SYNTAX Unsigned32 (1..12)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION
- "Number of suppported Input Channels."
- -- 1.3.6.1.4.1.28507.67.1.5.6.1
- ::= { esb7214Inputs 1 }
- esb7214InputTable OBJECT-TYPE
- SYNTAX SEQUENCE OF Esb7214InputEntry
- MAX-ACCESS not-accessible
- STATUS current
- DESCRIPTION ""
- -- 1.3.6.1.4.1.28507.67.1.5.6.2
- ::= { esb7214Inputs 2 }
- esb7214InputIndex OBJECT-TYPE
- SYNTAX Integer32 (1..12)
- MAX-ACCESS read-only
- STATUS current
- DESCRIPTION ""
- -- 1.3.6.1.4.1.28507.67.1.5.6.2.1.1
- ::= { esb7214InputEntry 1 }
- esb7214HygroEvtSen NOTIFICATION-TYPE
- OBJECTS {
- esb7214SensorIndex,
- esb7214HygroSensor}
- STATUS current
- DESCRIPTION
- "hygro limits exceeded"
- -- 1.3.6.1.4.1.28507.67.3.4
- ::= { events 4 }
- esb7214InputEvtSen NOTIFICATION-TYPE
- OBJECTS {
- esb7214SensorIndex,
- esb7214InputSensor}
- STATUS current
- DESCRIPTION
- "change of logical input sensor state"
- -- 1.3.6.1.4.1.28507.67.3.5
- ::= { events 5 }
- esb7214AirPressureEvtSen NOTIFICATION-TYPE
- OBJECTS {
- esb7214SensorIndex,
- esb7214AirPressure}
- STATUS current
- DESCRIPTION
- "Air Pressure limits exceeded
- "
- -- 1.3.6.1.4.1.28507.67.3.6
- ::= { events 6 }
- esb7214DewPtDiffEvtSen NOTIFICATION-TYPE
- OBJECTS {
- esb7214SensorIndex,
- esb7214DewPointDiff}
- STATUS current
- DESCRIPTION
- "Dew Point Difference limits exceeded"
- -- 1.3.6.1.4.1.28507.67.3.7
- ::= { events 7 }
- esb7214TempEvtSen NOTIFICATION-TYPE
- OBJECTS {
- esb7214SensorIndex,
- esb7214TempSensor}
- STATUS current
- DESCRIPTION
- "temperature limits exceeded"
- -- 1.3.6.1.4.1.28507.67.3.3
- ::= { events 3 }
- esb7214SwitchEvtPort NOTIFICATION-TYPE
- OBJECTS {
- esb7214PortIndex,
- esb7214PortName,
- esb7214PortState,
- esb7214PortSwitchCount}
- STATUS current
- DESCRIPTION
- "Event is triggered when a port is switched"
- -- 1.3.6.1.4.1.28507.67.3.1
- ::= { events 1 }
- esb7214PwrSupplyChangeEvt NOTIFICATION-TYPE
- OBJECTS {
- esb7214PwrSupplyIndex,
- esb7214PwrSupplyStatus}
- STATUS current
- DESCRIPTION
- "Event is triggered when Power Supply state
- changes"
- -- 1.3.6.1.4.1.28507.67.3.9
- ::= { events 9 }
- END