-- company power MIB -- -- { iso org(3) dod(6) internet(1) private(4) enterprises(1) company(2111) -- products(1) ups(1) -- -- ============================================================================================== companyMIB DEFINITIONS ::= BEGIN IMPORTS enterprises FROM RFC1155-SMI MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY FROM SNMPv2-SMI DisplayString FROM SNMPv2-TC TRAP-TYPE FROM RFC-1215 PositiveInteger, NonNegativeInteger FROM UPS-MIB; companyMIB MODULE-IDENTITY LAST-UPDATED "20100560000Z" ORGANIZATION "company Power Technology" CONTACT-INFO " " DESCRIPTION "The MIB module to describe UPS" ::= { enterprises 21111 } products OBJECT IDENTIFIER ::= { companyMIB 1 } ups OBJECT IDENTIFIER ::= { products 1 } inverter OBJECT IDENTIFIER ::= { products 2 } charger OBJECT IDENTIFIER ::= { products 3 } ATS OBJECT IDENTIFIER ::= { products 4 } upsIdent OBJECT IDENTIFIER ::= { ups 1 } upsRating OBJECT IDENTIFIER ::= { ups 2 } upsBattery OBJECT IDENTIFIER ::= { ups 3 } upsInput OBJECT IDENTIFIER ::= { ups 4 } upsOutput OBJECT IDENTIFIER ::= { ups 5 } upsBypass OBJECT IDENTIFIER ::= { ups 6 } upsTest OBJECT IDENTIFIER ::= { ups 7 } upsControl OBJECT IDENTIFIER ::= { ups 8 } agentConfig OBJECT IDENTIFIER ::= { ups 9 } commConfig OBJECT IDENTIFIER ::= { ups 10 } upsConfig OBJECT IDENTIFIER ::= { ups 11 } upsTraps OBJECT IDENTIFIER ::= { ups 12 } extend OBJECT IDENTIFIER ::= { ups 13 } solarIdent OBJECT IDENTIFIER ::= { inverter 1 } solarRating OBJECT IDENTIFIER ::= { inverter 2 } solarBattery OBJECT IDENTIFIER ::= { inverter 3 } solarGrid OBJECT IDENTIFIER ::= { inverter 4 } solarACOutput OBJECT IDENTIFIER ::= { inverter 5 } solarPV OBJECT IDENTIFIER ::= { inverter 6 } solarEnergy OBJECT IDENTIFIER ::= { inverter 7 } solarTest OBJECT IDENTIFIER ::= { inverter 8 } solarDefValue OBJECT IDENTIFIER ::= { inverter 9 } solarFaultInfo OBJECT IDENTIFIER ::= { inverter 10 } solarControl OBJECT IDENTIFIER ::= { inverter 11 } solarAgentConfig OBJECT IDENTIFIER ::= { inverter 12 } solarCommConfig OBJECT IDENTIFIER ::= { inverter 13 } solarConfig OBJECT IDENTIFIER ::= { inverter 14 } solarTraps OBJECT IDENTIFIER ::= { inverter 15 } solarExtend OBJECT IDENTIFIER ::= { inverter 16 } ATSIdent OBJECT IDENTIFIER ::= { ATS 1 } ATSRating OBJECT IDENTIFIER ::= { ATS 2 } ATSInformation OBJECT IDENTIFIER ::= { ATS 3 } ATSControl OBJECT IDENTIFIER ::= { ATS 4 } ATSAgentConfig OBJECT IDENTIFIER ::= { ATS 5 } ATSCommConfig OBJECT IDENTIFIER ::= { ATS 6 } ATSConfig OBJECT IDENTIFIER ::= { ATS 7 } ATSTraps OBJECT IDENTIFIER ::= { ATS 8 } ATSExtend OBJECT IDENTIFIER ::= { ATS 9 } ---======================================================= ---upsIdent --- prefix =upsId ---======================================================== upsIdManufacturer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "The name of the UPS manufacturer." ::= { upsIdent 1 } upsIdProtocol OBJECT-TYPE SYNTAX INTEGER { unknown(-1), pmv(99), p00(0), p01(1), p02(2), p03(3), p04(4), p05(5), p06(6), p07(7), p08(8), p09(9), p10(10), sec(80) } ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Protocol id." ::= { upsIdent 2 } upsIdModelName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..15)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Model designation." ::= { upsIdent 3 } upsIdSerialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "The UPS serial no." ::= { upsIdent 4 } upsIdName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the UPS. This object should be set by the administrator." ::= { upsIdent 5 } upsIdFWVersion OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "Main CPU firmware version." ::= { upsIdent 6 } upsIdUPSType OBJECT-TYPE SYNTAX INTEGER { standy(0), line-interactive(1), on-line(2) } ACCESS read-only STATUS mandatory DESCRIPTION "UPS type." ::= { upsIdent 7 } --=========================================================================== --upsRating --prefix =upsRat --the rating info of ups --========================================================================== upsRatinVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Volt DC" ACCESS read-only STATUS current DESCRIPTION "The rating input voltage of UPS" ::= { upsRating 1 } upsRatoutVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Volt DC" ACCESS read-only STATUS current DESCRIPTION "The rating output voltage of UPS" ::= { upsRating 2 } upsRatoutFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 HZ" ACCESS read-only STATUS current DESCRIPTION "The rating output frequency of UPS" ::= { upsRating 3 } upsRatoutCurrent OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The rating output current of UPS" ::= { upsRating 4 } upsRatoutApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 VA" ACCESS read-only STATUS current DESCRIPTION "The rating output apparent power of UPS" ::= { upsRating 5 } upsRatoutTruePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Wt" ACCESS read-only STATUS current DESCRIPTION "The rating output true power of UPS" ::= { upsRating 6 } upsRatBatVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 vol" ACCESS read-only STATUS current DESCRIPTION "The rating battery voltage of UPS" ::= { upsRating 7 } -- =========================================================================== -- upsBattery -- prefix = upsBat -- The Battery group. -- est=estimated -- =========================================================================== upsBatStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8) } ACCESS read-only STATUS mandatory DESCRIPTION "The indication of the status in the UPS system's batteries." ::= { upsBattery 1 } upsBatSecondsOnBattery OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-only STATUS current DESCRIPTION "If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power." ::= { upsBattery 2 } upsBatEstMinutesRemaining OBJECT-TYPE SYNTAX INTEGER UNITS "minutes" ACCESS read-only STATUS current DESCRIPTION "An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off." ::= { upsBattery 3 } upsBatEstChargeRemaining OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "percent" ACCESS read-only STATUS current DESCRIPTION "An estimate of the battery charge remaining expressed as a percent of full charge." ::= { upsBattery 4 } upsBatPBatVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Volt DC" ACCESS read-only STATUS current DESCRIPTION "The magnitude of the present Positive battery voltage." ::= { upsBattery 5 } upsBatNBatVoltage OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Volt DC" ACCESS read-only STATUS current DESCRIPTION "The magnitude of the present negative battery voltage." ::= { upsBattery 6 } upsBatPBatCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The positive battery present current." ::= { upsBattery 7 } upsBatNBatCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The present negative battery current." ::= { upsBattery 8 } upsBatPBatChargCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The Positive battery charging current." ::= { upsBattery 9 } upsBatNBatchargCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The present negative battery charging current." ::= { upsBattery 10 } upsBatPBatDischargCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The present positive battery discharging current." ::= { upsBattery 11 } upsBatNBatDischargCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The present negative battery discharging current." ::= { upsBattery 12 } upsBatTemperature OBJECT-TYPE SYNTAX INTEGER UNITS "degrees 0.1 Centigrade" ACCESS read-only STATUS current DESCRIPTION "The ambient temperature at or near the UPS Battery casing." ::= { upsBattery 13 } upsBatNumberInSeries OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS current DESCRIPTION "The number of battery in series." ::= { upsBattery 14 } upsBatNumberInParallel OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS current DESCRIPTION "The number of battery in Parallel." ::= { upsBattery 15 } upsBatPBatDischargCurrent2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "The present positive battery pipe2 discharging current." ::= { upsBattery 16 } -- =========================================================================== -- upsInput -- prefix = upsIn -- Input group. -- =========================================================================== upsInLineBads OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS current DESCRIPTION "A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance." ::= { upsInput 1 } upsInTtlApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1VA" ACCESS read-only STATUS current DESCRIPTION "Total input apparent power ." ::= { upsInput 2 } upsInTtlTruePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1WT" ACCESS read-only STATUS current DESCRIPTION "Total input active(true) power ." ::= { upsInput 3 } upsInNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS current DESCRIPTION "The number of input lines utilized in this device. This variable indicates the number of rows in the input table." ::= { upsInput 4 } upsInTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsInEntry ACCESS not-accessible STATUS current DESCRIPTION "A list of input table entries. The number of entries is given by the value of upsInputNumLines." ::= { upsInput 5 } upsInTtlVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The input utility line tatol voltage ." ::= { upsInput 6 } upsInTtlCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 A" ACCESS read-only STATUS current DESCRIPTION "The input utility line tatol current." ::= { upsInput 7 } upsInEntry OBJECT-TYPE SYNTAX UpsInEntry ACCESS not-accessible STATUS current DESCRIPTION "An entry containing information applicable to a particular input line." INDEX { upsInLineIndex } ::= { upsInTable 1 } UpsInEntry ::= SEQUENCE { upsInLineIndex PositiveInteger, upsInFrequency NonNegativeInteger, upsInVoltage NonNegativeInteger, upsInCurrent NonNegativeInteger, upsInApparentPower NonNegativeInteger, upsInTruePower NonNegativeInteger, upsInPowerFactor NonNegativeInteger, upsInLineVoltage NonNegativeInteger } upsInLineIndex OBJECT-TYPE SYNTAX INTEGER (0..10) ACCESS read-only STATUS current DESCRIPTION "The number of output lines" ::= { upsInEntry 1 } upsInFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1 Hertz" ACCESS read-only STATUS current DESCRIPTION "The present input frequency." ::= { upsInEntry 2 } upsInVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The input utility line voltage ." ::= { upsInEntry 3 } upsInCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1Amp" ACCESS read-only STATUS current DESCRIPTION "The magnitude of the present input current " ::= { upsInEntry 4 } upsInApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1VA" ACCESS read-only STATUS current DESCRIPTION "The magnitude of the present input Apparent power." ::= { upsInEntry 5 } upsInTruePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1Watts" ACCESS read-only STATUS current DESCRIPTION "The magnitude of the present input true power." ::= { upsInEntry 6 } upsInPowerFactor OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.01" ACCESS read-only STATUS current DESCRIPTION "Input true power/apparent power factor " ::= { upsInEntry 7 } upsInLineVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The input utility line voltage . if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase; if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase; if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase." ::= { upsInEntry 8 } -- =========================================================================== -- upsOutput -- prefix= upsOut -- Output group -- =========================================================================== upsOutSource OBJECT-TYPE SYNTAX INTEGER { other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), HE-ECO_mode(10), converter_mode(11) } ACCESS read-only STATUS current DESCRIPTION "The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode" ::= { upsOutput 1 } upsOutFrequency OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Hertz" ACCESS read-only STATUS current DESCRIPTION "The current output frequency of the UPS system " ::= { upsOutput 2 } upsOutTtlApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1VA" ACCESS read-only STATUS current DESCRIPTION "Total output apparent power ." ::= { upsOutput 3 } upsOutTtlTruePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1Watts" ACCESS read-only STATUS current DESCRIPTION "Total output active(true) power ." ::= { upsOutput 4 } upsOutTtlPercentLoad OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "percent" ACCESS read-only STATUS current DESCRIPTION "The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA." ::= { upsOutput 5 } upsOutNumLines OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "The number of output lines utilized in this device. This variable indicates the number of rows in the output table." ::= { upsOutput 6 } upsOutTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsOutEntry ACCESS not-accessible STATUS current DESCRIPTION "A list of output table entries. The number of entries is given by the value of upsOutputNumLines." ::= { upsOutput 7 } upsOutTtlVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1vot" ACCESS read-only STATUS current DESCRIPTION "Total output voltage ." ::= { upsOutput 8 } upsOutTtlCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-only STATUS current DESCRIPTION "Total output current." ::= { upsOutput 9 } upsOutStatus OBJECT-TYPE SYNTAX DisplayString (SIZE (4..4)) ACCESS read-only STATUS current DESCRIPTION " For HVDC device. char status[4]; status[0]status[1]:00, no output1; 01, line output1; 02, bat output1 status[2]status[3]:00, no output2; 01, line output2; 02, bat output2 " ::= { upsOutput 10 } upsOutSource2 OBJECT-TYPE SYNTAX INTEGER { other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7), batterytest(8), fault(9), HE-ECO_mode(10), converter_mode(11) } ACCESS read-only STATUS current DESCRIPTION "For HVDC(protocol:P12) machine. The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode" ::= { upsOutput 11 } upsOutEntry OBJECT-TYPE SYNTAX UpsOutEntry ACCESS not-accessible STATUS current DESCRIPTION "An entry containing information applicable to a particular output line." INDEX { upsOutLineIndex } ::= { upsOutTable 1 } UpsOutEntry ::= SEQUENCE { upsOutLineIndex PositiveInteger, upsOutVoltage NonNegativeInteger, upsOutCurrent NonNegativeInteger, upsOutApparentPower NonNegativeInteger, upsOutTruePower NonNegativeInteger, upsOutPowerFactor NonNegativeInteger, upsOutPercentLoad INTEGER, upsOutLineVoltage NonNegativeInteger } upsOutLineIndex OBJECT-TYPE SYNTAX INTEGER (0..10) ACCESS read-only STATUS current DESCRIPTION "The output line identifier." ::= { upsOutEntry 1 } upsOutVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The output voltage of the UPS system." ::= { upsOutEntry 2 } upsOutCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp" ACCESS read-only STATUS current DESCRIPTION "The output current of the UPS system" ::= { upsOutEntry 3 } upsOutApparentPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1VA" ACCESS read-only STATUS current DESCRIPTION "The present output apparent power." ::= { upsOutEntry 4 } upsOutTruePower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1Watts" ACCESS read-only STATUS current DESCRIPTION "The present output true power." ::= { upsOutEntry 5 } upsOutPowerFactor OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.01" ACCESS read-only STATUS current DESCRIPTION "Output true power/apparent power factor " ::= { upsOutEntry 6 } upsOutPercentLoad OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "percent" ACCESS read-only STATUS current DESCRIPTION "The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA." ::= { upsOutEntry 7 } upsOutLineVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The output line voltage of the UPS system. if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase; if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase; if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase." ::= { upsOutEntry 8 } upsOutFrequency OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1Hertz" ACCESS read-only STATUS current DESCRIPTION "The present output frequency." ::= { upsOutEntry 9 } -- =========================================================================== -- upsBypass -- prefix =upsBy -- =========================================================================== upsByFrequency OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Hertz" ACCESS read-only STATUS current DESCRIPTION "The present bypass frequency." ::= { upsBypass 1 } upsByNumLines OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table." ::= { upsBypass 2 } upsByTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsByEntry ACCESS not-accessible STATUS current DESCRIPTION "A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines." ::= { upsBypass 3 } upsByEntry OBJECT-TYPE SYNTAX UpsByEntry ACCESS not-accessible STATUS current DESCRIPTION "An entry containing information applicable to a particular bypass input." INDEX { upsByLineIndex } ::= { upsByTable 1 } UpsByEntry ::= SEQUENCE { upsByLineIndex PositiveInteger, upsByVoltage NonNegativeInteger, upsByCurrent NonNegativeInteger, upsByPower NonNegativeInteger, upsByLineVoltage INTEGER } upsByLineIndex OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS current DESCRIPTION "The bypass line identifier." ::= { upsByEntry 1 } upsByVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The present bypass voltage." ::= { upsByEntry 2 } upsByCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 RMS Amp" ACCESS read-only STATUS current DESCRIPTION "The present bypass current." ::= { upsByEntry 3 } upsByPower OBJECT-TYPE SYNTAX NonNegativeInteger UNITS "0.1Watts" ACCESS read-only STATUS current DESCRIPTION "The present true power conveyed by the bypass." ::= { upsByEntry 4 } upsByLineVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-only STATUS current DESCRIPTION "The present bypass line voltage. if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase; if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase; if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase." ::= { upsByEntry 5 } -- =========================================================================== -- upsTest -- prefix=upsTst -- =========================================================================== upsTstBatteryTest OBJECT-TYPE SYNTAX INTEGER { none(1), battTest10sec(2), battTestUntilLow(3), battTestWithTime(4), battTestCancelTest(5), battTestClearInfo(6) } ACCESS read-write STATUS current DESCRIPTION "This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime." ::= { upsTest 1 } upsTstBatteryTestResult OBJECT-TYPE SYNTAX INTEGER { donePassed(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6) } ACCESS read-only STATUS mandatory DESCRIPTION "The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results." ::= { upsTest 2 } upsTstBatteryTestStartTime OBJECT-TYPE SYNTAX DisplayString (SIZE(19..19)) ACCESS read-only STATUS current DESCRIPTION "The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)" ::= { upsTest 3 } upsTstBatterySettingTime OBJECT-TYPE SYNTAX INTEGER (12..5940) ACCESS read-write STATUS mandatory DESCRIPTION "The object specify the test time for battery test, the unit is seconds" ::= { upsTest 4 } --below 1 minute 0.2-1.0 ,larger than 1 minutes ,1,2,3..99; -- =========================================================================== -- upsControl -- prefix=upsCtl -- =========================================================================== upsCtlShutdownDelay OBJECT-TYPE SYNTAX INTEGER (-2..2147483648) UNITS "seconds" ACCESS read-write STATUS current DESCRIPTION "The delay in seconds the UPS remains on after being told to turn off. if value=-2 cancel shutdown, if value=-1 donothing, value=0 shutdown ups immediately" ::= { upsControl 1 } upsCtlSleepTime OBJECT-TYPE SYNTAX INTEGER (-1..2147483648) UNITS "minutes" ACCESS read-write STATUS current DESCRIPTION "The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsControl 2 } upsCtlStartupAfterDelay OBJECT-TYPE SYNTAX INTEGER (-1..2147483648) UNITS "seconds" ACCESS read-write STATUS current DESCRIPTION "Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. -1 mean not startup. must set upsCtlStartupAfterDelay before upsCtlShutdownDelay , the value must larger than 59 if the value not equal -1 " ::= { upsControl 3 } upsCtlbuzzer OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to 'on' or 'off' to enable or disable buzzer" ::= { upsControl 4 } upsCtlRemoteControlUPS OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to turn 'on' or 'off' UPS " ::= { upsControl 5 } upsCtloutletPoweron OBJECT-TYPE SYNTAX INTEGER (1..2) ACCESS write-only STATUS current DESCRIPTION "Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process" ::= { upsControl 6 } upsCtloutletPoweroff OBJECT-TYPE SYNTAX INTEGER (1..2) ACCESS write-only STATUS current DESCRIPTION "Setting this object to 1 means 1st outlet, 2 means 2nd outlet , immediately process" ::= { upsControl 7 } upsCtlOutlet1Powerofftime OBJECT-TYPE SYNTAX INTEGER (-1..999) ACCESS read-write STATUS current DESCRIPTION "setting this object to -1 means this control not effect, 0 means immediately process, >0 means wait times unit is minutes use in battery mode" ::= { upsControl 8 } upsCtlOutlet2Powerofftime OBJECT-TYPE SYNTAX INTEGER (-1..999) ACCESS read-write STATUS current DESCRIPTION "setting this object to -1 means this control not effect, 0 means immediately process , >0 means wait times unit is minutes .use in battery mode" ::= { upsControl 9 } upsCtlResetConfigure OBJECT-TYPE SYNTAX INTEGER { none(0), reset(1) } ACCESS read-write STATUS current DESCRIPTION " reset all configure para to default." ::= { upsControl 10 } --=========================================================================== -- -- agentConfig -- prefix=agent -- =========================================================================== agentConfigDatetime OBJECT-TYPE SYNTAX DisplayString (SIZE (19..19)) ACCESS read-write STATUS current DESCRIPTION "The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)" ::= { agentConfig 1 } ---====================================================================== -- commConfig -- prefix =comm ---====================================================================== commBaudRate OBJECT-TYPE SYNTAX INTEGER { B1200(1), B2400(2), B4800(3), B9600(4), B19200(5) } ACCESS read-write STATUS current DESCRIPTION "The UPS communicate baudrate" ::= { commConfig 1 } commDatabits OBJECT-TYPE SYNTAX INTEGER (8..9) ACCESS read-write STATUS current DESCRIPTION "The UPS communicate data bits" ::= { commConfig 2 } commStopbits OBJECT-TYPE SYNTAX INTEGER (1..2) ACCESS read-write STATUS current DESCRIPTION "The UPS communicate stop bits " ::= { commConfig 3 } commParity OBJECT-TYPE SYNTAX INTEGER { none(0), odd(1), even(2) } ACCESS read-write STATUS current DESCRIPTION "The UPS communicate Parity " ::= { commConfig 4 } commTimeout OBJECT-TYPE SYNTAX INTEGER (100..1000) ACCESS read-write STATUS current DESCRIPTION "The UPS communicate timeout" ::= { commConfig 5 } --=========================================================================== -- -- upsConfig --prefix=upsCfg -- =========================================================================== upsCfgAlarmbypass OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object enable /disable alarm bypass mode" ::= { upsConfig 1 } upsCfgAlarmbattery OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object enable/disable alarm battery mode" ::= { upsConfig 2 } upsCfgAutoReboot OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object enable/disable auto reboot" ::= { upsConfig 3 } upsCfgBypasswhenupsoff OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object start/stop bypass when ups off" ::= { upsConfig 4 } upsCfgBatterDDP OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable battery deep-discharge protection" ::= { upsConfig 5 } upsCfgConvertermode OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable converter mode " ::= { upsConfig 6 } upsCfgECOmode OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable ECO mode" ::= { upsConfig 7 } upsCfgAdvanceECOmode OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable advance ECO mode" ::= { upsConfig 8 } upsCfgGreenPowerFunction OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable green power function" ::= { upsConfig 9 } upsCfgBatteryOSC OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable battery open status check" ::= { upsConfig 10 } upsCfgAllowShort3times OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable short 3 times" ::= { upsConfig 11 } upsCfgColdstart OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to cold start ups" ::= { upsConfig 12 } upsCfgBypassNotAllowed OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable bypass mode" ::= { upsConfig 13 } upsCfgBatterylowprotect OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable battery low protect" ::= { upsConfig 14 } upsCfgP1progoutletcontrol OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable p1 programmable outlet control (battery mode)" ::= { upsConfig 15 } upsCfgP2progoutletcontrol OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable p2 programmable outlet control (battery mode)" ::= { upsConfig 16 } upsCfgInverterShortClear OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable Inverter short clear function" ::= { upsConfig 17 } upsCfgSitefaildetection OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Setting this object to enable/disable site fail detection" ::= { upsConfig 18 } upsCfgBatNumInParallel OBJECT-TYPE SYNTAX INTEGER (1..99) ACCESS read-write STATUS current DESCRIPTION "Battery numbers in parallel (battery numbers setting)" ::= { upsConfig 19 } upsCfgBatNumInSeries OBJECT-TYPE SYNTAX INTEGER (1..20) ACCESS read-write STATUS current DESCRIPTION "Battery numbers in series (battery numbers setting)" ::= { upsConfig 20 } upsCfgBypassmaxvoltage OBJECT-TYPE SYNTAX INTEGER (1760..2760) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "Bypass mode max voltage" ::= { upsConfig 21 } upsCfgBypassminvoltage OBJECT-TYPE SYNTAX INTEGER (1760..2640) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "Bypass mode min voltage" ::= { upsConfig 22 } upsCfgBypassmaxfrequency OBJECT-TYPE SYNTAX INTEGER (510..700) -- ( 510..600 ,610..700) UNITS "0.1 Hertz" ACCESS read-write STATUS current DESCRIPTION "Bypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)" ::= { upsConfig 23 } upsCfgBypassminfrequency OBJECT-TYPE SYNTAX INTEGER (400..590) --(400..490,500..590) UNITS "0.1 Hertz" ACCESS read-write STATUS current DESCRIPTION "Bypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)" ::= { upsConfig 24 } upsCfgECOmaxvoltage OBJECT-TYPE SYNTAX INTEGER (10..3000) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "ECO mode max voltage" ::= { upsConfig 25 } upsCfgECOminvoltage OBJECT-TYPE SYNTAX INTEGER (10..3000) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "ECO mode min voltage" ::= { upsConfig 26 } upsCfgFreeRunMaxFrequency OBJECT-TYPE SYNTAX INTEGER (400..700) UNITS "0.1 Hertz " ACCESS read-write STATUS current DESCRIPTION "Free run mode max frequency" ::= { upsConfig 27 } upsCfgFreeRunMinFrequency OBJECT-TYPE SYNTAX INTEGER (400..700) UNITS "0.1 Hertz " ACCESS read-write STATUS current DESCRIPTION "Free run mode min frequency" ::= { upsConfig 28 } upsCfgEPOStatus OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-only STATUS current DESCRIPTION "Get EPO status,configured by mamual" ::= { upsConfig 29 } upsCfgQSK1Status OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-only STATUS current DESCRIPTION "Get QSK 1 status" ::= { upsConfig 30 } upsCfgQSK2Status OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-only STATUS current DESCRIPTION "Get QSK 2 status" ::= { upsConfig 31 } upsCfgQSKT1Delaytime OBJECT-TYPE SYNTAX INTEGER (0..999) UNITS "minutes " ACCESS read-only STATUS current DESCRIPTION "Get QSKT 1 time delay" ::= { upsConfig 32 } upsCfgQSKT2Delaytime OBJECT-TYPE SYNTAX INTEGER (0..999) UNITS "minutes " ACCESS read-only STATUS current DESCRIPTION "Get QSKT 2 time delay" ::= { upsConfig 33 } upsCfgConstantPhaseAngle OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1) } ACCESS read-write STATUS current DESCRIPTION "setting this object to Enable/disable Constant Phase Angle function" ::= { upsConfig 34 } ---PE/PD q upsCfgInPhaseAngle OBJECT-TYPE SYNTAX INTEGER { Angle000(0), Angle120(120), Angle180(180), Angle240(240) } ACCESS read-only STATUS current DESCRIPTION "Get input phase angle" ::= { upsConfig 35 } ---QPD upsCfgOutPhaseAngle OBJECT-TYPE SYNTAX INTEGER { Angle000(0), Angle120(120), Angle180(180), Angle240(240) } ACCESS read-write STATUS current DESCRIPTION "Set output phase angle" ::= { upsConfig 36 } ---QPD PPD upsCfgLimiRunOnBatMode OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Enable/disable limited runtime on battery mode" ::= { upsConfig 37 } upsCfgChargingCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Amp DC" ACCESS read-only STATUS current DESCRIPTION "Set charging current to battery ." ::= { upsConfig 38 } upsCfgBatSeftCheckVolt OBJECT-TYPE SYNTAX INTEGER (2400..2800) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "BatTest until battery voltage lower than " ::= { upsConfig 39 } upsCfgOverChargVolt OBJECT-TYPE SYNTAX INTEGER (130..143) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set over charging voltage to per battery" ::= { upsConfig 40 } upsCfgBattUnderVolt OBJECT-TYPE SYNTAX INTEGER (2000..2400) UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set battery under voltage of setting value.value is a number ranging from 200V to 240V" ::= { upsConfig 41 } upsCfgBattLowVolt OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set battery low voltage of setting value.it is 10 to 40V high than battery under voltage. it is 10 to 40V high than battery under voltage.default 20. it means that the battery low point is battery under add 20. for example, if the battery under voltage is 210V, the battry low point voltage is 230V. " ::= { upsConfig 42 } upsCfgIn1VoltHLoss OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set input1 voltage high loss point." ::= { upsConfig 43 } upsCfgIn1VoltLLoss OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set input1 voltage low loss point." ::= { upsConfig 44 } upsCfgIn2VoltHLoss OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set input2 voltage high loss point." ::= { upsConfig 45 } upsCfgIn2VoltLLoss OBJECT-TYPE SYNTAX INTEGER UNITS "0.1 Volts" ACCESS read-write STATUS current DESCRIPTION "set input2 voltage low loss point." ::= { upsConfig 46 } upsCfgBatteryTurnOn OBJECT-TYPE SYNTAX INTEGER { disable(0), enable(1), notsupport(2) } ACCESS read-write STATUS current DESCRIPTION "Enable/disable battery turn on." ::= { upsConfig 47 } -- =========================================================================== -- upsTraps -- prefix = upsTraps -- Traps group -- =========================================================================== -- This section defines the well-known notifications sent by -- UPS agents. -- this traps use one share trap-node for send traps ,the trap-node vlaue between 1 and 127. -- the share trap-node name is trapleafnodev1v2; -- if failure or warning occur ,traps send immediately , if question not resolved,agent will resend every 4 seconds. -- info only send once trapleafnodev103 OBJECT-TYPE SYNTAX DisplayString (SIZE (16..16)) ACCESS not-accessible STATUS current DESCRIPTION "The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node char trap[16]; trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap" ::= { upsTraps 998 } trapleafnodev1v2 OBJECT-TYPE SYNTAX INTEGER (0..255) ACCESS not-accessible STATUS current DESCRIPTION "The share trap-node for send all traps" ::= { upsTraps 999 } cmpACFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "AC failure" ::= 1 cmpFanFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Fan failure" ::= 2 cmpUPSFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "UPS failure" ::= 3 cmpChargerFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Charger failure" ::= 4 cmpOverloadFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Overload failure" ::= 5 cmpOvertempFailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Over temperature fault." ::= 6 cmpInvertershortcircuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter short-circuited" ::= 7 cmpbatteryfusebeingoc TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery fuse being open-dcircuited failure" ::= 8 cmpLowbattery TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "The UPS has returned from a low battery condition." ::= 9 cmpSysgotoshutdown TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "System is going to shutdown" ::= 10 cmpSitefault TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Site fault" ::= 11 cmpPhasesequenceincorrect TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Phase sequence incorrect" ::= 12 cmpPhasesequenceincorrectbypass TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Phase sequence incorrect in bypass" ::= 13 cmpFanalarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Fan alarm." ::= 14 cmpEPOenabled TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EPO enabled" ::= 15 cmpUnabletotrunonUPS TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Unalbe to turn on UPS" ::= 16 cmpOvertemperaturealarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Over temperature alarm" ::= 17 cmpInputfrequnstablebypass TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Input frequency unstable in bypass" ::= 18 cmpChargeralarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Charger alarm" ::= 19 cmpL1inputfusenotwork TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L1 input fuse not working" ::= 20 cmpNeutralnotConnected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Neutral not connected" ::= 21 cmpL2inputfusenotwork TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L2 input fuse not working" ::= 22 cmpL3inputfusenotwork TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L3 input fuse not working" ::= 23 cmpPositivePFCabnormalL1 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Positive PFC abnormal in L1" ::= 24 cmpNegativePFCabnormalL1 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Negative PFC abnormal in L1" ::= 25 cmpPositivePFCabnormalL2 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Positive PFC abnormal in L2" ::= 26 cmpNegativePFCabnormalL2 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Negative PFC abnormal in L2" ::= 27 cmpPositivePFCabnormalL3 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Positive PFC abnormal in L3" ::= 28 cmpNegativePFCabnormalL3 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Negative PFC abnormal in L3" ::= 29 cmpBusvoltagenotwds TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bus voltage not within default setting" ::= 30 cmpBusvoltageovermaxvalue TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bus voltage over maxinum value" ::= 31 cmpBusvoltagebelowminvalue TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bus voltage below mininum value" ::= 32 cmpBusvoltagediffoutofrange TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bus voltage differences out fo acceptable range" ::= 33 cmpBusvoltageofsloperatetoofast TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bus voltage of slope rate drops too fast" ::= 34 cmpOvercurrentinPFCII TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "WARNING:Over current in PFC input inductor." ::= 35 cmpInvertervoloutofrange TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter voltage not within default setting." ::= 36 cmpInvertervolovermaxvalue TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter voltage over maximum value." ::= 37 cmpInvertervolbelowminvalue TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter voltage below minimum value." ::= 38 cmpBatteryoppositelyconnected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery oppositely connected." ::= 39 cmpL2phaseshortcicuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L2Phase inverter short-cicuited." ::= 40 cmpL3phaseshortcicuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L3Phase inverter short-cicuited." ::= 41 cmpL1L2invertershortcicuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L1L2Inverter short-cicuited." ::= 42 cmpL2L3invertershortcicuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L2L3Inverter short-cicuited." ::= 43 cmpL3L1invertershortcicuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L3L1Inverter short-cicuited." ::= 44 cmpL1negativepoweroutofrange TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L1 inverter negative powere out of acceptable range." ::= 45 cmpL2negativepoweroutofrange TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L2 inverter negative powere out of acceptable range." ::= 46 cmpL3negativepoweroutofrange TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "L3 inverter negative powere out of acceptable range." ::= 47 cmpBatterySCRshortcircuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery SCR short-circuited." ::= 48 cmpLineSCRshortcircuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Line SCR short-circuited." ::= 49 cmpInverterrelayopenfault TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter relay open fault." ::= 50 cmpInverterrelayshortcircuited TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter relay short-circuited." ::= 51 cmpInoutwiresoppositelyconnected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Input and output wires oppositely connected." ::= 52 cmpabnormalcanbuscommunication TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Abnormal in CAN-bus communication." ::= 53 cmpcommfailurebcupsboard TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Communication failure between cpus in control board.Or DSP and MCU communication error" ::= 54 cmpabnormalsyncsignalcircuit TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Abnomal in synchronous signal circuit." ::= 55 cmpabnormalsyncpulsesignalcircuit TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Abnomal in synchronous pulse signal circuit." ::= 56 cmpcurrent3punbalancedetected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Warning for a three-phase input current unbalance detected." ::= 57 cmpbatteryselftestfailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery self-test failure." ::= 58 cmpintercurrentunbalance TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Inverter inter-current unbalance." ::= 59 cmpbatterydisconnected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery disconnected." ::= 60 cmpabnormalhostsignalcircuit TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Abnormal in host signal circuit." ::= 61 cmpbatteryovercharged TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bettery overcharged." ::= 62 cmpbatteryvoltoohigh TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bettery voltage is too high." ::= 63 cmpbatteryvoltoolow TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bettery voltage is too low." ::= 64 cmpfemaleconnectornotconnwell TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Female connector of parallel cable not connected well." ::= 65 cmpmaleconnectornotconnwell TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Male connector of parallel cable not connected well." ::= 66 cmplockingbypassA3COW30M TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Locking inbypass mode after 3 consecutive overloads within 30 minutes" ::= 67 cmpparallelcabledisconnected TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Parallel cable disconnected" ::= 68 cmpsyncpulsecircuitfault TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Synchronous pulse signal circuit fault" ::= 69 cmpsyncsignalcircuitfalt TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Synchronous signal circuit fault" ::= 70 cmphostsignalcircuitfault TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Host signal circuit fault" ::= 71 cmpcanbuscommunicationfault TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Can-bus communication fault" ::= 72 cmplowlosspointforvolinACmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Low loss point for voltage in ac mode not consistent in parallel systems" ::= 73 cmphighlosspointforvolinACmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "High loss point for voltage in ac mode not consistent in parallel systems" ::= 74 cmplowlosspointforfreqinACmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Low loss point for frequency in ac mode not consistent in parallel systems" ::= 75 cmphighlosspointforfreqinACmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "High loss point for frequency in ac mode not consistent in parallel systems" ::= 76 cmplowlosspointforvolinbypassmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Low loss point for voltage in bypass mode not consistent in parallel systems" ::= 77 cmphighlosspointforvolinbypassmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "High loss point for voltage in bypass mode not consistent in parallel systems" ::= 78 cmplowlosspointforfreqinbypassmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Low loss point for frequency in bypass mode not consistent in parallel systems" ::= 79 cmphighlosspointforfreqinbypassmode TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "High loss point for frequency in bypass mode not consistent in parallel systems" ::= 80 cmploadunbalanced TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Load unbalanced" ::= 81 cmpoverloadalarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Overload alarm" ::= 82 cmpparallelnotconnectedwell TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Parallel cable not connected well" ::= 83 cmpcommunicationlost TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Communication lost" ::= 84 cmpbatteryconnnotsonsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery connection not consistent in parallel systems" ::= 85 cmpconverternotconsisstent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Converter setting not consistent in parallel systems" ::= 86 cmpbypassnotallownotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bypass not allowed setting not consistent in parallel systems" ::= 87 cmpACconnnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "AC connection not consistent in parallel systems" ::= 88 cmpinput3pcurrentunbalance TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Warning for three-phase ac input current unbalance" ::= 89 cmpbypassconnnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bypass connection not consistent in parallel systems" ::= 90 cmpbatteryprotectionnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery protection setting not consistent in parallel systems" ::= 91 cmpbatterydetectionnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery detection setting not consistent in parallel systems" ::= 92 cmpupsmodeltypesnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "UPS model types not consistent in parallel systems" ::= 93 cmpbypassnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bypass setting not consistent in parallel systems" ::= 94 cmpcapacitynotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Capacity of upss not consistent in parallel systems" ::= 95 cmpautorestartnotconsistent TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Auto restart setting not consistent in parallel systems" ::= 96 cmpBatteryReplace TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery need to be replace" ::= 97 cmpACNormal TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "AC normal" ::= 100 cmpOutputBadAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Output bad alarm" ::= 103 cmpBypassBadAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Bypass bad alarm" ::= 104 cmpOutputOffAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Output off alarm" ::= 105 cmpUPSShutAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "UPS shutdown alarm" ::= 106 cmpSystemOffAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "System off alarm" ::= 107 cmpFuseFailureAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Fuse failure alarm" ::= 108 cmpGenFailureAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "General failure alarm" ::= 109 cmpAwaitPowerAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Awaiting power alarm" ::= 110 cmpShutPendingAlarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Shutdown pending alarm" ::= 111 cmpBatDepleted TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery depleted" ::= 112 cmpUnknowStatus TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery unknow status" ::= 113 cmpOutputOn TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Output on" ::= 114 cmpTurntobypass TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Ups turn to bypass mode" ::= 115 cmpTurntobattery TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Ups turn to battery mode" ::= 116 cmpOutBooster TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Turn to booster" ::= 117 cmpOutReducer TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Turn to reducer" ::= 118 cmpOutBattest TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Turn to battery test mode" ::= 119 cmpOtherSource TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Other source" ::= 120 cmpBatfailure TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery failure" ::= 121 cmpBatTestDonePassed TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery test passed" ::= 122 cmpBatTestDoneWarning TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery test done warning " ::= 123 cmpBatTestDoneAborted TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery test done Aborted" ::= 124 cmpBatteryNormal TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery normal" ::= 125 cmpBatteryDischarging TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Battery Discharging " ::= 126 cmpP1cutoffprealarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "P1 cut off pre-alarm " ::= 127 cmpInputPhaseError TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Warning for input phase error for LV 6-10K UPS" ::= 128 cmpMaintainSwitchOpenalarm TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "Warning for maintain switch open" ::= 129 cmpEMDChAbnormal1 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 1 Abnormal" ::= 130 cmpEMDChAbnormal2 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 2 Abnormal" ::= 131 cmpEMDChAbnormal3 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 3 Abnormal" ::= 132 cmpEMDChAbnormal4 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 4 Abnormal" ::= 133 cmpEMDChAbnormal5 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 5 Abnormal: smoke alarm" ::= 134 cmpEMDChAbnormal6 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 6 Abnormal" ::= 135 cmpEMDChAbnormal7 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 7 Abnormal" ::= 136 cmpEMDChAbnormal8 TRAP-TYPE ENTERPRISE upsTraps DESCRIPTION "EMD Channels 8 Abnormal" ::= 137 --=============================================================================== --extend --=============================================================================== extendWorkTemperature OBJECT-TYPE SYNTAX INTEGER (-2200..2200) UNITS "degrees 0.1 Centigrade" ACCESS read-only STATUS current DESCRIPTION "The temperature of work environment" ::= { extend 1 } extendWorkhumidity OBJECT-TYPE SYNTAX INTEGER (0..100) UNITS "percent" ACCESS read-only STATUS current DESCRIPTION "The humidity of work environment" ::= { extend 2 } extendSmokeScope OBJECT-TYPE SYNTAX INTEGER (0..1000000) UNITS "%/FOOT" ACCESS read-only STATUS current DESCRIPTION "The smokeScope of work environment" ::= { extend 3 } extendEMDAlarm1 OBJECT-TYPE SYNTAX INTEGER { on(1), off(0) } ACCESS read-only STATUS current DESCRIPTION "Environment detector alarm 1" ::= { extend 4 } extendEMDAlarm2 OBJECT-TYPE SYNTAX INTEGER { on(1), off(0) } ACCESS read-only STATUS current DESCRIPTION "Environment detector alarm 2" ::= { extend 5 } extendEMDAlarm3 OBJECT-TYPE SYNTAX INTEGER { on(1), off(0) } ACCESS read-only STATUS current DESCRIPTION "Environment detector alarm 3" ::= { extend 6 } extendEMDAlarm4 OBJECT-TYPE SYNTAX INTEGER { on(1), off(0) } ACCESS read-only STATUS current DESCRIPTION "Environment detector alarm 4" ::= { extend 7 } END